Computation of EMI fields in a high voltage gas insulated substation during switching operations

被引:0
|
作者
Rao, MM [1 ]
Thomas, MJ [1 ]
Singh, BP [1 ]
机构
[1] BHEL R&D, Hyderabad, Andhra Pradesh, India
关键词
EMI; gas insulated substation; switching; disconnector; circuit breaker;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Numerical characterisation of the transient eletromagnetic field generated in a gas insulated substation during the operation of a disconnector switch or a circuit breaker is essential when sensitive control devices using VLSI circuits are being used in modern gas insulated substations. The quantification of emission levels from the gas insulated equipment during switching events is found to be important for the EMC design of control devices operating in such harsh EM environment and hence to ensure reliable operation of the systems. In the present study, transient electromagnetic field em fission from gas to air bushing through the silicon rubber ins alated housing has been quantified for Very Fast Transient Currents (VFTC) which are generated during switching events in a 245 kV GIS. For this purpose, the modified version of Finite Difference Time Domain (FDTD) technique has been adopted. For the estimation of transient field emission levels, a computational model has bean developed for the 245 kV gas to air bushing. The variation of EM field pattern along the axis of the bushing at various radial distances is plotted and the effect of parameters like frequency of transient current, physical positioning of the bushing above the ground plane etc., on emission levels is analysed as a part of the present study. The range of enhancement factors of the transient field levels due to the presence of a metallic structure on the ground plane, which simulates the control cubicle in a GIS is established. Finally, the transient EM field emission levels from the gas to air bushing for the VFTC waveform calculated at the entrance of the bushing are evaluated.
引用
收藏
页码:743 / 748
页数:6
相关论文
共 50 条
  • [21] MODULARIZATION OF HIGH VOLTAGE GAS INSULATED SUBSTATIONS
    D'Souza, Merwyn
    Dhara, Ravi S.
    Bouyer, Rene C.
    2018 IEEE INDUSTRY APPLICATIONS SOCIETY 65TH ANNUAL PETROLEUM AND CHEMICAL INDUSTRY TECHNICAL CONFERENCE (PCIC), 2018, : 305 - 312
  • [23] Study of Transient Enclosure Voltage Coupling to Secondary Cables in a Gas-Insulated Substation
    Cai, Yuanji
    Guan, Yonggang
    Liu, Weidong
    He, Jiaxi
    IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (02) : 761 - 768
  • [24] Prediction of switching transient electromagnetic fields in gas-insulated substations
    Lu, TB
    Cui, X
    Ianoz, M
    Tabara, D
    2002 3RD INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY, 2002, : 182 - 185
  • [25] Dynamic reactive power/voltage optimization control of substation considering the number of switching operations
    Yang, Su-Qin
    Han, Nian-Hang
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2010, 38 (24): : 131 - 136
  • [26] Influence of Surface Charge on Flashover Voltage of Gas Insulated Substation Basin Insulator under AC and DC Voltage
    Qi B.
    Gao C.
    Zhao L.
    Li C.
    Tu Y.
    Gaodianya Jishu/High Voltage Engineering, 2017, 43 (03): : 915 - 922
  • [27] Research on Lightning Over-Voltage in 1000kV Gas Insulated Switchgear Substation
    Zhang, Yu
    Xu, Wei
    Liu, Nian
    Zhang, Yunhong
    Hu, Jiefeng
    Zhu, Jianguo
    38TH ANNUAL CONFERENCE ON IEEE INDUSTRIAL ELECTRONICS SOCIETY (IECON 2012), 2012, : 6212 - 6217
  • [28] Case Study-80 kA Gas Insulated Substation Bergen Switching Station - New Jersey
    Labos, William
    Grossmann, Peter
    2014 IEEE PES T&D CONFERENCE AND EXPOSITION, 2014,
  • [29] Conducted immunity requirements for equipment operational during high voltage network switching operations
    Stewart, MG
    Siew, WH
    Walker, KF
    Barrack, CS
    Campbell, LC
    Shen, L
    Muir, F
    IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2001, 148 (05) : 391 - 396
  • [30] Analysis of VFTO during the failure of a 550-kV gas-insulated substation
    Moreira, D. C.
    Nunes, M. V. A.
    Moreira, D. D. C.
    Costa, D. K. D.
    ELECTRIC POWER SYSTEMS RESEARCH, 2020, 189