Modeling of breakdown during the post-arc phase of a vacuum circuit breaker

被引:23
|
作者
Sarrailh, P. [1 ,2 ]
Garrigues, L. [1 ,2 ]
Boeuf, J. P. [1 ,2 ]
Hagelaar, G. J. M. [1 ,2 ]
机构
[1] Univ Toulouse, UPS, INPT, LAPLACE Lab Plasma & Convers Energie, F-31062 Toulouse 9, France
[2] CNRS, LAPLACE, F-31062 Toulouse, France
来源
PLASMA SOURCES SCIENCE & TECHNOLOGY | 2010年 / 19卷 / 06期
关键词
FIELD; INTERRUPTION; TEMPERATURE; ELECTRONS; EMISSION; COPPER;
D O I
10.1088/0963-0252/19/6/065020
中图分类号
O35 [流体力学]; O53 [等离子体物理学];
学科分类号
070204 ; 080103 ; 080704 ;
摘要
After a high-current interruption in a vacuum circuit breaker (VCB), the electrode gap is filled with a high density copper vapor plasma in a large copper vapor density (similar to 10(22) m(-3)). The copper vapor density is sustained by electrode evaporation. During the post-arc phase, a rapidly increasing voltage is applied to the gap, and a sheath forms and expands, expelling the plasma from the gap when circuit breaking is successful. There is, however, a risk of breakdown during that phase, leading to the failure of the VCB. Preventing breakdown during the post-arc phase is an important issue for the improvement of VCB reliability. In this paper, we analyze the risk of Townsend breakdown in the high copper vapor density during the post-arc phase using a numerical model that takes into account secondary electron emission, volume ionization, and plasma and neutral transport, for given electrode temperatures. The simulations show that fast neutrals created in the cathode sheath by charge exchange collisions with ions generate a very large secondary electron emission current that can lead to Townsend breakdown. The results also show that the risk of failure of the VCB due to Townsend breakdown strongly depends on the electrode temperatures (which govern the copper vapor density) and becomes important for temperatures greater than 2100 K, which can be reached in vacuum arcs. The simulations also predict that a hotter anode tends to increase the risk of Townsend breakdown.
引用
收藏
页数:9
相关论文
共 50 条
  • [1] Plasma decay modeling during the post-arc phase of a. vacuum circuit breaker
    Sarrailh, P.
    Garrigues, L.
    Hagelaar, G. J. M.
    Boeuf, J. -P.
    Sandolache, G.
    Rowe, S. W.
    [J]. ISDEIV 2008: PROCEEDINGS OF THE XXIIIRD INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, VOLS 1 AND 2, 2008, : 406 - +
  • [2] Study on the Proportions of Charged Particles Absorbed by Post-arc Anode in the Post-arc Phase of a Vacuum Circuit Breaker
    Mo, Yongpeng
    Shi, Zongqian
    Jia, Shenli
    Wang, Lijun
    [J]. PROCEEDINGS OF THE 27TH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM (ISDEIV), VOL 1, 2016, : 337 - 340
  • [3] Two-dimensional simulation of the post-arc phase of a vacuum circuit breaker
    Sarrailh, Pierre
    Garrigues, Laurent
    Hagelaar, Gerjan J. M.
    Boeuf, Jean-Pierre
    Sandolache, Gabriela
    Rowe, Stephan W.
    Jusselin, Benoit
    [J]. IEEE TRANSACTIONS ON PLASMA SCIENCE, 2008, 36 (04) : 1046 - 1047
  • [4] Experimental investigations on the post-arc current of the vacuum circuit breaker in an active mechanical DC circuit breaker
    Jia, Shenli
    Tang, Qiang
    Shi, Zongqian
    Mo, Yongpeng
    [J]. AIP ADVANCES, 2021, 11 (05)
  • [5] Research on Measurement of Post-Arc Current of Mechanical Vacuum DC Circuit Breaker
    Cheng X.
    Xu P.
    Ge G.
    Li X.
    Tian X.
    [J]. Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2021, 36 (16): : 3516 - 3524
  • [6] Simulation of post-arc dielectric recovery characteristics of DC vacuum circuit breaker
    Liu, Xiaoming
    Yu, Deen
    Zou, Jiyan
    [J]. Zhenkong Kexue yu Jishu Xuebao/Journal of Vacuum Science and Technology, 2014, 34 (12): : 1285 - 1289
  • [7] Analysis of the Influence Factors of Post-Arc Dielectric Recovery on DC Vacuum Circuit Breaker
    Liu X.
    Shi H.
    Chen H.
    Jiang W.
    Zhou Y.
    Zou J.
    Tian J.
    [J]. Gongcheng Kexue Yu Jishu/Advanced Engineering Sciences, 2023, 55 (03): : 40 - 47
  • [8] Research on post-arc currents in vacuum circuit breaker and their analysis with reference to breaking mechanism
    Chmielak, Waldemar
    Pochanke, Zbigniew
    [J]. PRZEGLAD ELEKTROTECHNICZNY, 2010, 86 (11B): : 189 - 192
  • [9] Diagnosis of Post-Arc Residual Plasma in Vacuum Breaker
    Zhang Bohao
    [J]. 6TH INTERNATIONAL CONFERENCE ON ADVANCES IN ENERGY RESOURCES AND ENVIRONMENT ENGINEERING, 2021, 647
  • [10] Post-arc current in low voltage vacuum circuit breaker: Measurements and physical peculiarities
    Pavelescu, D
    Nitu, S
    Dumitrescu, G
    Anghelita, P
    [J]. ISDEIV: XXTH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, PROCEEDINGS, 2002, 20 : 67 - 70