Mesh fractal dimension detection on single-phrase-to-earth fault in the non-solidly earthed network

被引:0
|
作者
Zhao, CY [1 ]
Guo, YF [1 ]
机构
[1] N China Elect Power Univ, Sch Elect Engn, Baoding 071003, Hebei, Peoples R China
关键词
non-solidly earthed network; single-phrase-to-earth fault; identification of faulted line; fractal; mesh fractal dimension; GROUND NEUTRAL SYSTEM; LOCATION;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The most frequent fault type is single-phrase-to-earth fault in the non-solidly earthed network. After analyzing the characteristics of the existing methods about identifying the faulted fine in the non-solidly earthed network, the characteristics of the fault-current waveforms are analyzed deeply and a new method using mesh fractal dimension is presented. The mesh fractal dimension of zero-order currents of faulty line and normal line are calculated and compared, the faulted line can be determined correctly. The selecting result on fault feeder is out of all relation to the CT's polarity. The new method is right to be applied to neutral point unearthed system and neutral point ineffective earthed system. The fault line can be confirmed even when intermittent arc earth faults occur. Simulations of various earth faults under different conditions are performed using MATLAB. The results show the method is feasible and effective.
引用
收藏
页码:752 / 756
页数:5
相关论文
共 32 条
  • [31] Single Line to Ground Fault Detection in a Non-Effectively Grounded Distribution Network
    Wang, Xiaowei
    Gao, Jie
    Wei, Xiangxiang
    Zeng, Zhihui
    Wei, Yanfang
    Kheshti, Mostafa
    IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (06) : 3173 - 3186
  • [32] Single phase fault detection technique based on transient current and its application in non-solid grounded network
    Xu, BY
    Xue, YD
    Jing, L
    Yu, C
    SEVENTH INTERNATIONAL CONFERENCE ON DEVELOPMENTS IN POWER SYSTEM PROTECTION, 2001, (479): : 141 - 144