Mesh fractal dimension detection on single-phrase-to-earth fault in the non-solidly earthed network

被引:0
|
作者
Zhao, CY [1 ]
Guo, YF [1 ]
机构
[1] N China Elect Power Univ, Sch Elect Engn, Baoding 071003, Hebei, Peoples R China
关键词
non-solidly earthed network; single-phrase-to-earth fault; identification of faulted line; fractal; mesh fractal dimension; GROUND NEUTRAL SYSTEM; LOCATION;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The most frequent fault type is single-phrase-to-earth fault in the non-solidly earthed network. After analyzing the characteristics of the existing methods about identifying the faulted fine in the non-solidly earthed network, the characteristics of the fault-current waveforms are analyzed deeply and a new method using mesh fractal dimension is presented. The mesh fractal dimension of zero-order currents of faulty line and normal line are calculated and compared, the faulted line can be determined correctly. The selecting result on fault feeder is out of all relation to the CT's polarity. The new method is right to be applied to neutral point unearthed system and neutral point ineffective earthed system. The fault line can be confirmed even when intermittent arc earth faults occur. Simulations of various earth faults under different conditions are performed using MATLAB. The results show the method is feasible and effective.
引用
收藏
页码:752 / 756
页数:5
相关论文
共 32 条
  • [1] LC resonance mechanism analysis of fault transient for single phase earth fault in non-solidly earthed network
    Xue Yong-duan
    Xue Wen-jun
    Xu Bing-yin
    2013 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PES), 2013,
  • [2] Earthing fault detection based on electromagnetic field in non-solidly earthed network
    Sun, Bo
    Sun, Tongjing
    Xue, Yongduan
    Xu, Bingyin
    Han, Jinlu
    Dianli Zidonghua Shebei / Electric Power Automation Equipment, 2009, 29 (07): : 43 - 47
  • [3] Earth fault location based on transient phase current in non-solidly earthed network
    Sun, B. (sunbo@sdu.edu.cn), 1600, Power System Protection and Control Press (40):
  • [4] Simulation Analysis of Arc Grounding Fault in Non-solidly Earthed Network
    Li, Shurong
    Xue, Yongduan
    Xu, Bingyin
    2017 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, 2017,
  • [5] Earth fault protection in non-solidly earthed network based on transient zero sequence current comparison
    Xue, Yongduan
    Feng, Zuren
    Xu, Bingyin
    Chen, Yu
    Li, Jing
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2003, 27 (09): : 48 - 53
  • [6] Single-phase Grounding Fault Detection in Non-solidly Earthed Network Based on Low-voltage Measurements
    Zhang M.
    Luan W.
    Ai X.
    Xu B.
    Dianwang Jishu/Power System Technology, 2023, 47 (08): : 3457 - 3466
  • [7] Single phase to ground fault section location based on transient signals in non-solidly earthed network
    Sun, Bo
    Sun, Tongjing
    Xue, Yongduan
    Xu, Bingyin
    Ji, Tao
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2008, 32 (03): : 52 - 55
  • [8] Approximate Entropy Based Fault Localization and Fault Type Recognition for Non-solidly Earthed Network
    Pang, Qingle
    Liu, Xinyun
    Sun, Bo
    Ling, Qunli
    MEASUREMENT SCIENCE REVIEW, 2012, 12 (06): : 309 - 313
  • [9] Fault line selection in non-solidly earthed network based on direction traveling wave
    Zhang, Fan
    Pan, Zhen-Cun
    Zhang, Hui-Fen
    Zheng, Gang
    Ma, Shan-Shan
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2007, 27 (34): : 70 - 75
  • [10] Fault Line Selection in Non-solidly Earthed Network Based on Modulus Maximum Polarity
    Zhang, Yuanyuan
    Gong, Qingwu
    Chen, Daojun
    2009 INTERNATIONAL CONFERENCE ON MEASURING TECHNOLOGY AND MECHATRONICS AUTOMATION, VOL I, 2009, : 661 - 664