Effects of hot SF6 on post-arc circuit breaker design

被引:25
|
作者
Uchii, T [1 ]
Nishiwaki, S
Boggs, S
机构
[1] TM T&D Corp, Kawasaki, Kanagawa 2100862, Japan
[2] Univ Toronto, Dept Elect & Comp Engn, Toronto, ON, Canada
[3] Univ Connecticut, Dept Elect Engn, Elect Insulat Res Ctr, Storrs, CT 06269 USA
[4] Univ Connecticut, Dept Phys, Elect Insulat Res Ctr, Storrs, CT 06269 USA
关键词
Arc; gas circuit breaker; SF6; transient recovery voltage;
D O I
10.1109/TPWRD.2003.820210
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
SF6 is blown through the arc during interruption of an SF6 puffer circuit breaker. This hot gas flows down an exhaust tube into the chamber of a dead tank circuit breaker where it can lower the dielectric withstand between the exhaust tube and the tank of the circuit breaker, leading to dielectric breakdown during the transient recovery voltage after clearing. This paper presents experimental evidence that any such breakdown is controlled by,the hot gas near the exhaust tube, with cold gas in the remainder of gap having little effect on the breakdown voltage. This experimental conclusion is supported by a detailed theory for conditions under which breakdown can occur.
引用
收藏
页码:124 / 130
页数:7
相关论文
共 50 条
  • [21] Analysis of Dielectric Breakdown of Hot SF6 Gas in a Gas Circuit Breaker
    Kim, Hong-Kyu
    Chong, Jin-Kyo
    Song, Ki-Dong
    [J]. JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2010, 5 (02) : 264 - 269
  • [22] Experimental investigations on the post-arc current of the vacuum circuit breaker in an active mechanical DC circuit breaker
    Jia, Shenli
    Tang, Qiang
    Shi, Zongqian
    Mo, Yongpeng
    [J]. AIP ADVANCES, 2021, 11 (05)
  • [23] Design of intelligent temperature control system of SF6 circuit breaker to prevent SF6 from liquefaction
    Lin, Hai-tao
    Cao, Chun-cheng
    Luo, Yong-li
    Xue, Qing-kuan
    Cheng, Xian
    [J]. 2017 4TH INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT-SWITCHING TECHNOLOGY (ICEPE-ST), 2017, : 885 - 889
  • [24] Study on the effect of arc chamber structures on the post-arc characteristics of generator circuit breaker
    Yin, Jianning
    Zhao, Yongyong
    Duan, Jiandong
    Liang, Shuhua
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2024, 233
  • [25] Study on arc-flow interaction for a high voltage SF6 circuit breaker
    Liu, Xiao-Ming
    Cao, Yun-Dong
    Wang, Er-Zhi
    [J]. Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2005, 25 (07): : 151 - 155
  • [26] Measurements of particle concentrations in an SF6 arc plasma of an electrical circuit-breaker
    Ciobanu, SS
    Fleurier, C
    Hong, D
    Fiévet, C
    [J]. PROGRESS IN PLASMA PROCESSING OF MATERIALS 1997, 1997, : 247 - 254
  • [27] Pressure and Arc Voltage Measurement in a 252 kV SF6 Puffer Circuit Breaker
    Zhong Jianying
    Guo Yujing
    Zhang Hao
    [J]. PLASMA SCIENCE & TECHNOLOGY, 2016, 18 (05) : 490 - 493
  • [29] Pressure and Arc Voltage Measurement in a 252 kV SF6 Puffer Circuit Breaker
    钟建英
    郭煜敬
    张豪
    [J]. Plasma Science and Technology, 2016, (05) : 490 - 493
  • [30] The arc chamber flow field control of unload breaking of SF6 circuit breaker
    Jin, LJ
    Huang, JQ
    Ma, ZY
    Cao, LX
    [J]. PROCEEDINGS OF THE FOURTH INTERNATIONAL CONFERENCE ON ELECTROMAGNETIC FIELD PROBLEMS AND APPLICATIONS, 2000, : 403 - 405