Interruption of Low-Voltage DC Arc in Air Under Axial Magnetic Field

被引:7
|
作者
Islam, Asif [1 ]
Birtwhistle, David [2 ]
Saha, Tapan K. [2 ]
Islam, Mohammad Shariful [1 ]
机构
[1] NOJA Power Ltd, R&D & Testing Dept, Brisbane, Qld, Australia
[2] Univ Queensland, Sch ITEE, Power & Energy Syst Res Grp, Brisbane, Qld, Australia
关键词
Magnetic fields; Electrodes; Magnetic field measurement; Fuses; Magnetic circuits; Current measurement; Switches; Free-burning arc; thermal breakdown; axial magnetic field; current interruption; arc movement speed; VELOCITY;
D O I
10.1109/TPWRD.2019.2932456
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper represents the findings from our research in which a series of experiments were conducted on dc current interruption in air in axial magnetic field provided from rare earth magnets mounted in the test electrodes. The experimental range was as follows: arc voltage 80-100 V, arc length 5-10 mm, arc current 80-800 A, and applied field 35-2400 G. The free-burning arc diameter was measured in these experiments from high-speed photographs. It was found that a strong magnetic field can improve the interruption capacity of air-arc significantly. In the experiments, the successful switching time of both 220 and 330 A free-burning air-arc in 2.4 kG was less than half of the successful switching time of corresponding free-burning arcs in air. For higher current arcs, the outcome was more encouraging. An 800 A free-burning arc sustained for about 48 ms, whereas a 315 G field interrupted it within 8 ms. The information found on arc-root diameter and current density of 80-800 A free-burning arcs in air has filled a gap of data found in the literature. This information, in turn, will help to improve the theories available on free-burning arcs.
引用
收藏
页码:977 / 986
页数:10
相关论文
共 50 条
  • [21] Investigation of Vacuum Arc Voltage Characteristics Under Different Axial Magnetic Field Profiles
    Jia Shenli
    Song Xiaochuan
    Huo Xintao
    Shi Zongqian
    Wang Lijun
    PLASMA SCIENCE & TECHNOLOGY, 2010, 12 (06) : 729 - 733
  • [22] ELECTRONICALLY CONTROLLED SPECTROGRAPHIC LOW-VOLTAGE SPARK, INTERRUPTED ARC AND DC ARC SOURCE
    BARDOCZ, A
    SPECTROCHIMICA ACTA, 1955, 7 (04): : 238 - 241
  • [23] Signatures of Series Arc Faults to Aid Arc Detection in Low-Voltage DC Systems
    Ananthan, Sundaravaradan Navalpakkam
    Bastos, Alvaro Furlani
    Santoso, Surya
    Feng, Xianyong
    Penney, Charles
    Gattozzi, Angelo
    Hebner, Robert
    2020 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM), 2020,
  • [24] LOW-VOLTAGE ARC SUSTAINABILITY
    Eblen, Marcia
    Short, Tom
    2017 IEEE IAS ELECTRICAL SAFETY WORKSHOP (ESW), 2017,
  • [25] Voltage Differential Protection for Series Arc Fault Detection in Low-Voltage DC Systems
    Ananthan, Sundaravaradan Navalpakkam
    Feng, Xianyong
    Penney, Charles
    Gattozzi, Angelo
    Hebner, Robert
    Santoso, Surya
    INVENTIONS, 2021, 6 (01) : 1 - 12
  • [26] Low-Voltage ARC Sustainability
    Eblen, Marcia L.
    Short, Tom A.
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2018, 54 (03) : 2934 - 2946
  • [27] Vacuum arc transient behaviors and voltage characteristics in low-current DC interruption under rotating TMF
    Ma, Hui
    Wang, Jingyi
    Liu, Shaowei
    Hu, Feiliang
    Liu, Zhiyuan
    Geng, Yingsan
    Wang, Jianhua
    AIP ADVANCES, 2020, 10 (08)
  • [28] Dielectric Strength Recovery After Gas Arcs of Low-Voltage DC Hybrid Interruption
    Zhou, Wenliang
    Wu, Yi
    Niu, Chunping
    Sun, Hao
    He, Xubo
    Chen, Xiabo
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2024, 31 (01) : 330 - 338
  • [29] Development of High Resolution Magnetic Field Measurements for Switching Arc Diagnosis of Low-Voltage Switchgear
    Reil, Christian
    Schmidt, Hans-Peter
    2017 IEEE AFRICON, 2017, : 1185 - 1188
  • [30] Voltage of the vacuum arc with a ring anode in an axial magnetic field
    Keidar, M
    Beilis, II
    Boxman, RL
    Goldsmith, S
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 1997, 25 (04) : 580 - 585