Experimental investigation of a counter-flow heat pump driven liquid desiccant dehumidification system

被引:30
|
作者
Liu, Xiaohua [1 ]
Xie, Ying [1 ]
Zhang, Tao [1 ]
Chen, Liangliang [2 ]
Cong, Lin [2 ]
机构
[1] Tsinghua Univ, Dept Bldg Sci, Beijing 100084, Peoples R China
[2] Beijing Sinorefine Air Conditioning Technol Co LT, Beijing 100084, Peoples R China
基金
中国国家自然科学基金;
关键词
Liquid desiccant; Counter flow; Two-stage heat pump; Experimental results; AIR-CONDITIONING SYSTEM; MASS-TRANSFER PROCESSES; PERFORMANCE; DEHUMIDIFIER/REGENERATOR; TEMPERATURE; MODEL;
D O I
10.1016/j.enbuild.2018.09.007
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A counter-flow heat pump driven liquid desiccant dehumidification (HPLD) system is considered as an energy-efficient approach for the humid air handling process, with advantages in terms of higher efficiency and simpler configuration. It is found that the adoption of a multi-stage heat pump cycle can improve the system performance, and then experimental tests for the system performance of the HPLD system with a two-stage heat pump cycle are investigated in the present study. The effects of solution flow rate, air inlet parameters including outdoor air and indoor exhaust air, and supplementary water capacity for the system on the system performance are elucidated according to the experimental results. It is found that the solution flow rate could affect the heat recovery performance between outdoor air and indoor exhaust air, and the performance of the heat pump. Thus, there exists an optimal solution flow rate for this counter-flow HPLD system, and the coefficient of performance of the system (COPsys) can be as high as 6.5 under the experimental condition. Besides, the increase of outdoor air inlet parameters and the decrease of indoor exhaust air inlet parameters with enough indoor exhaust air flow rate for the system have favorable effects on the system performance, due to the promotion to the heat recovery performance of the system. And more supplementary water capacity to remove the redundant heating capacity of the system would also improve the system performance mainly through lowering the condensing temperature. However, supplementary water capacity cannot be added too much for the system due to the dehumidification demand. Furthermore, the coefficient of performance of this counterflow HPLD system is approximately 30% higher than that of a cross-flow HPLD system, handling more dehumidification demand. (C) 2018 Elsevier B.V. All rights reserved.
引用
收藏
页码:223 / 238
页数:16
相关论文
共 50 条
  • [41] Experimental investigation on a novel heat pump system based on desiccant coated heat exchangers
    Hua, L. J.
    Jiang, Y.
    Ge, T. S.
    Wang, R. Z.
    [J]. ENERGY, 2018, 142 : 96 - 107
  • [42] Experimental investigation of heat pump driven humidification-dehumidification desalination system for water desalination and space conditioning
    Lawal, Dahiru U.
    Antar, Mohamed A.
    Khalifa, Atia
    Zubair, Syed M.
    Al-Sulaiman, Fahad
    [J]. DESALINATION, 2020, 475
  • [43] Investigation on the coupled heat and mass transfer process between extremely high humidity air and liquid desiccant in the counter-flow adiabatic packed tower
    Wang, Zhenying
    Zhang, Xiaoyue
    Li, Zhen
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2017, 110 : 898 - 907
  • [44] Experimental and numerical investigation of a novel hybrid deep-dehumidification system using liquid desiccant
    Guan, Bowen
    Liu, Xiaohua
    Zhang, Tao
    Ma, Zhiyao
    Chen, Liangliang
    Chen, Xiaoyang
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2019, 192 : 396 - 411
  • [45] Operating characteristics and performance evaluation of carbon dioxide heat pump driven liquid desiccant dehumidification systems: A comparative study
    Cui, Qi
    Qu, Hongshuo
    Sun, Bo
    Gao, Enyuan
    Zhang, Xiaosong
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2022, 254
  • [46] Experimental investigation on flow boiling heat transfer characteristics in short flow passage counter-flow microchannels
    Li, Yun
    Cao, Jie
    Hua, Xia
    Wu, Huiying
    [J]. Huagong Xuebao/CIESC Journal, 2023, 74 (11): : 4501 - 4514
  • [47] Investigation on the liquid contact angle and its influence for liquid desiccant dehumidification system
    Qi Ronghui
    Lu Lin
    Jiang Yu
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2015, 88 : 210 - 217
  • [48] DESIGN AND EXPERIMENTAL INVESTIGATION OF A GAS-TO-GAS COUNTER-FLOW MICRO HEAT EXCHANGER
    Yang, Y.
    Gerken, I.
    Brandner, J. J.
    Morini, G. L.
    [J]. EXPERIMENTAL HEAT TRANSFER, 2014, 27 (04) : 340 - 359
  • [49] Experimental investigation of a novel multi-channel flat plate liquid desiccant dehumidification system
    Sharma, Akash
    Kaushal, Rajneesh
    [J]. ENERGY SOURCES PART A-RECOVERY UTILIZATION AND ENVIRONMENTAL EFFECTS, 2020, Taylor and Francis Inc., 325 Chestnut St, Suite 800, Philadelphia, PA 19106, United States : 1 - 19
  • [50] Performance study of a heat pump driven and hollow fiber membrane-based two-stage liquid desiccant air dehumidification system
    Zhang, Ning
    Yin, Shao-You
    Zhang, Li-Zhi
    [J]. APPLIED ENERGY, 2016, 179 : 727 - 737