Hot sanitary water production with CO2 heat pumps: Effect of control strategy on system performance and stratification inside the storage tank

被引:10
|
作者
Tammaro, M. [1 ]
Mauro, A. W. [1 ]
Montagud, C. [2 ]
Corberan, J. M. [2 ]
Mastrullo, R. [1 ]
机构
[1] Univ Naples Federico II, Dipartimento Ingn Ind, P Le Tecchio 80, Naples, Italy
[2] Univ Politecn Valencia, Inst Ingn Energet, Camino Vera S-N, E-46022 Valencia, Spain
关键词
Storage tank control; Sanitary hot water; Heat pump; Parametric analysis; Cost; REJECTION PRESSURE; CARBON-DIOXIDE; REFRIGERANT;
D O I
10.1016/j.applthermaleng.2016.01.094
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this work three different control strategies for the production of sanitary hot water by means of an electric heat pump working with CO2 are investigated. The heat pump is a prototype, here modelled in the vapour-compression software package IMST-ART. By simulating this model, the performance of the heat pump is correlated to the boundary conditions and is scaled to different sizes, namely 1, 1.5, and 2 times larger than the reference system. After having chosen an application for which the load profile of sanitary hot water during the year is known, these heat pumps are simulated in a TRNSYS16 model where the production of sanitary hot water and the consumption are buffered by the presence of a tank. Key parameter in guaranteeing comfort and good performance of the system is the stratification inside the storage tank. The size of the tank necessary to keep a certain level of comfort at the user is then determined through a parametric analysis for each size of the heat pump. The energetic performance is also evaluated for each system in terms of seasonal performance factor. Then, the results obtained are compared with a different system where the heat pump is equipped with an inverter and the circulation pump follows a different control logic. The size of the tank and the seasonal performance factor are therefore determined in this case too. Moreover, a "night&day" control logic is compared to these first two options to have a baseline of comparison in terms of volume of storage needed to guarantee a same level of comfort and performance. To provide information also on the running costs, a parametric analysis was run varying the type of control, the heat pump and the tank sizes for different load profiles. The results show that the size of the heat pump has a significant effect on the comfort of the user, which usually leads to oversizing of the storage tank when the load profile is unknown. With regard to this, the results obtained for the alternative control system show a 20% reduction of the volume of the tank, given a certain level of comfort, and is therefore useful to reduce the size of the storage tank. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:730 / 740
页数:11
相关论文
共 50 条
  • [21] Influence of ambient temperatures on performance of a CO2 heat pump water heating system
    Yokoyama, R
    Shimizu, T
    Ito, K
    Takemura, K
    PROCEEDINGS OF ECOS 2005, VOLS 1-3: SHAPING OUR FUTURE ENERGY SYSTEMS, 2005, : 1097 - 1104
  • [22] Performance Estimation and Optimal Operation of a CO2 Heat Pump Water Heating System
    Yokoyama, R.
    Kato, R.
    Wakui, T.
    Takemura, K.
    INTERNATIONAL JOURNAL OF THERMODYNAMICS, 2013, 16 (02) : 62 - 72
  • [23] Influence of ambient temperatures on performance of a CO2 heat pump water heating system
    Yokoyama, Ryohei
    Shimizu, Takeshi
    Ito, Koichi
    Takemura, Kazuhisa
    ENERGY, 2007, 32 (04) : 388 - 398
  • [24] Integrated CO2 system with HVAC and hot water for hotels: Field measurements and performance evaluation
    Smitt, S.
    Tolstorebrov, I
    Hafner, A.
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 116 : 59 - 69
  • [25] Influence of the hydronic loop configuration on the energy performance of a CO2 heat pump for domestic hot water production in a multi-family building
    Dongellini, Matteo
    Naldi, Claudia
    Morini, Gian Luca
    PROCEEDINGS OF BUILDING SIMULATION 2021: 17TH CONFERENCE OF IBPSA, 2022, 17 : 3228 - 3235
  • [26] Effect of evaporator air flow distribution on the performance of air source CO2 heat pumps through frost formation
    Alvandifar, Negar
    Cattani, Michele
    Kristofersson, Johannes
    Forooghi, Pourya
    10TH CONFERENCE ON AMMONIA AND CO2 REFRIGERATION TECHNOLOGIES, 2023, : 140 - 147
  • [27] Experimental performance study on a dual-mode CO2 heat pump system with thermal storage
    Liu, Fang
    Zhu, Weiquan
    Cai, Yang
    Groll, Eckhard A.
    Ren, Jianxing
    Lei, Yafeng
    APPLIED THERMAL ENGINEERING, 2017, 115 : 393 - 405
  • [28] Performance analysis of a hot water supply system with a CO2 heat pump by numerical simulation (1st report, modeling and analysis of heat pump)
    Yokoyama, Ryohei
    Shimuzu, Takeshi
    Takemura, Kazuhisa
    Ito, Koichi
    Nihon Kikai Gakkai Ronbunshu, B Hen/Transactions of the Japan Society of Mechanical Engineers, Part B, 2005, 71 (707): : 1885 - 1892
  • [29] Performance analysis of a hot water supply system with a CO2 heat pump by numerical simulation -: (1st report, modeling and analysis of heat pump)
    Yokoyama, Ryohei
    Shimizu, Takeshi
    Takemura, Kazuhisa
    Ito, Koichi
    JSME INTERNATIONAL JOURNAL SERIES B-FLUIDS AND THERMAL ENGINEERING, 2006, 49 (02) : 541 - 548
  • [30] Subcooling effect on the optimal performance for a transcritical CO2 heat pump with cold thermal energy storage
    Wang, Ji
    Evans, Michael
    Belusko, Martin
    Zhao, Chunrong
    Liu, Ming
    Bruno, Frank
    HEAT AND MASS TRANSFER, 2023, 59 (07) : 1257 - 1275