Electromagnetic-thermal analysis of 400 kV power transformer on ITER PPEN substation

被引:0
|
作者
Li, Peng [1 ,2 ]
Jiang, Jiafu [1 ]
Liu, Sheng [3 ]
Fu, Peng [1 ]
Huang, Yiyun [1 ]
Hui, Xie [4 ]
Qiang, Liu [4 ]
Zuo Hongyan [4 ]
机构
[1] Chinese Acad Sci, Inst Plasma Phys, Hefei 230031, Anhui, Peoples R China
[2] Univ Sci & Technol China, Hefei, Anhui, Peoples R China
[3] China Int Nucl Fus Energy Program Execut Ctr, Beijing, Peoples R China
[4] Baoding Tianwei Baobian Elect Co LTD, Baoding, Peoples R China
关键词
ITER; PPEN; temperature rise; ANSYS; short-circuit method; AC/DC CONVERTER;
D O I
10.3233/JAE-190105
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
As an important electrical power distribution system of ITER (International Thermonuclear Experimental Reactor) device, PPEN (Pulsed Power Electrical Network) feeds the pulsed loads for the superconducting coils and the heating and current driving systems. The PPEN transforms 400 kV power grid to 66 kV and 22 kV distribution voltage levels by 3 main step-down transformers. In this paper, the power loss of PPEN transformer is analyzed and calculated. The 2D PPEN transformer model is built. The temperature rise of PPEN transformer is calculated by ANSYS software. To validate the feasibility and correctness of the proposed method, the temperature rise test of PPEN transformer is carried out, then the related results are compared with the test data.
引用
收藏
页码:835 / 844
页数:10
相关论文
共 50 条
  • [31] Electromagnetic-thermal Analysis of the Effect of Microwave Ablation of Thyroid Nodules
    Wang, Jinzhi
    Xiao, Gaobiao
    2021 PHOTONICS & ELECTROMAGNETICS RESEARCH SYMPOSIUM (PIERS 2021), 2021, : 2425 - 2432
  • [32] Analysis of Coupled Electromagnetic-Thermal Effects in Superconducting Accelerator Magnets
    Fischer, E.
    Kurnyshov, R.
    Shcherbakov, P.
    8TH EUROPEAN CONFERENCE ON APPLIED SUPERCONDUCTIVITY (EUCAS'07), 2008, 97
  • [33] A Multiphysics Analysis of Coupled Electromagnetic-Thermal Phenomena in Cable Lines
    Cywinski, Artur
    Chwastek, Krzysztof
    ENERGIES, 2021, 14 (07)
  • [34] Electromagnetic-thermal analysis of a hybrid switched-reluctance motor
    Rizzo, M
    INTERNATIONAL JOURNAL OF APPLIED ELECTROMAGNETICS AND MECHANICS, 2001, 15 (1-4) : 103 - 110
  • [35] Control logic for the changeover of a spare transformer unit at "El furrial" substation 400/230/34.5 kV
    Marval, M.
    Serrano, A.
    2006 IEEE/PES TRANSMISSION & DISTRIBUTION CONFERENCE & EXPOSITION: LATIN AMERICA, VOLS 1-3, 2006, : 386 - 389
  • [37] Sensitivity studies on power transformer ferroresonance of a 400 kV double circuit
    Charalambous, C.
    Wang, Z. D.
    Osborne, M.
    Jarman, P.
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2008, 2 (02) : 159 - 166
  • [38] Mathematical Modeling of Fast and Accurate Coupled Electromagnetic-Thermal Analysis
    Ryu, Jun-Yeol
    Hwang, Sung-Woo
    Chin, Jun-Woo
    Hwang, Yong-Suk
    Yoon, Sang Won
    Lim, Myung-Seop
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2021, 57 (05) : 4636 - 4645
  • [39] Electromagnetic-Thermal Coupling Computation of the High Power Microwave Feed Output Window
    Wang, Yi-Gang
    Chen, Bin
    Chen, Hai-Lin
    Yi, Yun
    Chen, Qiang
    2015 7TH ASIA-PACIFIC CONFERENCE ON ENVIRONMENTAL ELECTROMAGNETICS (CEEM), 2015, : 320 - 324
  • [40] Analysis to coupled electromagnetic-thermal field of brushless doubly fed machine
    Xia Shengzhu
    Deng Xianming
    Wang Zhiye
    Liu Meng
    MATERIALS SCIENCE AND INFORMATION TECHNOLOGY, PTS 1-8, 2012, 433-440 : 7312 - 7317