Electromagnetic-thermal analysis of 400 kV power transformer on ITER PPEN substation

被引:0
|
作者
Li, Peng [1 ,2 ]
Jiang, Jiafu [1 ]
Liu, Sheng [3 ]
Fu, Peng [1 ]
Huang, Yiyun [1 ]
Hui, Xie [4 ]
Qiang, Liu [4 ]
Zuo Hongyan [4 ]
机构
[1] Chinese Acad Sci, Inst Plasma Phys, Hefei 230031, Anhui, Peoples R China
[2] Univ Sci & Technol China, Hefei, Anhui, Peoples R China
[3] China Int Nucl Fus Energy Program Execut Ctr, Beijing, Peoples R China
[4] Baoding Tianwei Baobian Elect Co LTD, Baoding, Peoples R China
关键词
ITER; PPEN; temperature rise; ANSYS; short-circuit method; AC/DC CONVERTER;
D O I
10.3233/JAE-190105
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
As an important electrical power distribution system of ITER (International Thermonuclear Experimental Reactor) device, PPEN (Pulsed Power Electrical Network) feeds the pulsed loads for the superconducting coils and the heating and current driving systems. The PPEN transforms 400 kV power grid to 66 kV and 22 kV distribution voltage levels by 3 main step-down transformers. In this paper, the power loss of PPEN transformer is analyzed and calculated. The 2D PPEN transformer model is built. The temperature rise of PPEN transformer is calculated by ANSYS software. To validate the feasibility and correctness of the proposed method, the temperature rise test of PPEN transformer is carried out, then the related results are compared with the test data.
引用
收藏
页码:835 / 844
页数:10
相关论文
共 50 条
  • [21] Study on Electromagnetic-Thermal Simulation of 10kV Air Insulated Switchgear
    Sun, Guanghui
    Chen, Sixiang
    Chen, Baiquan
    Liu, Yijun
    Chen, Bangfa
    Li, Hengzhen
    Deng, Richao
    Fu, Anzhi
    2023 5TH ASIA ENERGY AND ELECTRICAL ENGINEERING SYMPOSIUM, AEEES, 2023, : 378 - 383
  • [22] ITER PPEN变电站400 kV避雷器的设计及短路性能的分析
    江加福
    黄懿贇
    刘晓艳
    李国胜
    任文献
    沈洪如
    电瓷避雷器, 2018, (02) : 97 - 100+105
  • [23] Strategy Design and Transient Analysis of ITER PPEN Transformer On-Load Tap Changer During Converter Operation
    Renjing Fan
    Peng Fu
    Jun Tao
    Ge gao
    Zhiquan Song
    Liansheng Huang
    Xiaojiao Chen
    Jinchao Li
    Journal of Fusion Energy, 2018, 37 : 346 - 353
  • [24] Strategy Design and Transient Analysis of ITER PPEN Transformer On-Load Tap Changer During Converter Operation
    Fan, Renjing
    Fu, Peng
    Tao, Jun
    Gao, Ge
    Song, Zhiquan
    Huang, Liansheng
    Chen, Xiaojiao
    Li, Jinchao
    JOURNAL OF FUSION ENERGY, 2018, 37 (06) : 346 - 353
  • [25] Measurements and Computation of Electromagnetic Field in Transformer Station 400/110 kV Ernestinovo
    Nikolovski, S.
    Klaic, Z.
    Stefic, B.
    2009 IEEE BUCHAREST POWERTECH, VOLS 1-5, 2009, : 2296 - +
  • [26] Coupled electromagnetic-thermal analysis of roadway inductive power transfer pads within a model pavement
    Amirpour, Maedeh
    Kim, Seho
    Battley, Matthew P.
    Kelly, Piaras
    Bickerton, Simon
    Covic, Grant
    APPLIED THERMAL ENGINEERING, 2021, 189
  • [27] Electromagnetic-Thermal Field Coupling Calculation of Contactless Power Transfer Vehicle
    Wang Y.
    Zhang Q.
    Lin F.
    Dong L.
    Xinan Jiaotong Daxue Xuebao/Journal of Southwest Jiaotong University, 2020, 55 (03): : 545 - 551
  • [28] Risk Management Model of 69 kV Power Transformer Bushing in Metropolitan Substation
    Phadungthin, Rattanakorn
    Haema, Juthathip
    2017 4TH INTERNATIONAL CONFERENCE ON INDUSTRIAL ENGINEERING AND APPLICATIONS (ICIEA), 2017, : 341 - 344
  • [29] Simulation analysis of electromagnetic-thermal coupling for armature in inductive coilgun
    Guan X.
    Li Z.
    Zhao R.
    Cheng E.
    Qiangjiguang Yu Lizishu/High Power Laser and Particle Beams, 2011, 23 (08): : 2267 - 2272
  • [30] Multiphysics Sensitivity Analysis in FDTD Based Electromagnetic-Thermal Simulations
    Liu, Kae-An
    Sarris, Costas D.
    PROCEEDINGS OF THE 2020 IEEE/MTT-S INTERNATIONAL MICROWAVE SYMPOSIUM (IMS), 2020, : 150 - 153