Transmission Line Dynamic Circuit Model for Effective Length of Ground Electrode Under Lightning Transients

被引:6
|
作者
Kumar A, Senthil [1 ]
Manickavasagam, Krishnan [2 ]
机构
[1] Lab Electro Opt Syst LEOS, Environm Test Facil, Bengaluru 560058, India
[2] MS Ramaiah Univ Appl Sci, Elect Engn Dept, Bangalore 560054, Karnataka, India
关键词
Grounding; Soil; Electrodes; Integrated circuit modeling; Ionization; Resistance; Lightning; Effective length of ground electrode (ELGE); frequency-dependent soil parameters; impulse impedance (Zi); ionization; transient voltage (TV); IMPULSE IMPEDANCE;
D O I
10.1109/TEMC.2021.3124679
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The effective length of the ground electrode is one of the primary research interests of lightning grounding system design. In this article, using a practical numerical analysis, a new expression for estimating the effective length of the simple ground electrode is proposed. A new dynamic circuit model based on the transmission line is developed to derive the expression. The model considers the soil ionization, frequency-dependent soil parameters, mutual reactance, and skin effect. Several rigorous impulse test simulations are performed on different electrode lengths, soil properties, and lightning currents to estimate the effective length of ground electrode numerically. A new expression is arrived at using the curve-fitting and optimization technique from the relationships of the effective length with soil resistivity, impulse rise time, and current. The proposed dynamic model and the expression to obtain the effective length are validated by published results.
引用
收藏
页码:543 / 550
页数:8
相关论文
共 50 条
  • [31] A NONLINEAR TRANSMISSION-LINE MODEL OF THE LIGHTNING RETURN STROKE
    MATTOS, MAD
    CHRISTOPOULOS, C
    IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 1988, 30 (03) : 401 - 406
  • [32] Analysis of dynamic stability of a transmission tower-line system under tilt ground motion
    Wei W.
    Huang G.
    Xu F.
    Hu Y.
    Zhendong yu Chongji/Journal of Vibration and Shock, 2022, 41 (04): : 55 - 62and109
  • [33] Transmission line grounding arrangement that overcomes the effective length issue
    Lima, A. B.
    Paulino, J. O. S.
    Boaventura, W. C.
    Caetano, C. E. F.
    Cardoso, E. N.
    2016 33RD INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2016,
  • [34] Multi-rail transmission-line model as an equivalent circuit for electrochemical impedance of a porous electrode
    Siroma, Zyun
    Fujiwara, Naoko
    Yamazaki, Shin-ichi
    Asahi, Masafumi
    Nagai, Tsukasa
    Ioroi, Tsutomu
    JOURNAL OF ELECTROANALYTICAL CHEMISTRY, 2020, 878
  • [35] Study on calculation model of the lightning protection performance of shielding failure for 500kV double circuit transmission line
    Zhang, ZJ
    Sima, WX
    Liao, RJ
    PROCEEDINGS OF THE 7TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1-3, 2003, : 122 - 124
  • [36] BEHAVIOR OF TRANSMISSION-LINE TOWERS UNDER LIGHTNING SURGE CONDITIONS
    HAMZA, ASH
    ABDELGAWAD, NMK
    ENERGY CONVERSION AND MANAGEMENT, 1994, 35 (11) : 943 - 953
  • [37] Fail ure of 220 kV double circuit transmission line tower due to lightning
    Nair, Z
    Aparna, KM
    Khandagale, RS
    Gopalan, TV
    JOURNAL OF PERFORMANCE OF CONSTRUCTED FACILITIES, 2005, 19 (02) : 132 - 137
  • [38] Experimental and Analytical Studies on Lightning Surge Response of the Quadruple-Circuit Transmission Line
    Zhu, Qianxin
    Zhang, Yi
    Ma, Yutang
    Zhou, Fangrong
    Yin, Hongjiang
    Zhang, Haihu
    Pan, Hao
    Geng, Hao
    Zhang, Bingzhen
    Cheng, Zhengjun
    Yu, Lei
    Qiu, Tingwei
    IEEE ACCESS, 2023, 11 : 6879 - 6886
  • [39] Studying of Lightning Surge Transient Effect on 500 kV Quadruple Circuit Transmission Line
    Kusuma, Aristo Adi
    Pramana, Putu Agus Aditya
    Munir, Buyung S.
    Ayu, Rica S.