3D Localization Method of Partial Discharge in Air-Insulated Substation Based on Improved Particle Swarm Optimization Algorithm

被引:4
|
作者
Li, Pengfei [1 ]
Peng, Xinjie [1 ]
Yin, Kaiyang [1 ]
Xue, Yaxu [1 ]
Wang, Rongqing [1 ]
Ma, Zhengsen [1 ]
机构
[1] Pingdingshan Univ, Sch Elect & Mech Engn, Pingdingshan 467000, Peoples R China
来源
SYMMETRY-BASEL | 2022年 / 14卷 / 06期
关键词
partial discharge localization; improved particle swarm optimization algorithm; air-insulated substation; ultra-high frequency method; ANTENNA; SIGNALS; SENSOR; SYSTEM;
D O I
10.3390/sym14061241
中图分类号
O [数理科学和化学]; P [天文学、地球科学]; Q [生物科学]; N [自然科学总论];
学科分类号
07 ; 0710 ; 09 ;
摘要
Partial discharge (PD) localization in an air-insulated substation (AIS) can be used to assess insulation conditions efficiently. Many localization methods have been reported during the past few years. However, the error of the localization results has been large or the localization algorithm too inefficient. The reason is that the localization equation set is nonlinear and non-symmetrical. In this paper, an improved particle swarm optimization (PSO) algorithm is proposed to improve the localization accuracy in 3D. Firstly, the proposed localization method is based on the symmetrical antenna array and the location error distribution is analyzed. Secondly, the objective function of PSO is constructed using the error distribution. Specifically, the 3D location target is divided into two steps-plane coordinates and height. The two targets are optimized respectively. To verify the method, a test is carried out by a prefabricated fault bushing in the laboratory to compare with the existing methods. According to the results, the localization error is 0.21 m, which can locate the PD source accurately. A complete calculation takes 42.29 s, and the efficiency is increased by 16.13 times under the same accuracy. The comparison results show that the proposed method can greatly improve the efficiency while ensuring accuracy.
引用
收藏
页数:14
相关论文
共 50 条
  • [1] UHF Antenna Configuration Optimization for Partial Discharge Source Localization in Air-Insulated Substation
    Zhu, Ming-Xiao
    Zhang, Jia-Ning
    Liu, Qing
    Wang, Yan-Bo
    Deng, Jun-Bo
    Zhang, Guan-Jun
    Guo, An-Xiang
    Liu, Xiao-Wei
    2016 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD), 2016, : 873 - 876
  • [2] Localization of Multiple Partial Discharge Sources in Air-Insulated Substation Using Probability-Based Algorithm
    Zhu, Ming-Xiao
    Wang, Yan-Bo
    Liu, Qing
    Zhang, Jia-Ning
    Deng, Jun-Bo
    Zhang, Guan-Jun
    Shao, Xian-Jun
    He, Wen-Lin
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (01) : 157 - 166
  • [3] Localization Method for Multiple Partial Discharge Sources in Air-insulated Substation by Using Plane Intersection Method
    Zhu M.
    Liu Q.
    Wang Y.
    Deng J.
    Zhang G.
    Guo A.
    Zhang, Guanjun (gjzhang@mail.xjtu.edu.cn), 2018, Science Press (44): : 2970 - 2976
  • [4] Improved Methods for UHF Localization of Partial Discharge in Air-Insulated Substations
    Rashwan, Ahmed
    Reid, Alistair
    ENERGIES, 2023, 16 (10)
  • [5] Location Determination of Partial Discharge Sources in Air-Insulated Substation
    Yue, Ziqi
    Liu, Zeqiu
    IWCMC 2021: 2021 17TH INTERNATIONAL WIRELESS COMMUNICATIONS & MOBILE COMPUTING CONFERENCE (IWCMC), 2021, : 1852 - 1855
  • [6] Localization of Multiple Partial Discharge Sources in Air-Insulated Substation Space by RF Antenna Sensors Array
    Zhou, Shengqi
    Wu, Shiyou
    Xiong, Haiqiang
    Qiu, Riqiang
    Sun, Yule
    Zheng, Shusheng
    Yang, Zehong
    IEEE SENSORS JOURNAL, 2022, 22 (14) : 14481 - 14490
  • [7] Optimisation of antenna array allocation for partial discharge localisation in air-insulated substation
    Zhu, Ming-Xiao
    Liu, Qing
    Wang, Yan-Bo
    Li, Yuan
    Deng, Jun-Bo
    Mu, Hai-Bao
    Zhang, Guan-Jun
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2017, 11 (08) : 967 - 975
  • [8] Method for partial discharge localisation in air-insulated substations
    Li, Pengfei
    Zhou, Wenjun
    Yang, Shuai
    Liu, Yushun
    Tian, Yan
    Wang, Yong
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2017, 11 (03) : 331 - 338
  • [9] Radiometric localisation of partial discharge sources inside Air-insulated electrical substation
    Mishra, Dipak Kumar
    Bhukya, Anitha
    Koley, Chiranjib
    Roy, Nirmal Kumar
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2019, 13 (08) : 1122 - 1130
  • [10] UHF Sensors Based Localization of Partial Discharge Sources in Air-Insulated Electrical Substation Using TDOA and Relative RSS Information
    Dhara, Sourav
    Koley, Chiranjib
    Chakravorti, Sivaji
    IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2023, 72