Effect of Grounding Resistance Connected to Surge Arresters in Power Distribution Lines on Lightning Surge Behavior Observed in Customer's Equipment

被引:1
|
作者
Hidaka, Tetsuya [1 ]
Shiota, Katsushi [2 ]
Ishimoto, Kazuyuki [1 ]
Asakawa, Akira [1 ]
机构
[1] CRIEPI, Elect Power Engn Res Lab, Tokyo, Japan
[2] Chugoku Elect Power Co Inc, Tokyo, Japan
关键词
lightning; distribution line; surge arrester; overhead ground wire; grounding resistance; pole transformer;
D O I
10.1002/eej.22810
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In Japan, electric power companies have been spending large amounts of money on the construction costs and maintenance costs of low grounding resistances connected to surge arresters (Arrs) that are basically maintained below 30 . In a recent study, it has been clarified that the rate of protection against direct lightning hits on distribution lines with an overhead ground wire (GW) hardly decreases, even if the grounding resistance of Arrs is high. However the installation of Arrs on a pole where a pole transformer (Tr) is mounted has not been considered, and in the case of a high grounding resistance, the lightning surge behavior observed in the customer's equipment has not yet been clarified. To examine the grounding resistance of Arrs, it is necessary to understand such behavior in the case in which the grounding resistance of Arrs is varied. In this paper, we clarified the relationship between the grounding resistance connected to Arrs and lightning surge behavior in customer's equipment. The result shows that the grounding resistance of Arrs installed on a pole with a Tr can be increased to some extent without decreasing the lightning protection level of the customer's equipment by the installation of a GW and the shortening of the interval between concrete poles with Arrs. A reduction in the cost of grounding construction can be expected. (C) 2015 Wiley Periodicals, Inc.
引用
下载
收藏
页码:1 / 10
页数:10
相关论文
共 28 条
  • [21] Practical methodology for modeling and simulation of a lightning protection system using metal-oxide surge arresters for distribution lines
    Araujo, Marcel A.
    Flauzino, Rogerio A.
    Altafim, Ruy A. C.
    Batista, Oureste E.
    Moraes, Lucas A.
    ELECTRIC POWER SYSTEMS RESEARCH, 2015, 118 : 47 - 54
  • [22] Virginia power's use of polymer housed surge arresters to protect 138 kV transmission lines
    Babik, JJ
    Lamb, ML
    1996 IEEE TRANSMISSION AND DISTRIBUTION CONFERENCE PROCEEDINGS, 1996, : 283 - 287
  • [23] Lightning Surge Insulation Characteristics of Polymer Insulators for 6.6kV Power Distribution Lines
    Yoneda, Yasuaki
    Koga, Yoshiyasu
    Sato, Tomoyuki
    Kuno, Takafumi
    ICLP 2024 - 37th International Conference on Lightning Protection, 2024, : 216 - 222
  • [24] Electric potential assessment near distribution power lines caused by lightning surge wave propagation
    Mariut, Elena Larisa
    Helerea, Elena
    Ursachi, Corneliu
    2015 INTL AEGEAN CONFERENCE ON ELECTRICAL MACHINES & POWER ELECTRONICS (ACEMP), 2015 INTL CONFERENCE ON OPTIMIZATION OF ELECTRICAL & ELECTRONIC EQUIPMENT (OPTIM) & 2015 INTL SYMPOSIUM ON ADVANCED ELECTROMECHANICAL MOTION SYSTEMS (ELECTROMOTION), 2015, : 693 - 698
  • [25] A study of Degradation Characteristics and Diagnostic Method of Lightning Surge Arrester for 6.6 kV Power Distribution Lines
    Yoneda, Yasuaki
    Koga, Yoshiyasu
    Sato, Tomoyuki
    Yokoyama, Shigeru
    2018 34TH INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP 2018), 2018,
  • [26] Investigation on lightning surge current flows from residential solar power system to distribution lines and watt-hour meters
    Ishii, Tsunayoshi
    Takami, Jun
    Okabe, Shigemitsu
    IEEJ Transactions on Power and Energy, 2014, 134 (08) : 724 - 731
  • [27] Distribution arrester outages caused by lightning backflow current flowing from customer's facility into power distribution lines
    Nakada, Kazuo
    Yokota, Tsutomu
    Yokoyama, Shigeru
    Asakawa, Akira
    Kawabata, Tetsuji
    Electrical Engineering in Japan (English translation of Denki Gakkai Ronbunshi), 1999, 126 (03): : 9 - 20
  • [28] Distribution arrester outages caused by lightning backflow current flowing from customer's facility into power distribution lines
    Nakada, K
    Yokota, T
    Yokoyama, S
    Asakawa, A
    Kawabata, T
    ELECTRICAL ENGINEERING IN JAPAN, 1999, 126 (03) : 9 - 20