Effect of Grounding Resistance Connected to Surge Arresters in Power Distribution Lines on Lightning Surge Behavior Observed in Customer's Equipment

被引:1
|
作者
Hidaka, Tetsuya [1 ]
Shiota, Katsushi [2 ]
Ishimoto, Kazuyuki [1 ]
Asakawa, Akira [1 ]
机构
[1] CRIEPI, Elect Power Engn Res Lab, Tokyo, Japan
[2] Chugoku Elect Power Co Inc, Tokyo, Japan
关键词
lightning; distribution line; surge arrester; overhead ground wire; grounding resistance; pole transformer;
D O I
10.1002/eej.22810
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In Japan, electric power companies have been spending large amounts of money on the construction costs and maintenance costs of low grounding resistances connected to surge arresters (Arrs) that are basically maintained below 30 . In a recent study, it has been clarified that the rate of protection against direct lightning hits on distribution lines with an overhead ground wire (GW) hardly decreases, even if the grounding resistance of Arrs is high. However the installation of Arrs on a pole where a pole transformer (Tr) is mounted has not been considered, and in the case of a high grounding resistance, the lightning surge behavior observed in the customer's equipment has not yet been clarified. To examine the grounding resistance of Arrs, it is necessary to understand such behavior in the case in which the grounding resistance of Arrs is varied. In this paper, we clarified the relationship between the grounding resistance connected to Arrs and lightning surge behavior in customer's equipment. The result shows that the grounding resistance of Arrs installed on a pole with a Tr can be increased to some extent without decreasing the lightning protection level of the customer's equipment by the installation of a GW and the shortening of the interval between concrete poles with Arrs. A reduction in the cost of grounding construction can be expected. (C) 2015 Wiley Periodicals, Inc.
引用
收藏
页码:1 / 10
页数:10
相关论文
共 28 条