On the lack of correlation between PD readings and failure location in High-Voltage Stator Bars

被引:0
|
作者
da Silva, M. J. [1 ]
Pereira, F. [1 ]
Lamas, T. E. [1 ]
Cordeiro, J. F. [1 ]
Goncalves, C. S. [1 ]
Aoki, T. K. [1 ]
Faria, E. [1 ]
Hildinger, T. [1 ]
机构
[1] Voith Hydro Ltda, Sao Paulo, Brazil
关键词
partial discharges; Roebel bar; Multi-turn coil; hydrogenerator;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
After showing in a previous work that PD measurements suffer from poor repeatability and reproducibility, the present study turns now to a more qualitative approach, investigating if a method of PD fault location along a Roebel bar length can be used to identify insulation critical areas that later on could fail under electrical stress. Typical insulation "damages" have been created on the components in advance by submitting them to both thermal mechanical and electrical aging tests. Once such preliminary aging was done, the critical areas along the bars length were identified by mapping the PD readings on each component. Afterwards, every bar was subjected to a destructive electrical breakdown test. At last, the breakdown locations were compared with the PD mappings to search for any possible correlation between the two events. Based upon the present results, such correlation does not exist.