Pressure drop analysis of steam condensation in air-cooled circular tube bundles

被引:17
|
作者
O'Donovan, Alan [1 ]
Grimes, Ronan [1 ]
机构
[1] Univ Limerick, Stokes Inst, Dept Mech Aeronaut & Biomed Engn, Limerick, Ireland
关键词
Air-cooling; Condensation; Two-phase flow; Pressure drop; SOLAR POWER-PLANT; THERMODYNAMIC PERFORMANCE; FLOW; CONDENSERS; WIND; GRADIENTS; FRICTION;
D O I
10.1016/j.applthermaleng.2015.04.072
中图分类号
O414.1 [热力学];
学科分类号
摘要
Pressure losses on the condensing-side of an air-cooled condenser (ACC) have the potential to inhibit condenser performance and, ultimately, curtail plant efficiency. However, little information is available on the magnitude and effect of these losses in an ACC under typical Rankine cycle operating conditions. This article seeks to improve current understanding on steam-side pressure losses in ACCs by presenting an experimental study on the losses in a full-scale ACC circular tube bundle. Saturated steam at low pressure was condensed by a cross flow of cooling air, provided by a bank of axial fans. Full condensation occurred in all measurements, which were carried-out over a steam pressure and temperature range of approximately 0.05-0.14 bar absolute and 33-55 degrees C, respectively. These test parameters ensured that measurement program test conditions were representative of those expected in an operational thermoelectric power plant. Experimental mass fluxes, per individual tube, varied from 0.7 to 2 kg/m(2) s during testing. The pressure drop characteristics were, therefore, analysed over a vapour Reynolds numbers range of 1890-5150 and liquid Reynolds number range of 25-95. Results indicate that the measured pressure drop through the tube bundle was relatively small, in the range of 130-250 Pa. As shown in this article, the reason for this was due to momentum recovery as the steam condenses to form liquid condensate. This phenomenon offsets the frictional losses, which are shown to be comparable in magnitude to momentum recovery in a condensing flow. However, this may not always be the case. Therefore, since the frictional component is traditionally the most problematic to predict, a range of liquid gas two-phase frictional pressure drop predictive models were reviewed, and are presented herein. Comparisons between these models and the experimental data show that the most applicable model was found to be that of Lockhart & Martinelli. This demonstrated reasonable accuracy of +/- 18%. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:106 / 116
页数:11
相关论文
共 50 条
  • [21] Investigation on heat transfer and pressure drop correlations of R600a air-cooled finned tube evaporator for fridge
    Du, Su
    Li, Qingyang
    Cao, Xue
    Song, Qinglu
    Wang, Dechang
    Li, Yanhui
    Li, Lishun
    Liu, Jian
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2022, 144 : 118 - 127
  • [22] Thermo-flow performances of air-cooled condenser cell with oblique finned tube bundles
    Jin, Ruonan
    Yang, Xiaoru
    Yang, Lijun
    Du, Xiaoze
    Yang, Yongping
    [J]. INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2019, 135 : 478 - 492
  • [23] Numerical analysis of factors affecting condensation capacity of air-cooled condenser
    Zhao, Jinfeng
    Feng, Zhongbao
    Dou, Zhongzhou
    Yao, Yingying
    Zhu, Aijun
    Li, Yang
    Liu, Yan
    Jiang, Yan
    Jiang, Zhipeng
    [J]. THIRD INTERNATIONAL CONFERENCE ON ENERGY ENGINEERING AND ENVIRONMENTAL PROTECTION, 2019, 227
  • [24] Feasibility Analysis of Back-Pressure Steam Feeding Water Pump for Direct Air-Cooled Unit
    Zhao Xiaodong
    Wang Meng
    Du Xiaoze
    Yang Lijun
    Yang Yongping
    [J]. Electricity, 2013, 24 (01) : 31 - 35
  • [25] CONDENSATION OF A VAPOR-NONCONDENSABLE GAS-MIXTURE WITHIN A HORIZONTAL AIR-COOLED TUBE
    GONZALEZ, MT
    URBICAIN, MJ
    [J]. INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 1984, 11 (01) : 63 - 72
  • [26] Comparative Analysis of Steam Condensation Consisting of Air Outside of Single Tubes and Tube Bundles with Different Tube Diameters and Inclination Angles
    Zou Z.
    Wu L.
    Li F.
    Bian H.
    Cao B.
    Ding M.
    [J]. Hedongli Gongcheng/Nuclear Power Engineering, 2022, 43 (04): : 11 - 17
  • [27] Combined air-cooled condenser layout with in line configured finned tube bundles to improve cooling performance
    Kong, Yanqiang
    Wang, Weijia
    Zuo, Zhitao
    Yang, Lijun
    Du, Xiaoze
    Yang, Yongping
    [J]. APPLIED THERMAL ENGINEERING, 2019, 154 : 505 - 518
  • [28] Thermal Resistance of Steam Condensation in Horizontal Tube Bundles
    Grzebielec, Andrzej
    Rusowicz, Artur
    [J]. JOURNAL OF POWER TECHNOLOGIES, 2011, 91 (01): : 41 - 48
  • [29] Heat transfer at steam condensation on horizontal tube bundles
    Gogonin, I.I.
    Sosunov, V.I.
    Kataev, A.I.
    [J]. Elektrotekhnika, 1992, (04): : 48 - 51
  • [30] Numerical analysis of the heat transfer characteristics of steam-air condensation outside S-tube bundles
    Xiao J.
    Gao L.
    Sun Z.
    Jing R.
    Bian H.
    [J]. Harbin Gongcheng Daxue Xuebao/Journal of Harbin Engineering University, 2023, 44 (07): : 1242 - 1248