Performance of heat pumps charged with R170/R290 mixture

被引:69
|
作者
Park, Ki-Jung [1 ]
Jung, Dongsoo [1 ]
机构
[1] Inha Univ, Dept Mech Engn, Inchon 402751, South Korea
基金
新加坡国家研究基金会;
关键词
Alternative refrigerant; COP; Capacity; R290 (propane); R170 (ethane); Refrigerant mixture; Heat pump; DOMESTIC REFRIGERATORS; HCFC22;
D O I
10.1016/j.apenergy.2009.04.009
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
in this study, thermodynamic performance of R170/R290 mixture is measured on a heat pump bench tester in an attempt to substitute R22. The bench tester is equipped with a commercial hermetic rotary compressor providing a nominal capacity of 3.5 kW. All tests are conducted under the summer cooling and winter heating conditions of 7/45 degrees C and -7/41 degrees C in the evaporator and condenser, respectively. During the tests, the composition in R170/R290 mixture is varied from 0% to 10% with an interval of 2%. Test results show that the coefficient of performance (COP) and capacity of R290 are up to 15.4% higher and 7.5% lower, respectively than those of R22 for two conditions. For R170/R290 mixture, the COP decreases and the capacity increases with an increase in the composition of R170. The mixture of R170/R290 mixture at 4%/96% composition shows the similar capacity and COP as those of R22. For the mixture, the compressor discharge temperature is 17-28 degrees C lower than that of R22. For R170/R290 mixture, there is no problem with mineral oil since the mixture is composed of hydrocarbons. The amount of charge is reduced up to 58% as compared to R22. Overall, R170/R290 mixture is a good long term 'drop-in' candidate from the view point of energy efficiency and greenhouse warming to replace R22 in residential air-conditioners and heat pumps (C) 2009 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2598 / 2603
页数:6
相关论文
共 50 条
  • [31] Performance evaluation of a vapor injection refrigeration system using mixture refrigerant R290/R600a
    Hallak d'Angelo, Jose Vicente
    Aute, Vikrant
    Radermacher, Reinhard
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2016, 65 : 194 - 208
  • [32] Experimental study on hydrocarbon mixture refrigerant R600a/R290 in refrigerator
    Du, YP
    Lu, J
    Chen, H
    Sun, Y
    Yin, CX
    PROCEEDINGS OF THE 3RD INTERNATIONAL SYMPOSIUM ON HEAT TRANSFER ENHANCEMENT AND ENERGY CONSERVATION, VOLS 1 AND 2, 2004, : 1054 - 1057
  • [33] Evaluation of flammability characteristics of mixed refrigerants R134a/ R1270, R134a/R170, and R170/R1270
    Zhang, Zhihao
    He, Guogeng
    Ning, Qian
    Wang, Zihang
    Yang, Wei
    Hua, Jialiang
    Zhou, Sai
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2023, 156 : 1 - 11
  • [34] Comparing R-290 with R-22 in heat pumps
    Hwang, YH
    Gado, A
    Radermacher, R
    ASHRAE JOURNAL, 2003, 45 (01) : 40 - 40
  • [35] Performance evaluation of a fin-and-tube evaporator with R407C/R290/R600a refrigerant mixture
    Raj, M. H.
    Lal, D. M.
    INTERNATIONAL JOURNAL OF AMBIENT ENERGY, 2010, 31 (01) : 33 - 46
  • [36] Performance evaluation on an internal auto-cascade refrigeration cycle with mixture refrigerant R290/R600a
    Yan, Gang
    Hu, Hui
    Yu, Jianlin
    APPLIED THERMAL ENGINEERING, 2015, 75 : 994 - 1000
  • [37] Theoretical investigation on the performance of an ejector enhanced refrigeration cycle using hydrocarbon mixture R290/R600a
    Chen, Qi
    Hwang, Yunho
    Yan, Gang
    Yu, Jianlin
    APPLIED THERMAL ENGINEERING, 2020, 164
  • [38] Experimental investigation on flow boiling heat transfer performance of a new near azeotropic refrigerant mixture R290/R32 in horizontal tubes
    He, Guogeng
    Liu, Fang
    Cai, Dehua
    Jiang, Jingkai
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2016, 102 : 561 - 573
  • [39] INFLUENCES OF VARIABLE MASS FLOWRATE OF REFRIGERANT BLEND R125/R290 ON HEAT PUMP PERFORMANCE
    Wang, Fang
    Fan, Xiaowei
    Guo, Zhuangyu
    Zhang, Lu
    Zheng, Huiyan
    PROCEEDINGS OF THE ASME INTERNATIONAL MECHANICAL ENGINEERING CONGRESS AND EXPOSITION, 2015, VOL 8B, 2016,
  • [40] The performance and risk assessment of R290 in a 13 kW air source heat pump
    Tang, Weier
    He, Guogeng
    Zhou, Sai
    Sun, Wei
    Cai, Dehua
    Mei, Kui
    APPLIED THERMAL ENGINEERING, 2018, 144 : 392 - 402