Performance of heat pumps charged with R170/R290 mixture

被引:69
|
作者
Park, Ki-Jung [1 ]
Jung, Dongsoo [1 ]
机构
[1] Inha Univ, Dept Mech Engn, Inchon 402751, South Korea
基金
新加坡国家研究基金会;
关键词
Alternative refrigerant; COP; Capacity; R290 (propane); R170 (ethane); Refrigerant mixture; Heat pump; DOMESTIC REFRIGERATORS; HCFC22;
D O I
10.1016/j.apenergy.2009.04.009
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
in this study, thermodynamic performance of R170/R290 mixture is measured on a heat pump bench tester in an attempt to substitute R22. The bench tester is equipped with a commercial hermetic rotary compressor providing a nominal capacity of 3.5 kW. All tests are conducted under the summer cooling and winter heating conditions of 7/45 degrees C and -7/41 degrees C in the evaporator and condenser, respectively. During the tests, the composition in R170/R290 mixture is varied from 0% to 10% with an interval of 2%. Test results show that the coefficient of performance (COP) and capacity of R290 are up to 15.4% higher and 7.5% lower, respectively than those of R22 for two conditions. For R170/R290 mixture, the COP decreases and the capacity increases with an increase in the composition of R170. The mixture of R170/R290 mixture at 4%/96% composition shows the similar capacity and COP as those of R22. For the mixture, the compressor discharge temperature is 17-28 degrees C lower than that of R22. For R170/R290 mixture, there is no problem with mineral oil since the mixture is composed of hydrocarbons. The amount of charge is reduced up to 58% as compared to R22. Overall, R170/R290 mixture is a good long term 'drop-in' candidate from the view point of energy efficiency and greenhouse warming to replace R22 in residential air-conditioners and heat pumps (C) 2009 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2598 / 2603
页数:6
相关论文
共 50 条
  • [21] EXPERIMENTAL STUDY OF R290 ENHANCED SYSTEM PERFORMANCE IN RESIDENTIAL AIR-CONDITIONERS AND HEAT PUMPS
    Xu, B.
    Chen, J. P.
    Qi, Z. G.
    Li, F.
    23RD IIR INTERNATIONAL CONGRESS OF REFRIGERATION, 2011, 23 : 1576 - +
  • [22] Comparative analysis of the domestic hot water production with R290 and R744 heat pumps
    Masip, Ximo
    Hervas-Blasco, Estefania
    Navarro-Peris, Emilio
    Corberan, Jose M.
    14TH IIR GUSTAV-LORENTZEN CONFERENCE ON NATURAL FLUIDS, 2020, : 543 - 548
  • [23] Experimental analysis on R290 solubility and R290/oil mixture viscosity in oil sump of the rotary compressor
    Wu, Jianhua
    Chen, Zhenhua
    Lin, Jie
    Li, Jinbo
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2018, 94 : 24 - 32
  • [24] Assessment of R290 as a possible alternative to R22 in direct expansion solar assisted heat pumps
    Paradeshi L.
    Mokkala S.
    Simon J.
    Thermal Science, 2017, 21 : 369 - 378
  • [25] RESEARCH ON THE OPTIMUM HEAT REJECTION PRESSURE IN A TRANSCRITICAL R744/R290 MIXTURE CYCLE
    Zhang, X. P.
    Shen, H. G.
    Wang, F. K.
    Fan, X. W.
    7TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, PROCEEDINGS OF ISHVAC 2011, VOLS I-IV, 2011, : 887 - 893
  • [26] ASSESSMENT OF R290 AS A POSSIBLE ALTERNATIVE TO R22 IN DIRECT EXPANSION SOLAR ASSISTED HEAT PUMPS
    Paradeshi, Lokesh
    Mokkala, Srinivas
    Simon, Jayaraj
    THERMAL SCIENCE, 2017, 21 : S369 - S378
  • [27] Chiller Performance Study with Refrigerant R290
    Fuadi, Zulfa
    Yatim, Ardiyansyah
    Rizky, Rachmah
    Aisyah, Nyayu
    Alhamid, Idrus
    Budihardjo, Budihardjo
    Putra, Nandy
    10TH INTERNATIONAL MEETING OF ADVANCES IN THERMOFLUIDS (IMAT 2018): SMART CITY: ADVANCES IN THERMOFLUID TECHNOLOGY IN TROPICAL URBAN DEVELOPMENT, 2019, 2062
  • [28] Determination of the optimum heat rejection pressure in transcritical cycles working with R744/R290 mixture
    Zhang, X. P.
    Wang, F.
    Fan, X. W.
    Wei, X. L.
    Wang, F. K.
    APPLIED THERMAL ENGINEERING, 2013, 54 (01) : 176 - 184
  • [29] Re: R-290 in heat pumps
    Underwood, D
    ASHRAE JOURNAL, 2003, 45 (03) : 20 - 20
  • [30] Experimental Study on the Thermal Performance of R600a, R290 and R600a/R290 Mixtures in a Retrofit R134a Refrigeration System
    Ramathe, Teboho
    Huan, Zhongjie
    Mwesigye, Aggrey
    PROCEEDINGS OF THE 13TH CONFERENCE ON THE INDUSTRIAL AND COMMERCIAL USE OF ENERGY, 2015, : 178 - 186