Experimental analysis of dehumidification performance of an evaporative cooling-assisted internally cooled liquid desiccant dehumidifier

被引:38
|
作者
Park, Joon-Young [1 ]
Kim, Beom-Jun [1 ]
Yoon, Soo-Yeol [1 ]
Byon, Yoo-Suk [1 ]
Jeong, Jae-Weon [1 ]
机构
[1] Hanyang Univ, Coll Engn, Dept Architectural Engn, 222 Wangsimni Ro, Seoul 04763, South Korea
基金
新加坡国家研究基金会;
关键词
Dehumidification system; Internally cooled liquid desiccant system; Desiccant cooling; Evaporative cooling; MASS-TRANSFER PROCESSES; HEAT; MODEL;
D O I
10.1016/j.apenergy.2018.10.101
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The aim of this study is to empirically investigate the impact of the working-to-primary air flow ratio variation on the dehumidification performance of an evaporative cooling-assisted internally cooled liquid desiccant dehumidifier. In the experiment, the process air passed through the primary (or dehumidification) channels of the internally cooled liquid desiccant dehumidifier at a constant flow rate, while the working air flow passing through the secondary (or evaporative cooling) channels was modulated to vary the working-to-primary air flow ratio from 0.25 to 1.0 in 0.25 increments. To evaluate the impact of the working-to-primary air flow ratio on the dehumidification and cooling performance of the internally cooled liquid desiccant dehumidifier, four different performance indices, i.e., cooling capacity, wet-bulb effectiveness, volumetric mass transfer coefficient, and coefficient of performance, were measured in a series of experiments performed under various working-to primary air flow ratios. From those performance indicators, the overall heat, mass transfer performance, and energy efficiency of the internally cooled liquid desiccant dehumidifier could be rated. The experimental results indicate that the maximum values of the four selected performance indices are obtained at a working-to-primary air flow ratio of 0.5. To verify the reliability of the experimental results, a detailed simulation of the internally cooled liquid desiccant dehumidifier was performed using a sorption system simulation program (SorpSim). The measured performance data was in good agreement with the simulation results, within 20% error bounds. Consequently, we determined that the optimal dehumidification and cooling performance of the internally cooled liquid desiccant dehumidifier could be expected when the working-to-primary air flow ratio is 0.5.
引用
收藏
页码:177 / 185
页数:9
相关论文
共 50 条
  • [1] Cooling and dehumidification performance analysis of internally-cooled liquid desiccant absorbers
    Khan, AY
    APPLIED THERMAL ENGINEERING, 1998, 18 (05) : 265 - 281
  • [2] Experimental analysis of an internally-cooled liquid desiccant dehumidifier
    Zhang, Tao
    Liu, Xiaohua
    Jiang, Jingjing
    Chang, Xiaoming
    Jiang, Yi
    BUILDING AND ENVIRONMENT, 2013, 63 : 1 - 10
  • [3] Performance analysis on the internally cooled dehumidifier using liquid desiccant
    Liu, X. H.
    Chang, X. M.
    Xia, J. J.
    Jiang, Y.
    BUILDING AND ENVIRONMENT, 2009, 44 (02) : 299 - 308
  • [4] Counter-crossflow indirect evaporative cooling-assisted liquid desiccant dehumidifier: Model development and parameter analysis
    Zhang, Yanling
    Zhang, Hao
    Yang, Hongxing
    Chen, Yi
    Leung, Chun Wah
    APPLIED THERMAL ENGINEERING, 2022, 217
  • [5] Performance numerical analysis on an internally-cooled liquid desiccant dehumidifier
    Chan, X. M.
    Liu, X. H.
    Jiang, Y.
    BUILDING SIMULATION 2007, VOLS 1-3, PROCEEDINGS, 2007, : 607 - 613
  • [6] Energy benefit of a cascade liquid desiccant dehumidification in a desiccant and evaporative cooling-assisted building air-conditioning system
    Park, Joon-Young
    Dong, Hye-Won
    Cho, Hye-Jin
    Jeong, Jae-Weon
    APPLIED THERMAL ENGINEERING, 2019, 147 : 291 - 301
  • [7] Experimental and Theoretical Study of an Internally Cooled Liquid Desiccant Dehumidifier
    ZHENG Xin
    LU Yuan
    WANG Bo
    ZHAO Lifeng
    XIAO Yunhan
    Journal of Thermal Science, 2023, 32 (04) : 1684 - 1696
  • [8] Experimental and Theoretical Study of an Internally Cooled Liquid Desiccant Dehumidifier
    Xin Zheng
    Yuan Lu
    Bo Wang
    Lifeng Zhao
    Yunhan Xiao
    Journal of Thermal Science, 2023, 32 : 1684 - 1696
  • [9] Experimental and Theoretical Study of an Internally Cooled Liquid Desiccant Dehumidifier
    Zheng, Xin
    Lu, Yuan
    Wang, Bo
    Zhao, Lifeng
    Xiao, Yunhan
    JOURNAL OF THERMAL SCIENCE, 2023, 32 (04) : 1684 - 1696
  • [10] PERFORMANCE ANALYSIS ON THE INTERNALLY COOLED DEHUMIDIFIER USING TWO LIQUID DESICCANT SOLUTIONS
    Koronaki, I. P.
    Christodoulaki, R. I.
    Papaefthimiou, V. D.
    Rogdakis, E. D.
    PROCEEDINGS OF THE ASME 11TH BIENNIAL CONFERENCE ON ENGINEERING SYSTEMS DESIGN AND ANALYSIS, 2012, VOL 2, 2012, : 627 - 638