Thermal environment and air quality in office with personalized ventilation combined with chilled ceiling

被引:70
|
作者
Lipczynska, Aleksandra [1 ,2 ]
Kaczmarczyk, Jan [1 ]
Melikov, Arsen K. [2 ]
机构
[1] Silesian Tech Univ, Dept Heating Ventilat & Dust Removal Technol, PL-44100 Gliwice, Poland
[2] Tech Univ Denmark, Dept Civil Engn, Int Ctr Indoor Environm & Energy, DK-2800 Lyngby, Denmark
关键词
Personalized ventilation; Radiant cooling; Thermal comfort; Contaminant distribution; Personal exposure; DISPLACEMENT VENTILATION; EVAPORATIVE COOLER; HUMAN RESPONSE; PERFORMANCE; COMFORT; CONJUNCTION; TEMPERATURE; DESIGN; SYSTEM; HEALTH;
D O I
10.1016/j.buildenv.2015.05.035
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The thermal environment and air quality conditions provided with combined system of chilled ceiling and personalized ventilation (PV) were studied in a simulated office room for two occupants. The proposed system was compared with total volume HVAC solutions used today, namely mixing ventilation and chilled ceiling combined with mixing ventilation. The objective of the study was to evaluate whether PV can be the only ventilation system in the rooms equipped with chilled ceiling. The room air temperature was 26 degrees C in cases with traditional systems and 28 degrees C when PV was used. PV supplied air with the temperature of 25 degrees C. PV improved thermal conditions and was up to nearly 10 times more efficient in delivering clean air at workstations than mixing ventilation systems, which resulted in strong protection of occupants from the cross-infection. In the room space outside workstations no substantial differences in thermal environment were found between studied systems. The room air mixing with PV working alone was at the same level as with mixing ventilation. No substantial differences in contaminants' concentration distribution and air-change effectiveness were found between the studied systems in the occupied zone outside workstations. (C) 2015 Elsevier Ltd. All rights reserved.
引用
下载
收藏
页码:603 / 614
页数:12
相关论文
共 50 条
  • [31] Study on indoor thermal environment and air quality of office rooms controlled by personal displacement ventilation using CFD
    Zhao, JN
    Wang, LN
    Liu, J
    Gao, J
    Luo, ZW
    INDOOR AIR 2005: PROCEEDINGS OF THE 10TH INTERNATIONAL CONFERENCE ON INDOOR AIR QUALITY AND CLIMATE, VOLS 1-5, 2005, : 664 - 668
  • [32] An experimental study of air flow and temperature distribution in a room with displacement ventilation and a chilled ceiling
    Rees, Simon J.
    Haves, Philip
    BUILDING AND ENVIRONMENT, 2013, 59 : 358 - 368
  • [33] Optimized Operation of Combined Chilled Ceiling Displacement Ventilation System Using Genetic Algorithm
    Mossolly, Mounir
    Ghaddar, Nesreen
    Ghali, Kamel
    Jensen, Lars
    ASHRAE TRANSACTIONS 2008, VOL 114, PT 2, 2008, 114 : 541 - +
  • [34] SUBJECTIVE ASSESSMENTS OF THERMAL SENSATION FOR CEILING MOUNTED PERSONALIZED VENTILATION SYSTEM
    Yang, Bin
    Sekhar, Chandra S.
    Melikov, Arsen K.
    FIFTH INTERNATIONAL WORKSHOP ON ENERGY AND ENVIRONMENT OF RESIDENTIAL BUILDINGS AND THIRD INTERNATIONAL CONFERENCE ON BUILT ENVIRONMENT AND PUBLIC HEALTH, VOL I AND II, PROCEEDINGS, 2009, : 401 - 408
  • [35] Experimental Study of Indoor Air Distribution and Thermal Environment in a Ceiling Cooling Room with Mixing Ventilation, Underfloor Air Distribution and Stratum Ventilation
    Wu, Xiaozhou
    Gao, Hao
    Zhao, Mingming
    Gao, Jie
    Tian, Zhen
    Li, Xiangli
    BUILDINGS, 2023, 13 (09)
  • [36] Ceiling personalized ventilation combined with desk fans for reduced direct and indirect cross-contamination and efficient use of office space
    Habchi, Carine
    Ghali, Kamel
    Ghaddar, Nesreen
    Chakroun, Walid
    Alotaibi, Sorour
    ENERGY CONVERSION AND MANAGEMENT, 2016, 111 : 158 - 173
  • [37] Thermal and ventilation performance of combined passive chilled beam and displacement ventilation systems
    Shan, Wenyu
    Rim, Donghyun
    ENERGY AND BUILDINGS, 2018, 158 : 466 - 475
  • [38] Effects of combined central air conditioning diffusers and window-integrated ventilation system on indoor air quality and thermal comfort in an office
    Park, Dong Yoon
    Chang, Seongju
    SUSTAINABLE CITIES AND SOCIETY, 2020, 61
  • [39] The Influence of Evenly Distributed Ceiling Mounted Personalized Ventilation Devices on the Indoor Environment
    Bin, Yang
    Sekhar, S. C.
    INTERNATIONAL JOURNAL OF VENTILATION, 2008, 7 (02) : 99 - 112
  • [40] Optimized Strategy for Combined Liquid Desiccant Dehumidification Membrane with Chilled Ceiling and Displacement Ventilation System
    Muslmani, Mohamad
    Ghaddar, Nesreen
    Ghali, Kamel
    6TH INTERNATIONAL CONFERENCE ON ENERGY RESEARCH AND DEVELOPMENT, 2016, : 25 - 32