Feasibility study for partial discharge detection and defective region identification in power transformers by using distributed sensors

被引:8
|
作者
Mohammadi, Hasan [1 ]
Haghjoo, Farhad [1 ]
机构
[1] Shahid Beheshti Univ, Abbaspour Sch Engn, Dept Elect Engn, Tehran, Iran
关键词
partial discharge measurement; power transformer insulation; transformer cores; signal detection; transformer windings; partial discharge detection; defective region identification; power transformers; distributed sensors; partial discharge monitoring; insulation deterioration process; insulation condition; degradation mechanisms; transformer core; PD signal detection; defective phase identification; HV windings; quasireal PD signals; three-phase transformer; limited-band approach; broadband analysis; IEC60270; recommendation; apparent power 50 kVA; voltage; 20; kV; 400; V; PD DETECTION; LOCATION; LOCALIZATION;
D O I
10.1049/iet-gtd.2016.0204
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Monitoring of partial discharge (PD) and its progress as the main cause of the insulation deterioration process in power transformers can encompass valuable information about the related insulation condition and reveals degradation mechanisms. In this study, some simple sensors, which are made from a few turns wrapped around the transformer core, are used to detect PD signals. Moreover, a feasibility study is done to identify defective phase/region based on the captured PD signals waveforms through these sensors. The idea is implemented on a 50 kVA, 20 kV/400 V three-phase transformer by injecting artificial and quasi-real PD signals to different sections of HV windings. Also, various transformer connections are considered in the experimental studies to find the effect of them on the waveforms of the captured signals (e.g. peak-to-peak value and signal energy). The obtained experimental results show that small PDs (as low as 10 pC) is detectable by the mentioned sensors and defective phase can be identified in all of transformer connection cases. Furthermore, considering failure to identify defective regions by broadband analysis, a limited-band approach is proposed through obtaining |H(s)| for the sensors. The results show that exact defective phase/region identification is feasible by selecting a frequency band compatible with IEC60270 recommendation.
引用
收藏
页码:4006 / 4023
页数:18
相关论文
共 50 条
  • [1] Distributed Capacitive Sensors for Partial Discharge Detection and Defective Region Identification in Power Transformers
    Mohammadi, Hasan
    Haghjoo, Farhad
    [J]. IEEE SENSORS JOURNAL, 2017, 17 (06) : 1626 - 1634
  • [2] Feasibility study to use the current transformers as inductive partial discharge sensors
    Haghjoo, Farhad
    Savaei, Ali
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2016, 10 (15) : 3786 - 3794
  • [3] Partial discharge detection and localization in power transformers
    Gockenbach, E
    [J]. 2004 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2004, : 466 - 469
  • [4] Partial discharge location in power transformers using wideband RF detection
    Tang, Zhiguo
    Li, Chengrong
    Cheng, Xu
    Wang, Wei
    Li, Jinzhong
    Li, Jun
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2006, 13 (06) : 1193 - 1199
  • [5] Study on Location of Acoustic Emission Partial Discharge Detection in Power Transformers
    Zhang, Linhai
    Liu, Gang
    Li, Cheng
    Li, Yanming
    Zhang, Longjun
    Lu, Guojun
    [J]. 2007 IEEE INTERNATIONAL CONFERENCE ON SOLID DIELECTRICS, VOLS 1 AND 2, 2007, : 589 - +
  • [6] Partial Discharge Localization in Transformers Using UHF Sensors
    Sinaga, H. H.
    Phung, B. T.
    Ao, P. L.
    Blackburn, T. R.
    [J]. 2011 ELECTRICAL INSULATION CONFERENCE (EIC), 2011, : 64 - 68
  • [7] Design and testing of UHF sensors for Partial Discharge detection in transformers
    Lopez-Roldan, J.
    Tang, T.
    Gaskin, M.
    [J]. PROCEEDINGS OF 2008 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS, 2007, : 1052 - +
  • [8] Partial Discharge Monitoring in Power Transformers Using Low-Cost Piezoelectric Sensors
    Castro, Bruno
    Clerice, Guilherme
    Ramos, Caio
    Andreoli, Andre
    Baptista, Fabricio
    Campos, Fernando
    Ulson, Jose
    [J]. SENSORS, 2016, 16 (08)
  • [9] Partial discharge monitoring for power transformers using UHF sensors Part 1: Sensors and signal interpretation
    Judd, MD
    Yang, L
    Hunter, IBB
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2005, 21 (02) : 5 - 14
  • [10] PIFA ANTENNA FOR PARTIAL DISCHARGE DETECTION IN POWER TRANSFORMERS
    Szymczak, Cyprian