Condition Assessment of Arc Contacts through Dynamic Resistance Measurement (DRM) and Wavelet Analysis

被引:0
|
作者
Abdollah, Mohammad [1 ]
Razi-Kazemi, Ali Asghar [1 ]
机构
[1] KN Toosi Univ, Elect Engn, Tehran 1631714191, Iran
关键词
circuit breaker; arc contact; dynamic resistance measurement;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Circuit Breakers constitute one of the main electromechanical components of a power grid, playing an essential role in protecting other network components such as transformers and generators. Throughout their lifetimes, CBs experience thermal and mechanical stresses and other factors. The operation of CBs under short-circuit currents or the high number of times of performance at a fraction of short-circuit currents can lead to gradual deterioration of the inner parts of the interruption chamber such as the main and arc contacts. Dynamic resistance measurement test is an effective method to assess the condition of contacts in CBs. This paper attempted to examine the effect of erosion in moving arc contacts through analysis of dynamic strength properties measured from a real 24 kV gas CB. This paper involved the essential characteristics for assessing the condition of arc contacts in a CB through wavelet analysis and the prediction of erosion in arc contacts.
引用
收藏
页码:1139 / 1143
页数:5
相关论文
共 50 条
  • [1] Parameters for Condition Assessment of the High Voltage Circuit Breakers Arcing Contacts using Dynamic Resistance Measurement
    Obarcanin, Kerim
    Ostojic, Radenko
    Dzuzdanovic, Samir
    [J]. 2017 40TH INTERNATIONAL CONVENTION ON INFORMATION AND COMMUNICATION TECHNOLOGY, ELECTRONICS AND MICROELECTRONICS (MIPRO), 2017, : 1044 - 1048
  • [2] Tap Changer Condition Assessment Using Dynamic Resistance Measurement
    Osmanbasic, Edis
    Skelo, Goran
    [J]. SPECIAL ISSUE OF THE 4TH INTERNATIONAL COLLOQUIUM -TRANSFORMER RESEARCH AND ASSET MANAGEMENT, 2017, 202 : 52 - 64
  • [3] Study of Ablation of Arc Contacts and Dynamic Contact Resistance in High Current Breaker
    Xing, Licheng
    Zhang, Xiaodong
    Tong, Qingbin
    Xing, Gaoqi
    [J]. JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2020, 15 (03) : 1015 - 1023
  • [4] Study of Ablation of Arc Contacts and Dynamic Contact Resistance in High Current Breaker
    Licheng Xing
    Xiaodong Zhang
    Qingbin Tong
    Gaoqi Xing
    [J]. Journal of Electrical Engineering & Technology, 2020, 15 : 1015 - 1023
  • [5] Wavelet analysis and NDT for condition assessment of historic Masonry Bridge
    Kilic, Gokhan
    [J]. STRUCTURES, 2022, 45 : 275 - 283
  • [6] Tribology of material contacts under dynamic loading, studied by electrical resistance measurement
    Luo, XC
    Chung, DDL
    [J]. SURFACE ENGINEERING 2001 - FUNDAMENTALS AND APPLICATIONS, 2001, 697 : 323 - 328
  • [7] Condition Assessment of Power OLTC by Vibration Analysis Using Wavelet Transform
    Rivas, Edwin
    Burgos, Juan Carlos
    Garcia-Prada, Juan Carlos
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (02) : 687 - 694
  • [8] Insulation Condition Assessment Through Spectroscopic and Chemometrics Analysis
    Stevens, Gary C.
    Herman, Henryk
    Baird, Patrick
    [J]. 2007 IEEE INTERNATIONAL CONFERENCE ON SOLID DIELECTRICS, VOLS 1 AND 2, 2007, : 717 - +
  • [9] Online Condition Assessment of Interruption Chamber of Gas Circuit Breakers Using Arc Voltage Measurement
    Bagherpoor, Asghar
    Rahimi-Pordanjani, Sadegh
    Razi-Kazemi, Ali Asghar
    Niayesh, Kaveh
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (04) : 1776 - 1783
  • [10] An intrinsic assessment and comparison of biometric systems through wavelet analysis
    Burnes, JP
    Tien, JM
    Chang, WJ
    [J]. 2003 IEEE INTERNATIONAL CONFERENCE ON SYSTEMS, MAN AND CYBERNETICS, VOLS 1-5, CONFERENCE PROCEEDINGS, 2003, : 4514 - 4521