Tap Changer Condition Assessment Using Dynamic Resistance Measurement

被引:9
|
作者
Osmanbasic, Edis [1 ]
Skelo, Goran [2 ]
机构
[1] DV Power, Stockholmsvagen 18, S-18150 Lidingo, Sweden
[2] Elektroprenos BiH, Vilsonovo Setaliste 15, Sarajevo 7100, Bosnia & Herceg
关键词
Tap changer; DRM; Transformer; OLTC; Transformer maintenace; OLTC failures;
D O I
10.1016/j.proeng.2017.09.694
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The DVtest method (Dynamic Resistance Measurement - DRM) is an off-line, non-destructive testing method based on a dc current being injected through a winding and a tap changer as it moves through all of its positions. The test current is recorded with high resolution. Also, an on-load tap changer (OLTC) motor current can be recorded simultaneously with the test current. A high sampling rate is very important due to fast transition processes (transition time of a resistor OLTC type is approximately 50 ms). The DRM method has been proven as a very effective method in the early detection of possible faults on on-load tap-changers (OLTCs). This test may be used to detect problems such as slow transition time, open circuits, problems with contacts, transition resistors, mechanism, motor control, and much more. This paper provides the description of the DVtest method for OLTC analysis. In addition, a few interesting cases about detected tap changer defects and diagnostic analysis are presented, as well. (C) 2017 The Authors. Published by Elsevier Ltd.
引用
收藏
页码:52 / 64
页数:13
相关论文
共 50 条
  • [1] Diagnosis of On-Load Tap Changer (OLTC) Using Dynamic Resistance Measurement
    Aziz, Mohd Azhar Abdul
    Talib, Mohd Aizam
    Arumugam, Ragavan
    [J]. 2014 IEEE 8TH INTERNATIONAL POWER ENGINEERING AND OPTIMIZATION CONFERENCE (PEOCO), 2014, : 494 - 497
  • [2] On-Load Tap Changer's Dynamic Resistance Measurement Settings and Interpretation
    Erbrink, J. J.
    Aditya, J.
    Chmura, L. A.
    Smit, J. J.
    Leich, R.
    Quak, B.
    [J]. 2011 ELECTRICAL INSULATION CONFERENCE (EIC), 2011, : 54 - 58
  • [3] On-load tap changer diagnosis with dynamic resistance measurements
    Jongen, Rogier
    Seitz, Paul P.
    Strehl, Thomas
    Smit, Johan
    Leich, Rory
    Gulski, Edward
    [J]. PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), 2012, : 485 - 488
  • [4] Power transformer reliability assessment based on tap changer dynamic resistance and motor current measurements
    Jokic, Srdjan
    Cincar, Nada
    Novakovic, Bojana
    [J]. 2019 18TH INTERNATIONAL SYMPOSIUM INFOTEH-JAHORINA (INFOTEH), 2019,
  • [5] Diagnosis of Onload Tap Changer Contact Degradation by Dynamic Resistance Measurements
    Erbrink, Jur J.
    Gulski, Edward
    Smit, Johan J.
    Seitz, Paul P.
    Quak, Ben
    Leich, Rory
    Malewski, Ryszard
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) : 2121 - 2131
  • [6] On-load Tap Changer Diagnosis: Interpretation of Dynamic Resistance Deviations
    Erbrink, J. J.
    Gulski, E.
    Smit, J. J.
    Leich, R.
    Seitz, P. P.
    Quak, B.
    [J]. CONFERENCE RECORD OF THE 2010 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION (ISEI), 2010,
  • [7] Measurement Method for the Transition Resistance of On-load Tap Changer Based on Signal Processing
    Song, Dongdong
    Ding, Laiwei
    Dong, Biao
    Ma, Yuquan
    Liu, Xiyin
    [J]. Gaodianya Jishu/High Voltage Engineering, 2020, 46 (03): : 922 - 930
  • [8] A STUDY ON THE CONDITION OF REVERSE CONTROL ACTION OF TAP CHANGER IN A SINGLE ON-LOAD TAP CHANGER POWER-SYSTEM
    YORINO, N
    FUNAHASHI, A
    SASAKI, H
    KUBOKAWA, J
    [J]. ELECTRICAL ENGINEERING IN JAPAN, 1994, 114 (07) : 44 - 55
  • [9] A Joint Vibration and Arcing Measurement System for Online Condition Monitoring of Onload Tap Changer of the Power Transformer
    Seo, Junhyuck
    Ma, Hui
    Saha, Tapan Kumar
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (02) : 1031 - 1038
  • [10] Parameters for Condition Assessment of the High Voltage Circuit Breakers Arcing Contacts using Dynamic Resistance Measurement
    Obarcanin, Kerim
    Ostojic, Radenko
    Dzuzdanovic, Samir
    [J]. 2017 40TH INTERNATIONAL CONVENTION ON INFORMATION AND COMMUNICATION TECHNOLOGY, ELECTRONICS AND MICROELECTRONICS (MIPRO), 2017, : 1044 - 1048