A MEMS flow sensor applied in a variable-air-volume unit in a building air-conditioning system

被引:18
|
作者
Shikida, M. [1 ]
Yamazaki, Y. [2 ]
Yoshikawa, K. [2 ]
Sato, Kazuo [3 ]
机构
[1] Nagoya Univ, Ctr Micronano Mechatron, Chikusa Ku, Nagoya, Aichi 4648603, Japan
[2] Nagoya Univ, Dept Micronano Syst Engn, Nagoya, Aichi 4648603, Japan
[3] Nagoya Univ, Dept Micronano Syst Engn, MEMS Lab, Nagoya, Aichi 4648603, Japan
关键词
Flow sensor; Air-conditioning network; SHEAR-STRESS SENSOR;
D O I
10.1016/j.sna.2012.10.009
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A MEMS flow sensor was applied in a variable-air-volume (VAV) unit, composed of a butterfly damper and a flow sensor, to precisely control the supply of air in a large-scale air-conditioning network system used in a building. The MEMS flow sensor is composed of a hot-wire anemometer with an underside cavity to shorten the response time, and it was fabricated on a 25-mu m-thick polyimide film by photolithography and film deposition. The total thickness of the sensor structure is only 525 mu m. Four sensors were attached at 90 degrees to each other on the inner surface of an 8-in, duct, and the outputs obtained by the sensors were averaged. The results of an experimental evaluation of the sensor are as follows. First, the averaged sensor output depends on damper angle and the distance of the sensor from the damper. Second, it is higher than that obtained by a similar sensor in a straight duct. Third, a conversion curve was derived and used to calculate flow rate from the obtained outputs of the four sensors fitted in the VAV unit. (C) 2012 Elsevier B.V. All rights reserved.
引用
收藏
页码:212 / 217
页数:6
相关论文
共 50 条
  • [41] AIR-CONDITIONING SYSTEM RETROFIT FOR AN HISTORIC OFFICE BUILDING
    WESSEL, DJ
    ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1992, 34 (07): : 38 - &
  • [42] Performance evaluation of an actual building air-conditioning system
    Othman, M. F.
    Abdullah, H.
    Sulaiman, N. A.
    Hassan, M. Y.
    2ND INTERNATIONAL CONFERENCE ON MECHANICAL ENGINEERING RESEARCH (ICMER 2013), 2013, 50
  • [43] Reheat optimization of the variable-air-volume box
    Kusiak, Andrew
    Li, Mingyang
    ENERGY, 2010, 35 (05) : 1997 - 2005
  • [44] Active Disturbance Rejection Based Iterative Learning Control for Variable Air Volume Central Air-Conditioning System
    Lu, Shiying
    Ai, Wei
    Li, Xiangyang
    PROCEEDINGS OF 2018 IEEE 7TH DATA DRIVEN CONTROL AND LEARNING SYSTEMS CONFERENCE (DDCLS), 2018, : 1073 - 1078
  • [45] Global optimal control of variable air volume air-conditioning system with iterative learning: an experimental case study
    Meng, Qing-long
    Yan, Xiu-ying
    Ren, Qing-chang
    JOURNAL OF ZHEJIANG UNIVERSITY-SCIENCE A, 2015, 16 (04): : 302 - 315
  • [46] KRUPPS NEW AIR-CONDITIONING UNIT
    UFER, H
    KRIEGEL, E
    TECHNISCHE MITTEILUNGEN KRUPP WERKSBERICHTE, 1969, 27 (02): : 69 - &
  • [47] AIR-CONDITIONING CONTROL FOR A CONDOMINIUM BUILDING
    HAINES, RW
    HEATING-PIPING-AIR CONDITIONING, 1983, 55 (10): : 121 - 122
  • [48] AIR-CONDITIONING SYSTEMS OF THE KI BUILDING
    OKAMOTO, A
    HASEGAWA, T
    TOGARI, S
    ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1992, 34 (08): : 33 - 36
  • [49] Optimal control of combined air conditioning system with variable refrigerant flow and variable air volume for energy saving
    Zhu, Yonghua
    Jin, Xinqiao
    Fang, Xing
    Du, Zhimin
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2014, 42 : 14 - 25
  • [50] ATTENUATING NOISE GENERATED BY VARIABLE-AIR-VOLUME SYSTEMS
    STOKES, R