Determination of copper in liquid and solid insulation for large electrical equipment by ICP-OES. Application to copper contamination assessment in power transformers

被引:20
|
作者
Bruzzoniti, Maria Concetta [1 ]
De Carlo, Rosa Maria [1 ]
Sarzanini, Corrado [1 ]
Maina, Riccardo [2 ]
Tumiatti, Vander [2 ]
机构
[1] Univ Turin, Dept Chem, I-10125 Turin, Italy
[2] Sea Marconi Technol, I-10093 Turin, Italy
关键词
Copper determination; ICP-OES; Real oil samples; Power transformers; Copper deposition; EMISSION-SPECTROMETRY; CORROSIVE SULFUR; OILS; PCDF; DIBENZOFURANS; DEGRADATION; FAILURES; PCBS;
D O I
10.1016/j.talanta.2012.07.009
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
Copper is one of the main constituents of the components in power transformers and its presence both in liquid (mineral oil) and in solid (Kraft paper) insulators can lead to enhanced dielectric losses and to the subsequent deterioration of their insulating properties. Recently the latter have been correlated to plant failures which in turn may have severe impact on the environment. This paper describes the direct analysis of copper in insulating mineral oil by ICP-OES and how it was first optimized compared to the official American Society for Testing and Materials (ASTM) D7151 method. Detection and quantification limits of 8.8 mu g kg(-1) and 29.3 mu g kg(-1) were obtained. Secondly, copper determination was improved by coupling a microwave assisted dissolution procedure of the mineral oil which avoided the problems, in the real samples, due to the presence of solid species of copper which cannot be nebulized following traditional methods described in literature. Sixteen mineral insulating oils sampled from transformers in service were analyzed before and after dissolution. In order to evaluate copper speciation, size fractionation was performed by filtration on PTFE filters (0.45, 1 and 5 mu m). This test was performed on all the oil samples. Finally, because of the key role of the solid insulator in failed transformers, the Authors applied the developed method to study the copper deposition tendency onto the insulating Kraft paper tapes exerted by two unused oils (a corrosive and a non-corrosive one) under defined ageing conditions. (C) 2012 Elsevier B.V. All rights reserved.
引用
收藏
页码:703 / 711
页数:9
相关论文
共 14 条
  • [1] Determination of tantalum and nitrogen for semiconductor copper metallization technology by ICP-OES and its application to XRF
    Onuma, M
    Takenaka, M
    Yabuki, M
    Hayashi, M
    [J]. BUNSEKI KAGAKU, 2003, 52 (06) : 475 - 480
  • [2] Application of Modified BCR Sequential Extraction Method for the Fractionation and ICP-OES Determination of Copper in Asphaltite Combustion Waste
    Aydin, Firat
    Gunduz, Beniz
    Aydin, Isil
    Akba, Osman
    Saydut, Abdurrahman
    Hamamci, Candan
    [J]. ATOMIC SPECTROSCOPY, 2013, 34 (04) : 140 - 145
  • [3] Ionic liquid based dispersive liquid-liquid microextraction combined with ICP-OES for the determination of trace quantities of cobalt, copper, manganese, nickel and zinc in environmental water samples
    Leila Ranjbar
    Yadollah Yamini
    Abolfazl Saleh
    Shahram Seidi
    Mohammad Faraji
    [J]. Microchimica Acta, 2012, 177 : 119 - 127
  • [4] Ionic liquid based dispersive liquid-liquid microextraction combined with ICP-OES for the determination of trace quantities of cobalt, copper, manganese, nickel and zinc in environmental water samples
    Ranjbar, Leila
    Yamini, Yadollah
    Saleh, Abolfazl
    Seidi, Shahram
    Faraji, Mohammad
    [J]. MICROCHIMICA ACTA, 2012, 177 (1-2) : 119 - 127
  • [5] The high-frequency phenomenon of copper clad aluminum wires which are lower the alternating current resistance than copper solid wires, and the application of copper clad aluminum wires to the electrical equipment
    Ueda, Katsuhiko
    Hung, Chefen
    [J]. ELECTRICAL ENGINEERING IN JAPAN, 2023, 216 (03)
  • [6] Attapulgite modified with 2-hydroxy-1-naphthaldehyde as selective solid-phase extractant for determination of copper(II) in environmental samples by ICP-OES
    Zhenhua Li
    Li Zhang
    Zhipeng Zang
    Xijun Chang
    Xiaojun Zou
    [J]. Microchimica Acta, 2010, 171 : 161 - 168
  • [7] Attapulgite modified with 2-hydroxy-1-naphthaldehyde as selective solid-phase extractant for determination of copper(II) in environmental samples by ICP-OES
    Li, Zhenhua
    Zhang, Li
    Zang, Zhipeng
    Chang, Xijun
    Zou, Xiaojun
    [J]. MICROCHIMICA ACTA, 2010, 171 (1-2) : 161 - 168
  • [8] Factorial design optimization of experimental variables in the on-line separation/preconcentration of copper in water samples using solid phase extraction and ICP-OES determination
    Escudero, Luis A.
    Cerutti, S.
    Olsina, R. A.
    Salonia, J. A.
    Gasquez, J. A.
    [J]. JOURNAL OF HAZARDOUS MATERIALS, 2010, 183 (1-3) : 218 - 223
  • [9] Membrane solid phase microextraction with alumina hollow fiber on line coupled with ICP-OES for the determination of trace copper, manganese and nickel in environmental water samples
    Cui, Chao
    He, Man
    Hu, Bin
    [J]. JOURNAL OF HAZARDOUS MATERIALS, 2011, 187 (1-3) : 379 - 385
  • [10] Selective solid phase extraction of copper using a new Cu(II)-imprinted polymer and determination by inductively coupled plasma optical emission spectroscopy (ICP-OES)
    Yilmaz, Vedat
    Arslan, Zikri
    Hazer, Orhan
    Yilmaz, Hayriye
    [J]. MICROCHEMICAL JOURNAL, 2014, 114 : 65 - 72