Enhancing Worker and Equipment Protection Through Passive Arc-Fault Mitigation

被引:2
|
作者
Parsons, Antony [1 ]
Faber, Timothy [2 ]
Metzdorf, Mark A. [3 ]
机构
[1] Schneider Elect, Austin, TX 78758 USA
[2] Schneider Elect, Cedar Rapids, IA 52404 USA
[3] BP Prod North Amer Inc, Naperville, IL 60563 USA
关键词
Arc flash; arc-resistant switchgear; accident prevention; electrical safety;
D O I
10.1109/TIA.2020.2980489
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Existing arc flash standards like IEEE 1584 and 1584.1 present models that can be used to estimate incident energy levels in power distribution equipment but provide limited direction regarding how equipment construction should be considered in the calculations. Users performing arc flash risk assessments are left to apply engineering judgment when considering how barriers or isolation of components should be considered. This can lead to risk assessments that are inconsistent or incorrect. Current practices regarding arc flash evaluation in barriered and nonbarriered equipment are reviewed based on current standards. Gaps and potential concerns are discussed, including the lack of defined criteria to use in calculations, along with lack of criteria for determining when barrier systems are considered effective at preventing, mitigating, controlling, or containing arcing faults. A description of a new system that provides passive protection in low-voltage distribution equipment is presented. By providing improved protection for the incoming conductors and main circuit breaker itself, this line-side protection system reduces or eliminates the uncertainties, which allows for more consistent and accurate application of risk assessments. The new protection system enables arc flash protection to be provided by a passive, enclosed system that has been tested to verify performance. As such, the calculations and risk assessment are less reliant on assumptions regarding the performance of the equipment. Practical aspects of arc flash analysis and labeling and operation and maintenance of such equipment are also discussed.
引用
收藏
页码:2196 / 2204
页数:9
相关论文
共 10 条
  • [1] Arc-fault protection of branch circuits, cords, and connected equipment
    Parise, G
    Martirano, L
    Nabours, RE
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2004, 40 (03) : 896 - 899
  • [2] Arc-fault protection of branch circuits, cords and connected equipment
    Parise, G
    Martirano, L
    Nabours, RE
    [J]. 2003 IEEE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS TECHNICAL CONFERENCE, CONFERENCE RECORD, 2003, : 85 - 88
  • [3] The arc-fault circuit protection
    Parise, G
    Martirano, L
    Grasselli, U
    Benetti, L
    [J]. CONFERENCE RECORD OF THE 2001 IEEE INDUSTRY APPLICATIONS CONFERENCE, VOLS 1-4, 2001, : 1817 - 1822
  • [4] History of Aircraft Wiring Arc-Fault Protection
    Brusso, Barry C.
    [J]. IEEE INDUSTRY APPLICATIONS MAGAZINE, 2017, 23 (03) : 6 - 11
  • [5] DC arc-fault hazards analysis and protection in photovoltaic system
    Wu, Chunhua
    Xu, Wenxin
    Li, Zhihua
    Wang, Fei
    [J]. Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2020, 41 (09): : 198 - 206
  • [6] Prevention of electrical failure in photovoltaic array-II (ground-fault protection and arc-fault protection)
    [J]. Ishii, Takafumi, 1600, Institute of Electrical Engineers of Japan (134):
  • [7] Design of Fire Detection Equipment Due to The Arc-Fault Series on Low Voltage Networks Based on the Internet of Things (IoT)
    Ilman, Abdillah Fashiha
    Jauhari, Mohammad
    Dzulkiflih
    Nur, Mohammad
    [J]. 2020 THIRD INTERNATIONAL CONFERENCE ON VOCATIONAL EDUCATION AND ELECTRICAL ENGINEERING (ICVEE): STRENGTHENING THE FRAMEWORK OF SOCIETY 5.0 THROUGH INNOVATIONS IN EDUCATION, ELECTRICAL, ENGINEERING AND INFORMATICS ENGINEERING, 2020,
  • [8] IMPROVEMENT IN PASSIVE ARC FLASH PROTECTION THROUGH LIMITING ARCING DURATION
    Faber, Tim
    Schiazza, Terry L.
    Megna, Peter
    [J]. 2015 IEEE PETROLEUM AND CHEMICAL INDUSTRY COMMITTEE CONFERENCE (PCIC), 2015,
  • [9] Designing Of The Relay Protection Of The High-Voltage Power Equipment for Arc Fault by Sensors of the Electrical And Non-Electrical Values
    Nagay, Vladimir I.
    Sarry, Sergey V.
    Nagay, Ivan V.
    [J]. PROCEEDINGS OF THE 8TH INTERNATIONAL SCIENTIFIC SYMPOSIUM ON ELECTRICAL POWER ENGINEERING (ELEKTROENERGETIKA 2015), 2015, : 355 - 358
  • [10] Enhancing Resilience and Reliability of Active Distribution Networks through Accurate Fault Location and Novel Pilot Protection Method
    Xu, Lin
    Fan, Songhai
    Zhang, Hua
    Xiong, Jiayu
    Liu, Chang
    Mo, Site
    [J]. ENERGIES, 2023, 16 (22)