Numerical and experimental study on internally cooled liquid desiccant dehumidification concerning film shrinkage shape and vapor condensation

被引:21
|
作者
Wen, Tao [1 ]
Lu, Lin [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Peoples R China
关键词
Shrinkage; Vapor condensation; Empirical correlation; Falling film dehumidifier; Liquid desiccant; AIR-CONDITIONING EQUIPMENT; MASS-TRANSFER; LICL SOLUTION; COOLED/HEATED DEHUMIDIFIER/REGENERATOR; REGENERATION PERFORMANCE; MODEL DEVELOPMENT; SURFACTANT; FLOW;
D O I
10.1016/j.ijthermalsci.2018.10.046
中图分类号
O414.1 [热力学];
学科分类号
摘要
Falling film has been observed to shrink along its flow direction in a plate dehumidifier. The shrinkage of film reduces the absorption contact area and hence deteriorates the mass transfer performance. Another interesting phenomenon has also been observed, and the condensation of water vapor would occur on the non-wetted area in an internal cooling dehumidifier with a low cooling water temperature. Nevertheless, the film shrinkage and vapor condensation during the dehumidification process were seldom reported. This study developed a new model with the consideration of both the above two factors and phenomena. Besides, a new Sherwood number correlation was proposed based on the experimental data. The influences of different parameters on dehumidification performance were identified. The results indicated that the new model is able to predict the film shrinkage accurately with the average relative wetting ratio difference less than 4%, and the proposed Sherwood number correlation has high prediction accuracy with the mean absolute relative deviation of 7.1%. Then, the weather data of a typical summer day in Hong Kong was chosen to evaluate the influence of vapor condensation. It was found that compared with the situation without condensation, the relative increment of absolute moisture change ranges from 1.2% to 10.7% when concerning vapor condensation. The increment is closely related with the cooling water temperature and air humidity. In the typical summer day, the absolute moisture change has a relative 6.3% increment with the consideration of vapor condensation under certain operating conditions.
引用
收藏
页码:316 / 327
页数:12
相关论文
共 50 条
  • [31] Experimental study of dynamic characteristics of liquid desiccant dehumidification processes
    Wang, Lingshi
    Xiao, Fu
    Niu, Xiaofeng
    Gao, Dian-Ce
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2017, 23 (01) : 91 - 104
  • [32] An experimental study on the dehumidification performance of a counter flow liquid desiccant dehumidifier
    Wang, Lingshi
    Xiao, Fu
    Zhang, Xuejun
    Kumar, Ritunesh
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2016, 70 : 289 - 301
  • [33] Experimental study of a novel subcooling method based on liquid desiccant dehumidification for vapor-compression refrigeration systems
    She, Xiaohui
    Yin, Yonggao
    Luo, Yimo
    Lindeman, Brett
    Zhong, Dan
    Zhang, Xiaosong
    APPLIED THERMAL ENGINEERING, 2018, 130 : 1460 - 1471
  • [34] Dehumidification performance improvement by using liquid desiccant blends - An experimental study
    Kumar, Shiva
    Parida, Subhransu S.
    Kumar, Nitesh
    INDOOR AND BUILT ENVIRONMENT, 2023, 32 (05) : 1020 - 1032
  • [35] Heat and Mass Transfer Enhancement of a Multi-stage Internally-Cooled Membrane-Based Liquid Desiccant Dehumidification
    Fang, Song
    Wu, Qiao-Xian
    Rong, Yang-Yi-Ming
    Zhou, Xia
    Wang, Kai
    Qiu, Li-Min
    Zhi, Xiao-Qin
    Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics, 2021, 42 (09): : 2216 - 2226
  • [36] Mathematical modeling and parametric study of liquid desiccant system with internally-cooled dehumidifier
    Hendijani, Arash Doustani
    Gilani, Neda
    THERMAL SCIENCE AND ENGINEERING PROGRESS, 2018, 5 : 213 - 229
  • [37] EXPERIMENTAL STUDY ON A TWO-STAGE LIQUID DESICCANT DEHUMIDIFICATION SYSTEM USING DUAL DESICCANT SOLUTIONS
    Xiong, Z. Q.
    Wang, R. Z.
    Dai, Y. J.
    HEAT TRANSFER RESEARCH, 2015, 46 (04) : 383 - 397
  • [38] The experimental study of dehumidification and regeneration processes in a fin and tube liquid desiccant system
    Indrawan, Wisnu
    Lubis, Arnas
    Nasruddin
    Alhamid, M. I.
    CASE STUDIES IN THERMAL ENGINEERING, 2022, 39
  • [39] Experimental and theoretical research of a fin-tube type internally-cooled liquid desiccant dehumidifier
    Luo, Yimo
    Shao, Shuangquan
    Xu, Hongbo
    Tian, Chongqing
    Yang, Hongxing
    APPLIED ENERGY, 2014, 133 : 127 - 134
  • [40] Experimental analysis on dehumidification performance of an indoor passive falling film liquid desiccant moisture receptacle
    Chen Jianbo
    Xue Xue
    Qu Minglu
    Han Xing
    Kang Youli
    ENERGY AND BUILDINGS, 2016, 125 : 161 - 170