Numerical and experimental study on internally cooled liquid desiccant dehumidification concerning film shrinkage shape and vapor condensation

被引:21
|
作者
Wen, Tao [1 ]
Lu, Lin [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Peoples R China
关键词
Shrinkage; Vapor condensation; Empirical correlation; Falling film dehumidifier; Liquid desiccant; AIR-CONDITIONING EQUIPMENT; MASS-TRANSFER; LICL SOLUTION; COOLED/HEATED DEHUMIDIFIER/REGENERATOR; REGENERATION PERFORMANCE; MODEL DEVELOPMENT; SURFACTANT; FLOW;
D O I
10.1016/j.ijthermalsci.2018.10.046
中图分类号
O414.1 [热力学];
学科分类号
摘要
Falling film has been observed to shrink along its flow direction in a plate dehumidifier. The shrinkage of film reduces the absorption contact area and hence deteriorates the mass transfer performance. Another interesting phenomenon has also been observed, and the condensation of water vapor would occur on the non-wetted area in an internal cooling dehumidifier with a low cooling water temperature. Nevertheless, the film shrinkage and vapor condensation during the dehumidification process were seldom reported. This study developed a new model with the consideration of both the above two factors and phenomena. Besides, a new Sherwood number correlation was proposed based on the experimental data. The influences of different parameters on dehumidification performance were identified. The results indicated that the new model is able to predict the film shrinkage accurately with the average relative wetting ratio difference less than 4%, and the proposed Sherwood number correlation has high prediction accuracy with the mean absolute relative deviation of 7.1%. Then, the weather data of a typical summer day in Hong Kong was chosen to evaluate the influence of vapor condensation. It was found that compared with the situation without condensation, the relative increment of absolute moisture change ranges from 1.2% to 10.7% when concerning vapor condensation. The increment is closely related with the cooling water temperature and air humidity. In the typical summer day, the absolute moisture change has a relative 6.3% increment with the consideration of vapor condensation under certain operating conditions.
引用
收藏
页码:316 / 327
页数:12
相关论文
共 50 条
  • [21] Performance characteristics of a novel internally-cooled plate membrane liquid desiccant air dehumidification system
    Xiao, Liehui
    Yang, Minlin
    Yuan, Wu-Zhi
    Huang, Si-Min
    APPLIED THERMAL ENGINEERING, 2020, 172
  • [22] Model-based investigation of a heat pump driven, internally cooled liquid desiccant dehumidification system
    Liu, Jun
    Zhang, Tao
    Liu, Xiaohua
    BUILDING AND ENVIRONMENT, 2018, 143 : 431 - 442
  • [23] Performance correlations of an adjacently internally-cooled membrane contactor applied for liquid desiccant air dehumidification
    Huang, Si-Min
    Yang, Minlin
    Hong, Yuxiang
    Ye, Wei-Biao
    APPLIED THERMAL ENGINEERING, 2018, 129 : 1660 - 1669
  • [24] A view on the performance comparison between adiabatic and internally-cooled dehumidification processes using liquid desiccant
    Luo, Jielin
    Wang, Qiliang
    Zhang, Yanling
    Yang, Hongxing
    DESALINATION, 2024, 586
  • [25] Experimental analysis of a novel internally-cooled dehumidifier with self-cooled liquid desiccant
    Lun, Wei
    Li, Kuining
    Liu, Bin
    Zhang, Hongji
    Yang, Yuxiao
    Yang, Cheng
    BUILDING AND ENVIRONMENT, 2018, 141 : 117 - 126
  • [26] Study on an internally-cooled liquid desiccant dehumidifier with CFD model
    Luo, Yimo
    Chen, Yi
    Yang, Hongxing
    Wang, Yuanhao
    APPLIED ENERGY, 2017, 194 : 399 - 409
  • [27] Fabrication and Properties of Micro-Nanoencapsulated Phase Change Materials for Internally-Cooled Liquid Desiccant Dehumidification
    Niu, Xiaofeng
    Xu, Qing
    Zhang, Yi
    Zhang, Yue
    Yan, Yufeng
    Liu, Tao
    NANOMATERIALS, 2017, 7 (05):
  • [28] Thermodynamic Dynamic Characteristics of the Internally-cooled Membrane-based Liquid Desiccant Air Dehumidification System
    Yang, Yu
    Yan, Jun-Wei
    Zhou, Xuan
    Xiao, Lie-Hui
    Huang, Si-Min
    Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics, 2021, 42 (08): : 1944 - 1949
  • [29] Experimental study on dehumidification/regeneration of liquid desiccant: LiBr solution
    Bouzenada, S.
    Kaabi, A. N.
    Fraikin, L.
    Leonard, A.
    5TH INTERNATIONAL CONFERENCE ON AMBIENT SYSTEMS, NETWORKS AND TECHNOLOGIES (ANT-2014), THE 4TH INTERNATIONAL CONFERENCE ON SUSTAINABLE ENERGY INFORMATION TECHNOLOGY (SEIT-2014), 2014, 32 : 673 - 680
  • [30] Experimental Investigation on Dehumidification Using a Solid Composite Bio Desiccant Internally Cooled Using Nanofluids for Building Cooling
    Kumar, Shiva
    Hariharan, Girish
    Fayaz, Muhammad
    Kumar, Nitesh
    BUILDINGS, 2023, 13 (06)