Energy performance optimization of radiant slab cooling using building simulation and field measurements

被引:77
|
作者
Tian, Zhen [1 ]
Love, James A. [1 ]
机构
[1] Univ Calgary, Fac Environm Design, Calgary, AB T2N 1N4, Canada
关键词
Building energy performance; Radiant cooling; Simulation; EnergyPlus; Measurement and verification; THERMAL COMFORT;
D O I
10.1016/j.enbuild.2008.10.002
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Few field studies of energy performance of radiant cooling systems have been undertaken. A recently constructed 17,500 m 2 building with a multi-floor radiant slab cooling system in the tower was investigated through simulation calibrated with measured building energy use and meteorological data. For the very cold, dry region where the building was located, it was found that a typical floor of the tower would have had 30% lower annual energy use with a conventional variable air volume system than with the as-built radiant cooling-variable air volume combination. This was due to (1) simultaneous heating and cooling by the existing radiant cooling and air systems, (2) the large amount of free cooling possible in this climate, and (3) suboptimal control settings. If these issues were remedied and combined with improved envelope and a dedicated outdoor air system with exhaust air heat recovery, a typical floor could achieve annual energy use 80% lower than a typical floor of the existing building HVAC system. This shows that radiant thermal control can make a significant contribution to energy-efficiency, but only if the building design and operating practices complement the strengths of the radiant system. (C) 2008 Elsevier B.V. All rights reserved.
引用
收藏
页码:320 / 330
页数:11
相关论文
共 50 条
  • [21] Cooling capacity and acoustic performance of radiant slab systems with free-hanging acoustical clouds
    Karmann, Caroline
    Bauman, Fred S.
    Raftery, Paul
    Schiavon, Stefano
    Frantz, William H.
    Roy, Kenneth P.
    [J]. ENERGY AND BUILDINGS, 2017, 138 : 676 - 686
  • [22] Field evaluation of performance of radiant heating/cooling ceiling panel system
    Li, Rongling
    Yoshidomi, Togo
    Ooka, Ryozo
    Olesen, Bjarne W.
    [J]. ENERGY AND BUILDINGS, 2015, 86 : 58 - 65
  • [23] Modeling radiant heating and cooling systems: integration with a whole-building simulation program
    Strand, RK
    Baumgartner, KT
    [J]. ENERGY AND BUILDINGS, 2005, 37 (04) : 389 - 397
  • [24] Calibration of EnergyPlus Building Simulation Model Using Existing Field Measurements
    Ansari, A.A.
    Patil, K.A.
    [J]. Journal of Architectural Engineering, 2021, 27 (04):
  • [25] Calibration of EnergyPlus Building Simulation Model Using Existing Field Measurements
    Ansari, A. A.
    Patil, K. A.
    [J]. JOURNAL OF ARCHITECTURAL ENGINEERING, 2021, 27 (04)
  • [26] The numerical simulation of radiant floor cooling and heating system with double phase change energy storage and the thermal performance
    Xu, Ying
    Sun, Bin Bo
    Liu, Li Jun
    Liu, Xiao Yan
    [J]. JOURNAL OF ENERGY STORAGE, 2021, 40
  • [27] Using annual building energy analysis for the sizing of cooling tower for optimal chiller-cooling energy performance
    Liu, Chia-Wei
    Chuah, Yew-Khoy
    [J]. PROCEEDINGS OF THE 5TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS I AND II, 2007, : 43 - 49
  • [28] Performance of radiant cooling surfaces with respect to energy consumption and thermal comfort
    Oxizidis, Simos
    Papadopoulos, Agis M.
    [J]. ENERGY AND BUILDINGS, 2013, 57 : 199 - 209
  • [29] Optimization of a building energy performance by a multi-objective optimization, using sustainable energy combinations
    Li, Xiaoyan
    Rodriguez, Dragan
    [J]. EVOLVING SYSTEMS, 2021, 12 (04) : 949 - 963
  • [30] Simulation-Based Optimization of Data Center Cooling Performance Using Performance Indicators
    Petrongolo, John
    Nemati, Kourosh
    Fouladi, Kamran
    [J]. 2019 35TH SEMICONDUCTOR THERMAL MEASUREMENT, MODELING AND MANAGEMENT SYMPOSIUM (SEMI-THERM), 2019, : 91 - 95