摘要
A novel transient rotor current control scheme is proposed in this paper for a doubly-fed induction generator (DFIG) equipped with a superconducting magnetic energy storage (SMES) device to enhance its transient voltage and frequency support capacity during grid faults. The SMES connected to the DC-link capacitor of the DFIG is controlled to regulate the transient dc-link voltage so that the whole capacity of the grid side converter (GSC) is dedicated to injecting reactive power to the grid for the transient voltage support. However, the rotor-side converter (RSC) has different control tasks for different periods of the grid fault. Firstly, for Period I, the RSC injects the demagnetizing current to ensure the controllability of the rotor voltage. Then, since the dc stator flux degenerates rapidly in Period II, the required demagnetizing current is low in Period II and the RSC uses the spare capacity to additionally generate the reactive (priority) and active current so that the transient voltage capability is corroborated and the DFIG also positively responds to the system frequency dynamic at the earliest time. Finally, a small amount of demagnetizing current is provided after the fault clearance. Most of the RSC capacity is used to inject the active current to further support the frequency recovery of the system. Simulations are carried out on a simple power system with a wind farm. Comparisons with other commonly used control methods are performed to validate the proposed control method.
引用
收藏
页数:12
相关论文
共 50 条
  • [1] A novel transient rotor current control scheme of a doubly-fed induction generator equipped with superconducting magnetic energy storage for voltage and frequency support
    沈阳武
    柯德平
    孙元章
    Daniel Kirschen
    王轶申
    胡元朝
    Chinese Physics B, 2015, (07) : 54 - 65
  • [2] Advanced Auxiliary Control of an Energy Storage Device for Transient Voltage Support of a Doubly Fed Induction Generator
    Shen, Yang-Wu
    Ke, De-Ping
    Sun, Yuan-Zhang
    Kirschen, Daniel S.
    Qiao, Wei
    Deng, Xiang-Tian
    IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2016, 7 (01) : 63 - 76
  • [3] A POWER CONTROL SCHEME FOR DOUBLY-FED INDUCTION GENERATOR
    Sguarezi Filho, Alfeu J.
    Oliveira Filho, M. E.
    Ruppert, Ernesto
    2009 BRAZILIAN POWER ELECTRONICS CONFERENCE, VOLS 1 AND 2, 2009, : 1 - 8
  • [4] Primary frequency control of doubly fed induction generator-superconducting magnetic energy storage complementary system
    Liu, Wei
    Gu, Wei
    Sun, Rong
    Li, Qun
    Wang, Rui
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2012, 27 (09): : 108 - 116
  • [5] Frequency Control Support of a Doubly-Fed Induction Generator Based on the Torque Limit
    Kang, Moses
    Kim, Keonhui
    Muljadi, Eduard
    Park, Jung-Wook
    Kang, Yong Cheol
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2016, 31 (06) : 4575 - 4583
  • [6] Doubly-Fed Induction Generator Control Under Voltage Sags
    Lima, K.
    Luna, A.
    Rodriguez, P.
    Watanabe, E.
    Teodorescu, R.
    Blaabjerg, F.
    2008 IEEE ENERGY 2030 CONFERENCE, 2008, : 511 - +
  • [7] Power quality and stability improvement alongside decoupled control of frequency and voltage in doubly-fed induction generator by battery energy storage
    Neda Azizi
    Hassan Moradi CheshmehBeigi
    Electrical Engineering, 2022, 104 : 4091 - 4101
  • [8] Power quality and stability improvement alongside decoupled control of frequency and voltage in doubly-fed induction generator by battery energy storage
    Azizi, Neda
    CheshmehBeigi, Hassan Moradi
    ELECTRICAL ENGINEERING, 2022, 104 (06) : 4091 - 4101
  • [9] Inertia and Droop Frequency Control Strategy of Doubly-Fed Induction Generator Based on Rotor Kinetic Energy and Supercapacitor
    Yan, Xiangwu
    Sun, Xuewei
    ENERGIES, 2020, 13 (14)
  • [10] Decoupling Control Strategy for Doubly-fed Induction Generator the Rotor Cross-Coupling Voltage
    Zhou Yuanshen
    PROCEEDINGS OF THE 27TH CHINESE CONTROL CONFERENCE, VOL 5, 2008, : 174 - 179