Molecular epidemiology of Legionella pneumophila serogroup 1 isolates following long-term chlorine dioxide treatment in a university hospital water system

被引:26
|
作者
Casini, B. [1 ,2 ]
Valentini, P. [2 ]
Baggiani, A. [2 ]
Torracca, F. [2 ]
Frateschi, S. [1 ]
Nelli, L. Ceccherini [1 ]
Privitera, G. [2 ]
机构
[1] Univ Pisa, Dept Expt Pathol, I-56127 Pisa, Italy
[2] Univ Pisana, Azienda Osped, Unit Hosp Hyg & Epidemiol, Pisa, Italy
关键词
Legionella pneumophila serogroup 1; molecular typing; chlorine susceptibility;
D O I
10.1016/j.jhin.2008.03.003
中图分类号
R1 [预防医学、卫生学];
学科分类号
1004 ; 120402 ;
摘要
This paper describes the results of a five-year monitoring programme applied to the water distribution system of the University Hospital of Pisa (Italy). The purpose of the programme was to evaluate the efficacy of an integrated water safety plan in controlling Legionella spp. colonisation of the potable water system. The impact of the safety plan on the ecology of legionella in the water network was evaluated by studying the genetic variability and the chlorine susceptibility of the strains isolated prior to, and throughout, the application of continuous chlorine dioxide treatment. After 45 months of water hyperchlorination, Legionella spp. were still present but the positive supply points were reduced by 79.4%. The samples exceeding 10(3) cfu/L were reduced by 83.8% and the mean counts showed a decrease of 94.6%. The majority of the isotates belonged to Legionella pneumophila serogroup 1 (overall positivity rate: 161/423; 38%). Molecular typing was performed on 61 isotates (37.9% of the positive samples) selected on spatial and temporal criteria. This revealed the circulation and the persistence in the hospital environment of three prevalent types of L. pneumophila Wadsworth, demonstrating allelic and electrophoretic characteristic profiles and different chlorine susceptibility. Two of these, one predominant and pre-dating the sanitation regimen, and one other isolated after three years of water treatment, were chlorine tolerant. Despite the ineffectiveness of chlorine dioxide in eradicating L. pneumophila, the risk management plan adopted appeared to discourage further cases of nosocomial legionellosis. (C) 2008 The Hospital Infection Society. Published by Elsevier Ltd. All rights reserved.
引用
收藏
页码:141 / 147
页数:7
相关论文
共 10 条
  • [1] CONTROL OF LEGIONELLA-PNEUMOPHILA IN A HOSPITAL WATER-SYSTEM BY CHLORINE DIOXIDE
    WALKER, JT
    MACKERNESS, CW
    MALLON, D
    MAKIN, T
    WILLIETS, T
    KEEVIL, CW
    [J]. JOURNAL OF INDUSTRIAL MICROBIOLOGY, 1995, 15 (04): : 384 - 390
  • [2] DISTRIBUTION OF LEGIONELLAE IN A HOSPITAL WATER-SYSTEM - PREVALENCE OF IMMUNOLOGICALLY AND GENETICALLY RELATED LEGIONELLA-PNEUMOPHILA SEROGROUP-6 ISOLATES
    OTT, M
    BENDER, L
    LUCK, PC
    MEYER, P
    HACKER, J
    [J]. FEMS MICROBIOLOGY LETTERS, 1992, 95 (2-3) : 201 - 206
  • [3] Molecular epidemiology of Legionella pneumophila serogroup 1 isolates identify a prevalent sequence type, ST505, and a distinct clonal group of clinical isolates in Toyama Prefecture, Japan
    Kanatani, Jun-ichi
    Isobe, Junko
    Kimata, Keiko
    Shima, Tomoko
    Shimizu, Miwako
    Kura, Fumiaki
    Sata, Tetsutaro
    Watahiki, Masanori
    [J]. JOURNAL OF INFECTION AND CHEMOTHERAPY, 2013, 19 (04) : 644 - 652
  • [4] A 17-month evaluation of a chlorine dioxide water treatment system to control Legionella species in a hospital water supply
    Srinivasan, A
    Bova, G
    Ross, T
    Mackie, K
    Paquette, N
    Merz, W
    Perl, TM
    [J]. INFECTION CONTROL AND HOSPITAL EPIDEMIOLOGY, 2003, 24 (08): : 575 - 579
  • [5] Long-Term Effects of Hospital Water Network Disinfection on Legionella and Other Waterborne Bacteria in an Italian University Hospital
    Casini, Beatrice
    Buzzigoli, Andrea
    Cristina, Maria Luisa
    Spagnolo, Anna Maria
    Del Giudice, Pietro
    Brusaferro, Silvio
    Poscia, Andrea
    Moscato, Umberto
    Valentini, Paola
    Baggiani, Angelo
    Privitera, Gaetano
    [J]. INFECTION CONTROL AND HOSPITAL EPIDEMIOLOGY, 2014, 35 (03): : 293 - 299
  • [6] The presence of a specific genotype of Legionella pneumophila serogroup 1 in a hospital and municipal water distribution system over a 12-year period
    Darelid, J
    Bernander, S
    Jacobson, K
    Löfgren, S
    [J]. SCANDINAVIAN JOURNAL OF INFECTIOUS DISEASES, 2004, 36 (6-7) : 417 - 423
  • [7] LONG-TERM SURVIVAL OF LEGIONELLA-PNEUMOPHILA SEROGROUP-1 UNDER LOW-NUTRIENT CONDITIONS AND ASSOCIATED MORPHOLOGICAL-CHANGES
    PASZKOKOLVA, C
    SHAHAMAT, M
    COLWELL, RR
    [J]. FEMS MICROBIOLOGY ECOLOGY, 1992, 102 (01) : 45 - 55
  • [8] Evaluation of the ability of chlorine to inactivate selected organisms from the biofilm of a drinking water distribution system simulator following a long-term wastewater cross-connection
    Gibbs, SG
    Meckes, MC
    Green, CF
    Scarpino, PV
    [J]. JOURNAL OF ENVIRONMENTAL ENGINEERING AND SCIENCE, 2004, 3 (02) : 97 - 105
  • [9] Behavior of major and trace elements in a transient surface water/groundwater system following removal of a long-term wastewater treatment facility source
    Keefe, S. H.
    Barber, L. B.
    Hubbard, L. E.
    Bradley, P. M.
    Roth, D. A.
    Kolpin, D. W.
    [J]. SCIENCE OF THE TOTAL ENVIRONMENT, 2019, 668 : 867 - 880
  • [10] MORPHOLOGICAL AND BIOCHEMICAL-CHANGES IN THE ADULT MALE-RAT REPRODUCTIVE-SYSTEM FOLLOWING LONG-TERM TREATMENT WITH 1,2-DIBROMO-3-CHLOROPROPANE
    AHMAD, N
    WISNER, JR
    WARREN, DW
    [J]. ANATOMICAL RECORD, 1988, 222 (04): : 340 - 349