Flow distribution in the air cooler of HTGR passive cavity cooling system

被引:4
|
作者
Qin, Haiqi [1 ]
Li, Xiaowei [1 ]
Zhang, Li [1 ]
Wu, Xinxin [1 ]
机构
[1] Tsinghua Univ, Inst Nucl & New Energy Technol, Collaborat Innovat Ctr Adv Nucl Energy Technol, Key Lab Adv Reactor Engn & Safety,Minist Educ, Beijing 100084, Peoples R China
基金
中国国家自然科学基金;
关键词
High temperature gas-cooled reactor; Passive cavity cooling system; Air cooler; Flow distribution; PARALLEL-CHANNEL CONFIGURATIONS; DIVIDING MANIFOLD SYSTEMS; PRESSURE-DROP; HEAT-EXCHANGERS; CFD SIMULATION; DESIGN; UNIFORMITY; PERFORMANCE;
D O I
10.1016/j.anucene.2022.109478
中图分类号
TL [原子能技术]; O571 [原子核物理学];
学科分类号
0827 ; 082701 ;
摘要
Passive Cavity Cooling System (PCCS) is an important safety related system for High Temperature Gas-cooled Reactor (HTGR). Air cooler is one of the key components of this system. The non-uniform flow distribution is a common issue encountered in similar Parallel Tube Heat Exchanger (PTHX). Improving flow uniformity is favorable for both thermal hydraulic performance and structure safety. In this work, the flow distribution characteristics of a compact parallel tube air cooler with U-type header arrangement are theoretically and numerically investigated. First, a theoretical discrete model is proposed for flow distribution in PTHX. It reveals that the static pressure distributions in the headers are influenced by static pressure recovery, friction resistance and local pressure drop, which is directly related with flow uniformity. Then, the flow uniformity of Z-type and U-type header arrangements is numerically investigated and compared in detail. Moreover, the effects of thermal hydraulic parameter and geometrical parameter on flow uniformity are successively evaluated. Numerical results show that the flow uniformity of PCCS air cooler with U-type header arrangement is more excellent than that of Z-type header arrangement. Thermal hydraulic parameters, such as tube-side water temperature and mass flow rate, have little impact on flow uniformity. Nevertheless, the flow distribution characteristics are very sensitive to the geometrical parameters, including the insertion angle configuration, the flow area ratio of header to parallel heat transfer tubes (AR) and the cross-sectional area ratio of distribution header to collection header (DCR). Reasonable insertion angle configuration and decreasing AR can effectively enhance the flow uniformity of PCCS air cooler. For header match, it should be avoided that the distribution header diameter below the collection header diameter. As a result, the optimal structure design determined in this work is an air cooler with U-type header arrangement, where the inlet insertion angle is 0 degrees, the outlet insertion angle is 180 degrees, and the diameters of distribution header and collection header are both 120 mm. Its flow uniformity is improved by more than 50% compared with present design. This work reports a promising design modification, as the potential structure optimization for HTGR PCCS air cooler.
引用
收藏
页数:17
相关论文
共 50 条
  • [1] ANALYSIS OF PASSIVE REACTOR CAVITY COOLING SYSTEM FOR A 600 MWTH HTGR USING MELCOR CODE
    Kim, Jin-Hyuck
    Huh, Changwook
    Jin, Chang-Yong
    Jeon, Seong-Su
    22ND INTERNATIONAL CONFERENCE NUCLEAR ENERGY FOR NEW EUROPE, (NENE 2013), 2013,
  • [2] Optimization of cooling water system with precooling air cooler
    Zhang J.
    Ren X.
    Wang Y.
    Chemical Engineering Transactions, 2018, 65 : 337 - 342
  • [3] Effects of sub-cooler on cooling performance of variable refrigerant flow air conditioning system
    Tu, Qiu
    Zhang, Lina
    Cai, Wei
    Guo, Xiujuan
    Deng, Chenmian
    Zhang, Jie
    Wang, Bingjun
    APPLIED THERMAL ENGINEERING, 2017, 127 : 1152 - 1163
  • [4] Sensitivity of SC-HTGR Conduction Cooldown to Reactor Cavity Cooling System Failure
    Mays, Brian
    Lommers, Lewis
    Yoder, Stacy
    Shahrokhi, Farshid
    NUCLEAR TECHNOLOGY, 2022, 208 (08) : 1311 - 1323
  • [5] Experimental analysis on mixed convection in reactor cavity cooling system of HTGR for hydrogen production
    Shin, Dong-Ho
    Kim, Chan Soo
    Park, Goon-Cherl
    Cho, Hyoung Kyu
    INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2017, 42 (34) : 22046 - 22053
  • [6] Air Flow Distribution Measurement of the Vehicle Cooling System Test Rig
    Lee, J. H.
    Latiff, Z. A.
    Perang, M. R. M.
    Said, M. F. M.
    PROCEEDINGS OF THE 3RD INTERNATIONAL CONFERENCE ON AUTOMOTIVE INNOVATION GREEN ENERGY VEHICLE (AIGEV 2018), 2019, 2059
  • [7] Simulation of a Predominantly Passive Natural Air Cooling System
    Venter, P. V. Z.
    van Eldik, M.
    2018 INTERNATIONAL CONFERENCE ON THE DOMESTIC USE OF ENERGY (DUE), 2018, : 150 - 155
  • [8] ROTATING CAVITY WITH AXIAL THROUGHFLOW OF COOLING AIR - FLOW STRUCTURE
    FARTHING, PR
    LONG, CA
    OWEN, JM
    PINCOMBE, JR
    JOURNAL OF TURBOMACHINERY-TRANSACTIONS OF THE ASME, 1992, 114 (01): : 237 - 246
  • [9] COOLING OF CEMENT IN THE AIR SEPARATOR OR IN THE CEMENT COOLER
    ZISSELMAR, R
    ZEMENT-KALK-GIPS, 1980, 33 (05): : 244 - 249
  • [10] Spatial distribution of air temperature and air flow analysis in radiant cooling system using CFD technique
    Khatri, Rahul
    Khare, Vaibhav Rai
    Kumar, Hemant
    ENERGY REPORTS, 2020, 6 : 268 - 275