Analysis and optimization of injection characteristics and comprehensive performance of low GWP refrigerant HP-1 in high temperature heat pump systems

被引:3
|
作者
Wang, Yuehan [1 ]
Nan, Xiaohong [1 ]
Ouyang, Hongsheng [2 ]
Guo, Zhikai [2 ]
Hu, Bin [3 ]
Wang, R. Z.
机构
[1] Xian Univ Architecture & Technol, Sch Bldg Serv Sci & Engn, Xian 710055, Peoples R China
[2] Zhejiang Res Inst Chem Ind Co Ltd, State Key Lab Fluorinated Greenhouse Gases Replace, Hangzhou 310023, Peoples R China
[3] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Shanghai 200240, Peoples R China
关键词
HP-1; HTHP; Environmentally friendly refrigerant; Injection Characteristics; Performance analysis optimization; Decarbonization; VAPOR-INJECTION; SCROLL COMPRESSOR; 2-PHASE INJECTION; LIQUID INJECTION; R32; HCFO-1224YD(Z); INTERMEDIATE; ALTERNATIVES; R1233ZD(E); HFC-245FA;
D O I
10.1016/j.enbuild.2023.113799
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In the context of low-GWP refrigerants becoming a research hotspot, the environmentally friendly refrigerant HP1 with independent intellectual property rights in China has demonstrated significant advantages in fields such as data centers and 5G base stations. However, there are few applied studies in the field of high-temperature heat pumps (HTHPs), therefore, in this study, HP-1 was utilized in HTHP system and this process was combined with the injection technology. It has been proven to be an effective approach for performance improvement. The injection characteristics of HP-1-based HTHP were analyzed and optimized with a focus on safety, stability, and efficient operation. The application advantages of HP-1 were compared and analyzed in terms of thermodynamic performance and Total Equivalent Warming Impact. The results indicated that there were three types of characteristic injection pressures based on system performance, corresponding to the maximum coefficient of performance (COP), the lowest electronic expansion valve inlet refrigerant temperature, and the lowest exhaust temperature of the compressor. Further, the corresponding control equations for injection pressure were obtained. Based on the safety injection pressure, the optimal COP under injection pressure could effectively improve the COP of the system by 2.1-5.2 %, and the exhaust temperature also increased by 6.1-10.1 %. When the temperature of the heat source was 50 degrees C and the target heating temperature was 120 degrees C, the heating capacity of HP-1 increased by 10.8 % compared with that of R245fa, the COP of the system increased by 2.7 %, and the volume heating capacity increased by 10.3 %. Moreover, the emission reduction effect of HP-1 was significant, and the carbon dioxide emissions were reduced by 15.4-39.1 %. The analysis shows that HP-1 exhibits better performance and environmental characteristics than HFC-245fa. This study is of guiding significance to improve the thermodynamic performance of HTHP, for the safe and efficient operation and energy saving and emission reduction in the industrial field.
引用
收藏
页数:18
相关论文
共 50 条
  • [41] Effects of injection styles on heating performance of a heat pump with sub-cooler refrigerant injection: Experimental and thermodynamic analysis
    Zhang, Lina
    Tu, Qiu
    Yuan, Xiaoyuan
    Wu, Xiaogang
    INDOOR AND BUILT ENVIRONMENT, 2023, 32 (05) : 864 - 880
  • [42] Performance analysis of a novel dual exhaust mixed refrigerant heat pump with large temperature lift
    Tang, Qixiong
    Wang, Huirong
    Guo, Hao
    THERMAL SCIENCE AND ENGINEERING PROGRESS, 2024, 56
  • [43] Thermodynamic analysis of high temperature cascade heat pump with R718 (high stage) and six different low-GWP refrigerants (low stage)
    Hosseinnia, Seyed Mojtaba
    Amiri, Leyla
    Nesreddine, Hakim
    Monney, Dominique
    Poncet, Sebastien
    CASE STUDIES IN THERMAL ENGINEERING, 2024, 53
  • [44] Theoretical evaluation of energy, exergy, and minimum superheat in a high-temperature heat pump with low GWP refrigerants
    Sulaiman, Adam Y.
    Cotter, Donal
    Arpagaus, Cordin
    Hewitt, Neil
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2023, 153 : 99 - 109
  • [45] Performance Comparison of High-Temperature Heat Pumps with Different Vapor Refrigerant Injection Techniques
    Yang, Yuqiang
    Wang, Yu
    Xu, Zhaoyang
    Xie, Baojiang
    Hu, Yong
    Yu, Jiatao
    Chen, Yehong
    Zhang, Ting
    Lu, Zhenneng
    Gong, Yulie
    PROCESSES, 2024, 12 (03)
  • [46] Thermodynamic analysis of a dual-pressure evaporation high-temperature heat pump with low GWP zeotropic mixtures for steam generation
    Feng, Chunyu
    Guo, Cong
    Chen, Junbin
    Tan, Sicong
    Jiang, Yuyan
    ENERGY, 2024, 294
  • [47] Condensation heat transfer characteristics and energy conversion performance analysis for low GWP refrigerants in plate heat exchangers
    Jung, Jae Hoon
    Ko, Yun Mo
    Kang, Yong Tae
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2021, 166
  • [48] A NON-FLAMMABLE LOW GWP REFRIGERANT FOR CENTRIFUGAL CHILLERS AND HIGH TEMPERATURE HEAT PUMPS: R-1336mzz(Z)
    Juhasz, Jason
    Kontomaris, Konstantinos
    1ST IIR INTERNATIONAL CONFERENCE ON THE APPLICATION OF HFO REFRIGERANTS, 2018, : 231 - 237
  • [49] Performance of Automotive Ultra-Low Temperature Economized Vapor Injection Heat Pump Air Conditioning Using R1234yf Refrigerant
    Liu Y.
    Li W.
    Zhang L.
    Shi J.
    Chen J.
    Chen, Jiangping (jpchen_sjtu@163.com), 2020, Shanghai Jiaotong University (54): : 1108 - 1116
  • [50] Comprehensive performance evaluation method of working fluids for high temperature heat pump based on multi-objective optimization
    Xu, Chang
    Ma, Hongting
    Yu, Xiaohui
    APPLIED THERMAL ENGINEERING, 2024, 247