A dual-mode system for water purification and cooling using a thermal desalination technique coupled to a heat pump unit

被引:4
|
作者
Anand, B. [1 ]
Shankar, R. [2 ]
Jimenez-Garcia, J. C. [1 ]
Rivera, W. [1 ]
机构
[1] Univ Nacl Autonoma Mexico, Inst Energias Renovables, Temixco, Morelos, Mexico
[2] MVJ Coll Engn, Dept Aeronaut Engn, Bangalore, India
关键词
Desalination; Cooling; Humidification; -dehumidification; Heat pump; Waste heat recovery; THERMOPHYSICAL PROPERTIES; PERFORMANCE ANALYSIS; EXERGY ANALYSIS; DEHUMIDIFICATION; DRIVEN; ENERGY; OPTIMIZATION; SEAWATER;
D O I
10.1016/j.applthermaleng.2023.120096
中图分类号
O414.1 [热力学];
学科分类号
摘要
Humidification-dehumidification is one of the most suitable small-scale desalination methods based on air humidification and condensation. The major energy-consuming components for a humidification-dehumidification process are a heat source for the humidifier and a cooling source for the dehumidifier. To improve the performance of these processes, the fluids were preheated using different energy sources or waste heat. In recent years, preheating air or saline water using heat from a heat pump's condenser has been explored to improve the system's performance and to produce cooling and desalination simultaneously. However, separate heat exchangers and additional solar collectors/heaters were used to preheat the second fluid. In this work, the air-cooled condenser of a heat pump has been replaced by an evaporative condenser and used as a humidifier. This configuration has been scarcely explored in the literature and requires a single heat exchanger to preheat the fluids. On the other hand, the heat pump's evaporator was used to produce low-temperature coolant, circulated through a cooling coil where the humid air from the evaporative condenser is cooled and dehumidified to produce fresh water and cooling simultaneously. This modification ensures reduced space requirement and better system performance than other heat pumps coupled to humidification-dehumidification systems for simultaneous cooling and desalination. Also, the present system operates flexibly to switch between desalination and cooling mode (mode-1) to cooling mode (mode-2). Towards this, a mathematical model of the system has been developed and analyzed under various operating conditions. The system's performance, which includes desalination yield, cooling output, gained output ratio, and coefficient of performance under each mode of operation, is studied for different ambient conditions and evaporator temperatures. The maximum desalination yield, cooling output, gained output ratio, and coefficient of performance of mode-1 are 4.55 LPH, 0.82 kWth, 3.79, and 0.75, respectively. The maximum cooling output and COP of mode-2 are 3.79 kWth and 3.82, respectively. The exergy efficiencies for mode-1 and mode-2 are 32.7 % and 29.7 %, respectively.
引用
收藏
页数:13
相关论文
共 50 条
  • [31] Optimization and analysis of a multi-functional heat pump system with air source and gray water source in cooling mode
    Liu, Xiaoyu
    Lau, Siu-Kit
    Li, Haorong
    Shen, Hui
    ENERGY AND BUILDINGS, 2017, 149 : 339 - 353
  • [32] Heat and Mass Transfer Analysis of a Water and Solute Separation System-Using Solar Thermal Energy for Water Desalination
    Li, Peiwen
    Peri, Aditya
    Ma, Hongzhang
    Chen, Yingwen
    PROCEEDINGS OF ASME 9TH INTERNATIONAL CONFERENCE ON ENERGY SUSTAINABILITY, 2015, VOL 2, 2016,
  • [33] Assessment of thermoeconomic and thermoenvironmental impacts of a novel solar desalination system using a heat pump, evacuated tubes, cover cooling, and ultrasonic mist
    Sharshir, Swellam W.
    Kandeal, A. W.
    Joseph, Abanob
    Elsayad, Mamoun M.
    Abdullah, A. S.
    Jang, Sung-Hwan
    Elashmawy, Mohamed
    Abdelaziz, Gamal B.
    Ghazaly, Nouby M.
    Yuan, Zhanhui
    APPLIED THERMAL ENGINEERING, 2024, 254
  • [34] Performance Analysis and Optimization of Solar-Coupled Mine Water-Source Heat Pump Combined Heating and Cooling System
    Zhao, Chang
    Zhao, Jianhui
    Wang, Mei
    SUSTAINABILITY, 2024, 16 (11)
  • [35] Feasibility Study of a Heating, Cooling and Domestic Hot Water System Combining a Photovoltaic-Thermal System and a Ground Source Heat Pump
    Jeong, Yong-Dae
    Yu, Min Gyung
    Nam, Yujin
    ENERGIES, 2017, 10 (08):
  • [36] Electrification of residential heating, cooling and hot water: Load smoothing using onsite photovoltaics, heat pump and thermal batteries
    Li, Yuanyuan
    Rosengarten, Gary
    Stanley, Cameron
    Mojiri, Ahmad
    JOURNAL OF ENERGY STORAGE, 2022, 56
  • [37] New proposed system for freeze water desalination using auto reversed R-22 vapor compression heat pump
    Attia, Ahmed A. A.
    DESALINATION, 2010, 254 (1-3) : 179 - 184
  • [38] Techno-economic control strategy optimization for water-source heat pump coupled with ice storage district cooling system
    Chen, Qiong
    Wei, Wenhan
    Li, Nan
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2022, 138 : 148 - 158
  • [39] Thermodynamic investigation and optimization of a heat pump coupled open-air, open-water humidification dehumidification desalination system with a direct contact dehumidifier
    He, Weifeng
    Yang, Hongxing
    Han, Dong
    DESALINATION, 2019, 469
  • [40] Performance analysis of an open absorption heat pump and thermal desalination system for heat and water recovery of coal-fired flue gas based on zero liquid discharge
    Xue, Yuan
    Zhao, Bohan
    Wang, Sijiao
    Yin, Peili
    Wang, Hongxi
    ENERGY CONVERSION AND MANAGEMENT, 2022, 273