Data center energy conservation study utilizing loop heat pipes as a chip-level cooling technique and its industrial application

被引:24
|
作者
Xue, Zhi Hu [1 ]
Ai, Bang Cheng [1 ]
Qu, Wei [1 ]
机构
[1] China Acad Aerosp Aerodynam, Beijing 100074, Peoples R China
关键词
Electronics cooling; Data center; Energy saving; Loop heat pipe; Chip-level cooling; Thermal management; AIR-SIDE ECONOMIZERS; FLAT EVAPORATOR; SYSTEMS; DESIGN; PERFORMANCE; FLOW;
D O I
10.1016/j.applthermaleng.2022.119715
中图分类号
O414.1 [热力学];
学科分类号
摘要
The thermal management and energy consumption for data centers became an increasing challenge due to a significant increase in their number, size and power density in modern information and digitization age. The electricity using by cooling system contributed the important fraction of energy consumption in datacenters, and it is of great significance to carry out the research of new cooling technologies to improve the cooling efficiency of datacenters. This paper initiatively presents the basic energy conservation principle of chip-level cooling technique based on the loop heat pipe (LHP) for natural cooling throughout a year. An energy-saving theoretical evaluation model based on the LHP chip-level cooling method is developed for assessing the energy utilizing efficiency and energy-saving levels in datacenters. Two kinds of real computer servers using two water-cooling LHPs with flat evaporator are introduced. The evaporator volume of a LHP is 54 x 44 x 12 mm3. The tests show that the servers work safely with the inlet water temperature of 40 degrees C and flow rate of 0.027 m3/h in the condenser of LHP. Lastly, the applications in two industrial data centers based on the LHP chip-level cooling technique are practiced. The annual cooling-PUE of a cloud-computing datacenter in Hohhot city is 1.053, and the annual PUE of a supercomputer-center in Beijing city is 1.15. Their operation data both show that the energy savings of the cooling system and the whole data center could be up to 81 % and 30 % respectively compared to the traditional CRAH cooling technique, which are in accordance with the predicted results of theoretical evaluation model.
引用
收藏
页数:13
相关论文
共 22 条
  • [1] Performance and energy consumption study of a dual-evaporator loop heat pipe for chip-level cooling
    Zhang, Yixue
    Wang, Guiyuan
    Wang, Xinyuan
    Wang, Jiacheng
    Xue, Hongyao
    Luan, Tao
    APPLIED THERMAL ENGINEERING, 2025, 258
  • [2] Server chip-level cooling technology in data center based on LHP
    Xue Z.
    Ai B.
    Qu W.
    Huazhong Keji Daxue Xuebao (Ziran Kexue Ban)/Journal of Huazhong University of Science and Technology (Natural Science Edition), 2024, 52 (07): : 126 - 131
  • [3] Progress of chip-level indirect liquid cooling technology and enhanced heat transfer in data centers
    Yin, Rui
    Yin, Shaowu
    Yang, Likun
    Tong, Lige
    Liu, Chuanping
    Wang, Li
    Huagong Jinzhan/Chemical Industry and Engineering Progress, 2024, 43 (11): : 6010 - 6030
  • [4] Experimental research and energy effectiveness analysis on chip-level two-stage loop thermosyphon system for data centre free cooling
    Chen, Xiaoxuan
    Ding, Tao
    Wang, Lu
    Li, Zhen
    APPLIED THERMAL ENGINEERING, 2024, 245
  • [5] Principles of loop thermosyphon and its application in data center cooling systems: A review
    Ding, Tao
    Chen, Xiaoxuan
    Cao, Hanwen
    He, Zhiguang
    Wang, Jianmin
    Li, Zhen
    RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2021, 150
  • [6] Experimental study on the performance of cascaded separate microchannel heat pipes for data center cooling
    Zhang, Ying
    Pan, Chunlin
    Wang, Nan
    Tu, Yuwei
    Tian, Yuan
    Xu, Meng
    APPLIED THERMAL ENGINEERING, 2025, 262
  • [7] Experimental study of pump-driven chip-level two-phase cooling system for data centres
    Wang, Leixin
    Cheng, Hao
    Yang, Tongzhi
    Yuan, Weixing
    Ren, Kexian
    INDOOR AND BUILT ENVIRONMENT, 2024, 33 (01) : 57 - 73
  • [8] From Chip to Cooling Tower Data Center Modeling: Chip Leakage Power and Its Impact on Cooling Infrastructure Energy Efficiency
    Breen, Thomas J.
    Walsh, Ed J.
    Punch, Jeff
    Shah, Amip J.
    Bash, Cullen E.
    Kumari, Niru
    Cader, Tahir
    JOURNAL OF ELECTRONIC PACKAGING, 2012, 134 (04)
  • [9] FROM CHIP TO COOLING TOWER DATA CENTER MODELING: CHIP LEAKAGE POWER AND ITS IMPACT ON COOLING INFRASTRUCTURE ENERGY EFFICIENCY
    Breen, Thomas J.
    Walsh, Ed J.
    Punch, Jeff
    Shah, Amip J.
    Bash, Cullen E.
    Kumari, Niru
    Cader, Tahir
    PROCEEDINGS OF THE ASME PACIFIC RIM TECHNICAL CONFERENCE AND EXHIBITION ON PACKAGING AND INTEGRATION OF ELECTRONIC AND PHOTONIC SYSTEMS, MEMS AND NEMS 2011, VOL 2, 2012, : 433 - +
  • [10] Study on heat transfer performance of loop heat pipe reactor and its industrial application
    Wang, Zhi-Liang
    Zhang, Hong
    Zhuang, Jun
    Xiandai Huagong/Modern Chemical Industry, 2007, 27 (07): : 45 - 49