Experimental study of pump-driven chip-level two-phase cooling system for data centres

被引:1
|
作者
Wang, Leixin [1 ]
Cheng, Hao [1 ]
Yang, Tongzhi [1 ]
Yuan, Weixing [1 ,3 ]
Ren, Kexian [1 ,2 ]
机构
[1] Beihang Univ, Sch Aeronaut Sci & Engn, Lab Ergon & Environm Control, Beijing, Peoples R China
[2] Tsinghua Univ, Sch Architecture, Dept Bldg Sci, Beijing, Peoples R China
[3] Beihang Univ, Sch Aeronaut Sci & Engn, Lab Ergon & Environm Control, 37 Xueyuan Rd, Beijing 100191, Peoples R China
关键词
Pump-driven; two-phase cooling; chip-level; energy saving; data centre; central processing units; internal refrigerant cycle; external water cycle; HEAT-PIPE SYSTEM; THERMAL MANAGEMENT; THERMOSIPHON LOOP; ENERGY; PERFORMANCE; AIR;
D O I
10.1177/1420326X231183300
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In this study, we proposed and designed a pump-driven chip-level two-phase cooling system (PCTCS) and experimentally demonstrated that it can directly cool central processing units in data centres (DCs). The operation of the PCTCS involves an internal refrigerant cycle (IRC) and an external water cycle (EWC). Within the IRC, multiple mini-channel evaporators enable the dissipation of heat from the CPUs in the servers through a plate heat exchanger to initiate the EWC, which is followed by the dissipation of the heat to the environment. We performed experiments to systematically analyze the effects of key operation parameters on PCTCS performance of the IRC. The results indicated that the average and the highest core temperature of the CPUs were 76.3 degrees C and 79.0 degrees C, respectively, under extremely harsh heat dissipation conditions. The key driving component of the PCTCS is a refrigerant pump with high energy efficiency ratio (EERp) defined as ratio of heat dissipated by the power of the refrigerant pump. The EERp was 17-18 when the CPUs were at 0% load and 38-42 and 68-76 when the CPUs were at 50% and 100% loads, respectively. Moreover, optimizing the flow resistance of the IRC can improve the performance of the PCTCS.
引用
收藏
页码:57 / 73
页数:17
相关论文
共 50 条
  • [1] Modeling and Performance Analysis of a Pump-Driven Chip-Level Two-Phase Cooling System in Data Centers
    Wang, Leixin
    Cheng, Hao
    Yang, Tongzhi
    Yuan, Weixing
    Ren, Kexian
    APPLIED SCIENCES-BASEL, 2023, 13 (13):
  • [2] Cooling performance of a pump-driven two phase cooling system for free cooling in data centers
    Ma, Yuezheng
    Ma, Guoyuan
    Zhang, Shuang
    Zhou, Feng
    APPLIED THERMAL ENGINEERING, 2016, 95 : 143 - 149
  • [3] Two-Phase Liquid Cooling System for Electronics, Part 1: Pump-Driven Loop
    Salamon, Todd
    Amalfi, Raffaele L.
    Lamaison, Nicolas
    Marcinichen, Jackson B.
    Thome, John R.
    PROCEEDINGS OF THE SIXTEENTH INTERSOCIETY CONFERENCE ON THERMAL AND THERMOMECHANICAL PHENOMENA IN ELECTRONIC SYSTEMS ITHERM 2017, 2017, : 667 - 677
  • [4] Experimental study on the boiling heat transfer characteristics of a pump-driven two-phase cooling loop system for high heat flux avionics
    Wang, Jiaxuan
    Yu, Binbin
    Qian, Chenyi
    Shi, Junye
    Chen, Jiangping
    THERMAL SCIENCE AND ENGINEERING PROGRESS, 2023, 45
  • [5] Experimental study on a pump-driven CO2 two-phase thermosyphon loop
    Tong, Zhen
    Song, Yulong
    Wang, Wencheng
    Han, Zekun
    APPLIED THERMAL ENGINEERING, 2024, 257
  • [6] NUMERICAL INVESTIGATION OF THE FLOW DISTRIBUTION CHARACTERISTICS OF THE EVAPORATIVE COOLING PLATE IN A PUMP-DRIVEN TWO-PHASE FLOW SYSTEM
    Zhou, Nianyong
    Lv, Wenyu
    Liu, Yang
    Tang, Guanghua
    Bao, Qingguo
    Zou, Youxin
    Zhao, Yingjie
    THERMAL SCIENCE, 2024, 28 (05): : 4115 - 4129
  • [7] Experimental study on a novel pump-driven heat pipe/vapor compression system for rack-level cooling of data centers
    Sun, Xiaoqing
    Zhang, Ce
    Han, Zongwei
    Dong, Jiaxiang
    Zhang, Yiqi
    Li, Mengyi
    Li, Xiuming
    Wang, Qinghai
    Wen, Zhenwu
    Zheng, Baoli
    ENERGY, 2023, 274
  • [8] Experimental investigation on a novel integrated system of vapor compression and pump-driven two phase loop for energy saving in data centers cooling
    Ma, Yuezheng
    Ma, Guoyuan
    Zhang, Shuang
    Xu, Shuxue
    ENERGY CONVERSION AND MANAGEMENT, 2015, 106 : 194 - 200
  • [9] Experimentally comparative study on two-phase natural and pump-driven loop used in HVAC systems
    Zhang, Penglei
    Li, Xianting
    Shi, Wenxing
    Wang, Baolong
    Rong, Xingyue
    APPLIED THERMAL ENGINEERING, 2018, 142 : 321 - 333
  • [10] Experimental research on dynamic characteristics and control strategy of the pump-driven two-phase loop with dual evaporators
    Zhang, Penglei
    Liu, Kehan
    Li, Yue
    Yang, Xiaorui
    Li, Xiaolin
    CASE STUDIES IN THERMAL ENGINEERING, 2022, 38