Experimental study of pump-driven chip-level two-phase cooling system for data centres

被引:1
|
作者
Wang, Leixin [1 ]
Cheng, Hao [1 ]
Yang, Tongzhi [1 ]
Yuan, Weixing [1 ,3 ]
Ren, Kexian [1 ,2 ]
机构
[1] Beihang Univ, Sch Aeronaut Sci & Engn, Lab Ergon & Environm Control, Beijing, Peoples R China
[2] Tsinghua Univ, Sch Architecture, Dept Bldg Sci, Beijing, Peoples R China
[3] Beihang Univ, Sch Aeronaut Sci & Engn, Lab Ergon & Environm Control, 37 Xueyuan Rd, Beijing 100191, Peoples R China
关键词
Pump-driven; two-phase cooling; chip-level; energy saving; data centre; central processing units; internal refrigerant cycle; external water cycle; HEAT-PIPE SYSTEM; THERMAL MANAGEMENT; THERMOSIPHON LOOP; ENERGY; PERFORMANCE; AIR;
D O I
10.1177/1420326X231183300
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In this study, we proposed and designed a pump-driven chip-level two-phase cooling system (PCTCS) and experimentally demonstrated that it can directly cool central processing units in data centres (DCs). The operation of the PCTCS involves an internal refrigerant cycle (IRC) and an external water cycle (EWC). Within the IRC, multiple mini-channel evaporators enable the dissipation of heat from the CPUs in the servers through a plate heat exchanger to initiate the EWC, which is followed by the dissipation of the heat to the environment. We performed experiments to systematically analyze the effects of key operation parameters on PCTCS performance of the IRC. The results indicated that the average and the highest core temperature of the CPUs were 76.3 degrees C and 79.0 degrees C, respectively, under extremely harsh heat dissipation conditions. The key driving component of the PCTCS is a refrigerant pump with high energy efficiency ratio (EERp) defined as ratio of heat dissipated by the power of the refrigerant pump. The EERp was 17-18 when the CPUs were at 0% load and 38-42 and 68-76 when the CPUs were at 50% and 100% loads, respectively. Moreover, optimizing the flow resistance of the IRC can improve the performance of the PCTCS.
引用
收藏
页码:57 / 73
页数:17
相关论文
共 50 条
  • [31] Flow distribution characteristics of gravity- and pump-driven CO2 two-phase thermosyphon loops with three evaporators
    Tong, Zhen
    Wang, Peng
    Han, Zekun
    Wang, Wencheng
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2025, 173 : 76 - 87
  • [32] Experimental Study of Two-Phase Cooling to Enable Large-Scale System Computing Performance
    Kulkarni, Devdatta
    Tang, Xudong
    Ahuja, Sandeep
    Dischler, Richard
    Mahajan, Ravi
    PROCEEDINGS OF THE 17TH IEEE INTERSOCIETY CONFERENCE ON THERMAL AND THERMOMECHANICAL PHENOMENA IN ELECTRONIC SYSTEMS (ITHERM 2018), 2018, : 596 - 601
  • [33] Two-phase liquid-immersion data center cooling system: Experimental performance and thermoeconomic analysis
    Kanbur, Baris Burak
    Wu, Chenlong
    Fan, Simiao
    Tong, Wei
    Duan, Fei
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 118 : 290 - 301
  • [34] Experimental Demonstration of Pressure-Driven Flash Boiling for Transient Two-Phase Cooling
    Shah, Ujash
    Ma, Matthew
    Barako, Michael T.
    Bar-Cohen, Avram
    Iyer, Subramanian S.
    Fisher, Timothy S.
    IEEE TRANSACTIONS ON COMPONENTS PACKAGING AND MANUFACTURING TECHNOLOGY, 2021, 11 (10): : 1604 - 1614
  • [35] Two-phase pumped cooling system for power electronics; analyses and experimental results
    van Gerner, Henk Jan
    Cao, Changmin
    Pedroso, Douglas A.
    te Nijenhuis, Arne K.
    Castro, Ignacio
    Dsouza, Herol
    2024 30TH INTERNATIONAL WORKSHOP ON THERMAL INVESTIGATIONS OF ICS AND SYSTEMS, THERMINIC 2024, 2024,
  • [36] Time Domain Theoretical Research on Flow Stability of a Pump Driven Two-Phase System
    Su, Yang
    Li, Xiao-Wei
    Wu, Xin-Xin
    Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics, 2022, 43 (02): : 459 - 464
  • [37] Experimental study of two-phase pump performance using a full size nuclear reactor pump
    Chan, AMC
    Kawaji, M
    Nakamura, H
    Kukita, Y
    NUCLEAR ENGINEERING AND DESIGN, 1999, 193 (1-2) : 159 - 172
  • [38] Experimental Study on a Pump Driven Loop-Heat Pipe for Data Center Cooling
    Zhang, Shuang
    Ma, Guoyuan
    Zhou, Feng
    JOURNAL OF ENERGY ENGINEERING, 2015, 141 (04)
  • [39] Experimental Study of a Centrifugal Pump Handling Viscous Fluid and Two-Phase Flow
    Paternost, G. M.
    Bannwart, A. C.
    Estevam, V.
    SPE PRODUCTION & OPERATIONS, 2015, 30 (02): : 146 - 155
  • [40] Experimental Study of Two-Phase Performance of an Electric-Submersible-Pump Stage
    Gamboa, Jose
    Prado, Mauricio
    SPE PRODUCTION & OPERATIONS, 2012, 27 (04): : 414 - 421