Application of stochastic filter to three-phase nonuniform transmission lines

被引:0
|
作者
Gautam, Amit Kumar [1 ,2 ]
Majumdar, Sudipta [1 ]
机构
[1] Delhi Technol Univ, Dept Elect & Commun Engn, Delhi, India
[2] Delhi Technol Univ, Dept Elect & Commun Engn, Delhi 110042, India
关键词
Extended Kalman filter; unscented Kalman filter; non-uniform transmission lines; state space modelling; Fourier series expansion; STATE ESTIMATION;
D O I
10.1080/00207217.2023.2235723
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper implements the stochastic filters for state and parameter estimation of nonuniform transmission lines (NTL). In general, transmission line (TL) problem is a continuous time and space problem. By taking the line loading noise into account, the TL equations become a stochastic partial differential equation (PDE) rather than a simple set of coupled finite stochastic differential equations (SDE). By transforming the spatial variables into the Fourier domain, the stochastic PDE can be transformed into an infinite sequence of SDE. After truncation to a finite set of Fourier series coefficients, it becomes a finite set of coupled linear SDE, which is the required domain in which extended Kalman filter (EKF) and unscented Kalman filter (UKF) can be applied. For state space equation of EKF and UKF, the voltage and current of periodic NTL are expanded into an infinite set of spatial harmonics. In this way, the voltage and current measurement of NTL become an eigenvalue problem. The NTL is considered as cascade of small infinite NTL and the four distributed primary parameters of the periodic NTL are expressed using Fourier series expansion. Finally, the Kalman filter (KF)-based state estimation and the EKF- and UKF-based parameter estimation have been compared with recursive least squares (RLS) method. The simulation results present the superiority of the method.
引用
收藏
页码:1495 / 1516
页数:22
相关论文
共 50 条
  • [21] Identification of three-phase permanent or temporary fault at transmission lines with shunt reactors
    Li, Yong-Li
    Li, Bo-Tong
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2010, 30 (01): : 82 - 90
  • [22] Transient analysis of three-phase transmission lines with initial voltage and current distributions
    Li, JC
    ELECTRIC POWER SYSTEMS RESEARCH, 1995, 35 (03) : 177 - 186
  • [23] Single real transformation matrices applied to double three-phase transmission lines
    Campos, J. C. C.
    Pissolato Filho, J.
    Prado, A. J.
    Kurokawa, S.
    ELECTRIC POWER SYSTEMS RESEARCH, 2008, 78 (10) : 1719 - 1725
  • [24] A frequency dependent mode domain model for double three-phase transmission lines
    Prado, AJ
    Pissolato, J
    Tavares, MC
    Portela, CM
    2000 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY, VOLS I-III, PROCEEDINGS, 2000, : 1059 - 1064
  • [25] Three-Phase Distance Matrices Filter
    Hsu, Wei-Chun
    Liu, Yuan-Chen
    Pan, Kuan-Yu
    PROCEEDINGS OF THE FIRST INTERNATIONAL WORKSHOP ON EDUCATION TECHNOLOGY AND COMPUTER SCIENCE, VOL III, 2009, : 41 - 44
  • [26] Fluctuations in the structure of three-phase lines
    Cornell Univ, Ithaca, United States
    Physica A: Statistical Mechanics and its Applications, 1998, 251 (1-2): : 27 - 39
  • [27] Fluctuations in the structure of three-phase lines
    Bukman, DJ
    Widom, B
    PHYSICA A, 1998, 251 (1-2): : 27 - 39
  • [28] NONUNIFORM TRANSMISSION LINES
    GURLEY, JG
    PROCEEDINGS OF THE INSTITUTE OF RADIO ENGINEERS, 1952, 40 (02): : 220 - 221
  • [29] Three-Phase Transmission Line Modelling
    Orsagova, Jaroslava
    PROCEEDINGS OF THE 7TH INTERNATIONAL SCIENTIFIC CONFERENCE ELECTRIC POWER ENGINEERING 2006, 2006, : 203 - 205
  • [30] Automatic EMI filter design for three-phase PWM inverter used in automotive transmission
    Filomeno, Giovanni
    Krueger, Bastian
    Tenberge, Peter
    Dennin, Dirk
    ELEKTROTECHNIK UND INFORMATIONSTECHNIK, 2021, 138 (02): : 110 - 116