Experimental Study on a Multi-Evaporator Loop Heat Pipe with a Dual-Layer Structure Condenser

被引:1
|
作者
Lu, Depu [1 ,2 ]
Xie, Rongjian [2 ]
Wen, Jiajia [2 ]
机构
[1] Shanghai Jiao Tong Univ, Sch Mech Engn, Shanghai 200240, Peoples R China
[2] Chinese Acad Sci, Shanghai Inst Tech Phys, Shanghai 200083, Peoples R China
基金
中国国家自然科学基金;
关键词
multi-evaporator loop heat pipe; dual-layer condenser; heat sharing characteristic; propylene; variable heating power; adverse elevation;
D O I
10.1007/s11630-023-1829-4
中图分类号
O414.1 [热力学];
学科分类号
摘要
A loop heat pipe (LHP) is a kind of passive heat transfer device that uses the latent heat of the working fluid and the capillary forces of the capillary wicks. It demonstrates high heat transfer efficiency, long-distance heat transfer, and high pipeline flexibility. The multi-evaporator loop heat pipe (MeLHP) is a special loop heat pipe with multiple evaporators so that heat collection and emission from multiple heat sources can be achieved. In this paper, a new type of the multi-evaporator loop heat pipe prototype with a dual-layer condenser was designed, which can ensure the uniform and symmetrical layout of pipelines. The working temperature was 20 degrees C, and propylene was used as the working fluid. The performance of the same evaporator in a single-loop LHP was considered as a reference. The experiment was conducted under two heating modes, i.e. single-evaporator heating and multi-evaporator heating, and the working stability of the prototype was verified by applying periodic heating power change and adverse elevation condition. It was observed that the prototype can be successfully started in different heating modes with a heat transfer limit of 230 W. In the test, the four loops were different in heat transfer limit due to the differences of flow resistance, and less power distribution to the loop with lowest heat transfer limit was considered to be beneficial to the prototype's performance. Meanwhile, the prototype showed good heat sharing characteristic as the maximum temperature difference is low (smaller than 2 K in single-evaporator heating mode and 0.5 K in multi-evaporator heating mode). The prototype was of good operational reliability and found to be adaptable to the adverse elevation and cyclic variation of the heating power to a certain extent.
引用
收藏
页码:1466 / 1476
页数:11
相关论文
共 50 条
  • [21] Experimental study on a multi-evaporator mutual defrosting system for air source heat pumps
    Rong, Xiangyang
    Long, Weiguo
    Jia, Jikang
    Liu, Lianhua
    Si, Pengfei
    Shi, Lijun
    Yan, Jinyue
    Liu, Boran
    Zhao, Mishen
    APPLIED ENERGY, 2023, 332
  • [22] Experimental study of heat transfer capacity for loop heat pipe with flat disk evaporator
    Zhang, Zikang
    Zhang, Hao
    Ma, Zhenyuan
    Liu, Zhichun
    Liu, Wei
    APPLIED THERMAL ENGINEERING, 2020, 173
  • [23] Effect of condenser location on heat transfer characteristics of miniature loop heat pipe with flat evaporator
    Huo, Jie-Peng
    Wang, Shuang-Feng
    Zhang, Xian-Feng
    Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics, 2013, 34 (02): : 360 - 363
  • [24] Experimental study on loop heat pipe with two-wick flat evaporator
    Liu, Zhichun
    Wang, Dongdong
    Jiang, Chi
    Yang, Jinguo
    Liu, Wei
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2015, 94 : 9 - 17
  • [25] Experimental study of the loop heat pipe with a flat disk-shaped evaporator
    Wang, Dongdong
    Liu, Zhichun
    Shen, Jun
    Jiang, Chi
    Chen, Binbin
    Yang, Jinguo
    Tu, Zhengkai
    Liu, Wei
    EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2014, 57 : 157 - 164
  • [26] Experimental study on the operating characteristics of a flat bifacial evaporator loop heat pipe
    Joung, Wukchul
    Yu, Taeu
    Lee, Jinho
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2010, 53 (1-3) : 276 - 285
  • [27] Experimental study on operating parameters of miniature loop heat pipe with flat evaporator
    Wang, Shuangfeng
    Huo, Jiepeng
    Zhang, Xianfeng
    Lin, Zirong
    APPLIED THERMAL ENGINEERING, 2012, 40 : 318 - 325
  • [28] EXPERIMENTAL STUDY ON A FLAT LOOP HEAT PIPE COUPLING THE COMPENSATION CHAMBER AND THE CONDENSER
    Mo, Dong-chuan
    Zou, Guan-sheng
    Lu, Shu-shen
    PROCEEDINGS OF THE ASME INTERNATIONAL HEAT TRANSFER CONFERENCE - 2010, VOL 5: FUEL CELLS, GAS TURBINES, HEAT PIPES, JET IMPINGEMENT, RADIATION, 2010, : 349 - 354
  • [29] Effect of evaporator/condenser elevations on a loop heat pipe with non-condensable gas
    Wang, Huanfa
    Lin, Guiping
    Shen, Xiaobin
    Bai, Lizhan
    Yang, Rui
    Wen, Dongsheng
    APPLIED THERMAL ENGINEERING, 2020, 180
  • [30] Experimental investigation of the miniture loop heat pipe with flat evaporator
    Singh, Randeep
    Akbarzadeh, Aliakbar
    Mochizuki, Mastaka
    Nguyen, Thang
    Wuttijumnong, Vijit
    Advances in Electronic Packaging 2005, Pts A-C, 2005, : 697 - 702