Dynamic performance analysis and thermal modelling of a novel two-phase spray cooled rack system for data center cooling

被引:17
|
作者
Liu, Pengfei [1 ]
Kandasamy, Ranjith [1 ]
Ho, Jin Yao [1 ]
Wong, Teck Neng [1 ]
Toh, Kok Chuan [1 ]
机构
[1] Nanyang Technol Univ, Sch Mech & Aerosp Engn, 50 Nanyang Ave, Singapore 639798, Singapore
基金
新加坡国家研究基金会;
关键词
Spray cooled rack; Dynamic study; Thermal modelling; Data center; Energy saving;
D O I
10.1016/j.energy.2023.126835
中图分类号
O414.1 [热力学];
学科分类号
摘要
Cooling systems in information technology (IT) equipment account for the greatest share of direct energy consumption in data centers. Conventional air-cooling schemes are thermally inefficient and energy intensive as they require large temperature difference between heat source and cooling medium. To overcome the aforementioned drawbacks of air-cooling, a "chillerless" novel spraying architecture which has the capability of performing high heat flux cooling, is highly scalable and easily adaptable by modern data centers is proposed in this paper. To demonstrate the scalability and performance of this new cooling scheme, a full-scale spray cooled rack system which has the capacity of housing up to 12 server units is developed. The dynamic performance of the spray cooled rack system under variable ambient temperature is studied. It is found that the ambient temperature strongly affects the spray cooling performances and the chamber pressure stability. A grey box model of the system is established. The newly developed model has successfully predicted the temperature variation on both the water side and spray cooling side with reasonable accuracy. Our model sets the foundation for predictive control of the chamber pressure and workload management of the spray cooling scheme for application in largescale data centers.
引用
收藏
页数:19
相关论文
共 50 条
  • [31] Thermal performance analyses and optimization of data center centralized-cooling system
    Wang, Siqi
    Tu, Rang
    Chen, Xianzhong
    Yang, Xu
    Jia, Kun
    APPLIED THERMAL ENGINEERING, 2023, 222
  • [32] Performance analysis of a novel thermal transpiration vacuum cooling system
    Zhang, Wenjie
    Lu, Wei
    Wang, Botao
    INTERNATIONAL JOURNAL OF GREEN ENERGY, 2022, 19 (02) : 149 - 158
  • [33] Thermal Performance Evaluation of a Data Center Cooling System under Fault Conditions
    Cho, Jinkyun
    Park, Beungyong
    Jeong, Yongdae
    ENERGIES, 2019, 12 (15)
  • [34] Passive two-phase cooling of air circuit breakers in data center power distribution systems
    Robinson, A. J.
    Colenbrander, J.
    Byrne, G.
    Burke, P.
    McEvoy, J.
    Kempers, R.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2020, 121
  • [35] Energy-saving potential of separated two-phase thermosiphon loops for data center cooling
    Sulaiman, Mohammed W.
    Daraghmeh, Hafiz M.
    Wang, Chi-Chuan
    JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2020, 141 (01) : 245 - 265
  • [36] Simulation study on cooling effect of two-phase liquid-immersion cabinet in data center
    Sun, Xiaoqing
    Han, Zongwei
    Li, Xiuming
    APPLIED THERMAL ENGINEERING, 2022, 207
  • [37] Energy-saving potential of separated two-phase thermosiphon loops for data center cooling
    Mohammed W. Sulaiman
    Hafiz M. Daraghmeh
    Chi-Chuan Wang
    Journal of Thermal Analysis and Calorimetry, 2020, 141 : 245 - 265
  • [38] PERFORMANCE ANALYSIS OF AN AIR COMPRESSION REFRIGERATION SYSTEM FOR DATA CENTER COOLING
    Rong, Weilai
    Ma, Guoyuan
    Han, Cong
    Xu, Shuxue
    Sun, Shangyu
    Yu, Guoxin
    THERMAL SCIENCE, 2024, 28 (5A): : 3777 - 3788
  • [39] PERFORMANCE ANALYSIS OF AN AIR COMPRESSION REFRIGERATION SYSTEM FOR DATA CENTER COOLING
    RONG, Weilai
    MA, Guoyuan
    HAN, Cong
    XU, Shuxue
    SUN, Shangyu
    YU, Guoxin
    Thermal Science, 2024, 28 (05): : 3777 - 3788
  • [40] Experimental study on thermal performance of a pumped two-phase battery thermal management system
    Zhu, Yue
    Fang, Yidong
    Su, Lin
    Fei, Ye
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2020, 44 (06) : 4664 - 4676