A numerical study on performance efficiency of a low-temperature horizontal ground-source heat pump system

被引:4
|
作者
Gao, Wu [1 ]
Masum, Shakil [1 ]
Qadrdan, Meysam [1 ]
Thomas, Hywel Rhys [1 ]
机构
[1] Cardiff Univ, Sch Engn, Queens Bldg, Cardiff CF24 3AA, Wales
基金
英国工程与自然科学研究理事会;
关键词
Horizontal ground -source heat pump system; Performance efficiency; Ground temperature; Fluid temperature; Coefficient of performance; District heating and cooling network; COUPLED HEAT; THERMAL PERFORMANCE; NEURAL-NETWORKS; ENERGY-BALANCE; SIMULATION; EXCHANGER; SURFACE; MODEL; FIELD; CONDUCTIVITY;
D O I
10.1016/j.enbuild.2023.113137
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Exploitation of shallow ground and its low-grade heat potential is fundamental to designing 5th generation district heating and cooling (DHC) networks. Horizontal ground-source heat pump (HGSHP) systems are a common way to utilize shallow geothermal energy. Realistic estimation and prediction of performance of a HGSHP system and shallow ground thermal behaviour should consider the whole system including building heating and cooling load, heat pump and ground heat exchanger, and the ground. This should be accompanied by realistic atmospheric and ground conditions. In this paper, a three-dimensional coupled thermal-hydraulic model with realistic boundary conditions adopting a whole system approach is presented. Dynamic heat pump coefficient of performance (COP) that depends on seasonal variation of heating/cooling demand and ground conditions are also considered. Model validations are conducted against experimental and analytical results in literatures. The model is applied for evaluating a HGSHP system to support development of a 5th generation DHC network on a potential site in the UK. Several influencing factors, such as ground moisture transfer, building thermal load mode, buried depth of ground loops, and initial ground temperature profile are studied to assess performance efficiency of the HGSHP system and evolution of ground thermal behaviour in response to heat extraction or rejection into the ground. The results show that 5% of the monthly total heat demand of the site could be met by the designed HGSHP system, consisting of 200 U-shaped ground loops buried at the depth of 3 m and pure water as the heat carrier. Overlooking the ground moisture transfer or hyperbolizing the ground saturation would overestimate the load-carrying capacity of the HGSHP system. The HGSHP system is more efficient with a higher heat pump COP under the heating and cooling mode than under the heating-only mode. Predicted performance of the HGSHP system improves with buried depth of the ground loops. The results also show that a 1 celcius increase in the undisturbed ground temperature could suffice up to 8% of the monthly total heat demand of the site.
引用
收藏
页数:19
相关论文
共 50 条
  • [41] Hybrid ground-source heat pump system with active air source regeneration
    Allaerts, K.
    Coomans, M.
    Salenbien, R.
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2015, 90 : 230 - 237
  • [42] A review of ground-source heat pump systems with heat pipes for energy efficiency in buildings
    Wu, Siyuan
    Dai, Yuchao
    Lie, Xiaolu
    Oppong, Francis
    Xu, Cangsu
    [J]. CLEANER ENERGY FOR CLEANER CITIES, 2018, 152 : 413 - 418
  • [43] Performance of a direct expansion ground-source heat pump for air conditioning
    Moriya, Dai
    Takeda, Tetsuaki
    [J]. Proceedings of the International Conference on Power Engineering 2021, ICOPE 2021, 2021,
  • [44] Evaluation of ground-source heat pump combined latent heat storage system performance in greenhouse heating
    Benli, Hueseyin
    Durmus, Aydin
    [J]. ENERGY AND BUILDINGS, 2009, 41 (02) : 220 - 228
  • [45] Energetic performance analysis of a ground-source heat pump system with latent heat storage for a greenhouse heating
    Benli, Huseyin
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2011, 52 (01) : 581 - 589
  • [46] INFLUENCE FACTORS ANALYSIS ON HEAT TRANSFER PERFORMANCE OF UNDERGROUND HEAT EXCHANGER IN GROUND-SOURCE HEAT PUMP SYSTEM
    Wu, X. Y.
    Dai, X. L.
    Yang, J. C.
    [J]. 7TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, PROCEEDINGS OF ISHVAC 2011, VOLS I-IV, 2011, : 811 - 817
  • [47] Numerical modelling of transient soil temperature distribution for horizontal ground heat exchanger of ground source heat pump
    Kayaci, Nurullah
    Demir, Hakan
    [J]. GEOTHERMICS, 2018, 73 : 33 - 47
  • [48] A Case Study of a Ground-Source Heat Pump System in an East China Office Building
    Li, Zhengrong
    Zhao, Mingming
    Yu, Sheng
    Li, Haozhu
    [J]. 6TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS I-III, PROCEEDINGS, 2009, : 1586 - 1592
  • [49] Ground-source heat pump system research - Past, present, and future
    Spitler, JD
    [J]. HVAC&R RESEARCH, 2005, 11 (02): : 165 - 167
  • [50] Exergy analysis and operational efficiency of a horizontal ground-source heat pump system operated in low-energy test house under simulated occupancy conditions
    Ally, Moonis R.
    Munk, Jeffrey D.
    Baxter, Van D.
    Gehl, Anthony C.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2012, 35 (04): : 1092 - 1103