Study on the Detection of Single and Dual Partial Discharge Sources in Transformers Using Fiber-Optic Ultrasonic Sensors

被引:0
|
作者
Liu, Feng [1 ]
Shi, Yansheng [1 ]
Zhang, Shuainan [1 ]
Wang, Wei [1 ]
机构
[1] North China Elect Power Univ, Sch Elect & Elect Engn, Beijing 102206, Peoples R China
基金
中国国家自然科学基金;
关键词
fiber-optic ultrasonic sensors; transformer fault diagnosis; DOA estimation; single and dual PD source detection; DOA ESTIMATION;
D O I
10.3390/photonics11090815
中图分类号
O43 [光学];
学科分类号
070207 ; 0803 ;
摘要
Partial discharge is a fault that occurs at the site of insulation defects within a transformer. Dual instances of partial discharge origination discharging simultaneously embody a more intricate form of discharge, where the interaction between the discharge sources leads to more intricate and unpredictable insulation damage. Conventional piezoelectric transducers are magnetically affixed to the exterior metal tank of transformers. The ultrasonic signals emanating from partial discharge undergo deflection and reverberation upon traversing the windings, insulation paperboards, and the outer shell, resulting in signal attenuation and thus making it difficult to detect such faults. Furthermore, it is challenging to distinguish between simultaneous discharges from dual partial discharge sources and continuous discharges from a single source, often leading to missed detection and repairs of fault points, which increase the maintenance difficulty and cost of power equipment. With the advancement of MEMS (Micro-Electro-Mechanical System) technology, fiber-optic ultrasonic sensors have surfaced as an innovative technique for optically detecting partial discharges. These sensors are distinguished by their minute dimensions, heightened sensitivity, and robust immunity to electromagnetic disturbances. and excellent insulation properties, allowing for internal installation within power equipment for partial discharge monitoring. In this study, we developed an EFPI (Extrinsic Fabry Perot Interferometer) optical fiber ultrasonic sensor that can be installed inside transformers. Based on this sensor array, we also created a partial discharge ultrasonic detection system that estimates the directional information of single and dual partial discharge sources using the received signals from the sensor array. By utilizing the DOA (Direction of Arrival) as a feature recognition parameter, our system can effectively detect both simultaneous discharges from dual partial discharge sources and continuous discharges from a single source within transformer oil tanks, meeting practical application requirements. The detection methodology presented in this paper introduces an original strategy and resolution for pinpointing the types of partial discharges occurring under intricate conditions within power apparatus, effectively distinguishing between discharges from single and dual partial discharge sources.
引用
收藏
页数:14
相关论文
共 50 条
  • [1] Fiber-Optic Acoustic Sensors for Partial Discharge Detection in Power Cables
    Hao, Chen
    Yang, Xu
    Sen, Qian
    Lei, Su
    PROCEEDINGS OF THE 21ST INTERNATIONAL SYMPOSIUM ON HIGH VOLTAGE ENGINEERING, VOL 1, 2020, 598 : 572 - 581
  • [2] Localization for Dual Partial Discharge Sources in Transformer Oil Using Pressure-Balanced Fiber-Optic Ultrasonic Sensor Array
    Liu, Feng
    Shi, Yansheng
    Zhang, Shuainan
    Wang, Wei
    SENSORS, 2024, 24 (14)
  • [3] Sulfur Hexafluoride-Filled Extrinsic Fabry-Perot Interferometric Fiber-Optic Sensors for Partial Discharge Detection in Transformers
    Dong, Bo
    Han, Ming
    Sun, Liqun
    Wang, Jiajun
    Wang, Yunjing
    Wang, Anbo
    IEEE PHOTONICS TECHNOLOGY LETTERS, 2008, 20 (17-20) : 1566 - 1568
  • [4] Fiber-optic ultrasonic sensors and applications
    Qiao Xue-Guang
    Shao Zhi-Hua
    Bao Wei-Jia
    Rong Qiang-Zhou
    ACTA PHYSICA SINICA, 2017, 66 (07)
  • [5] The detection of ultrasound using fiber-optic sensors
    Culshaw, Brian
    Thursby, Graham
    Betz, Daniel
    Sorazu, Borja
    IEEE SENSORS JOURNAL, 2008, 8 (7-8) : 1360 - 1367
  • [6] Ultrasonic Detection Coherence of Fiber Bragg Grating for Partial Discharge in Transformers
    Shi, Cheng
    Ma, Guoming
    Mao, Naiqiang
    Zhang, Qiang
    Zheng, Qing
    Li, Chengrong
    Zhao, Shujing
    2017 IEEE 19TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2017,
  • [7] Partial discharge detection using the fiber-optic Mach–Zehnder interferometer system for XLPE cables
    Yanpeng Hao
    Yanwen Chen
    Yun Chen
    Ying Liu
    Yanting Cheng
    Lin Yang
    Jiapeng Xiao
    Tao Huang
    Electrical Engineering, 2022, 104 : 2133 - 2140
  • [8] Direct detection of charge and discharge process in supercapacitor by fiber-optic LSPR sensors
    Qian, Siyu
    Chen, Xinlong
    Jiang, Shiyu
    Pan, Qiwen
    Gao, Yachen
    Wang, Lei
    Peng, Wei
    Liang, Shanjun
    Zhu, Jie
    Liu, Shengchun
    NANOPHOTONICS, 2020, 9 (05) : 1071 - 1079
  • [9] Fiber-optic components for single-mode fiber optic sensors
    Schmidlin, EM
    SECOND PACIFIC NORTHWEST FIBER OPTIC SENSOR WORKSHOP, 1996, 2872 : 59 - 70
  • [10] Wavelength Locking and Calibration of Fiber-Optic Ultrasonic Sensors Using Single-Sideband-Modulated Laser
    Alshammari, Mohammed
    Han, Ming
    PHOTONICS, 2024, 11 (11)