Analytical model for characterizing mass transfer of volatile organic compounds in internally-cooled liquid desiccant dehumidifiers

被引:0
|
作者
Liu, Zhihang [1 ]
Fu, Huangxi [1 ]
Huang, Shunyi [1 ]
机构
[1] Jiangxi Univ Sci & Technol, Sch Civil & Surveying & Mapping Engn, Ganzhou 341000, Peoples R China
关键词
Analytical model; Mass transfer; Volatile organic compounds; Liquid desiccant; Internally-cooled dehumidifier; INDOOR AIR-QUALITY; PERFORMANCE;
D O I
10.1016/j.applthermaleng.2025.126109
中图分类号
O414.1 [热力学];
学科分类号
摘要
Volatile organic compounds (VOCs) in indoor air pose a significant hazard to human health, owing to their potential associated chronic and acute health risks. Liquid dehumidification has emerged as a promising technology for eliminating indoor VOCs. However, the studies on the mass transfer behavior of VOCs in dehumidifiers are mainly confined to experimental and numerical methods, which are both time-consuming and labor-intensive. In contrast, analytical methods are more attractive and advantageous in solving these problems. Therefore, in the present study, we propose an analytical model to quantify the mass transfer behavior of VOCs in an internally-cooled dehumidifier. To confirm the broad applicability of the proposed model, both the hydrophilic and hydrophobic properties of VOCs were considered. Formaldehyde and benzene were selected as two typical representatives. The reliability of the proposed model was demonstrated by investigating the VOC transfer characteristics and removal performance as the key factors varied. It was found that the analytical results agree well with the published numerical results. With variation of the key parameters, the trends of the VOC removal performance obtained by the analytical and numerical methods are basically in agreement. The analytical model can not only effectively describe the mass transfer characteristics of VOCs, but also adequately determine the VOCs removal performance. Moreover, the analytical model shows a wide-range response to different VOCs, with the order of Henry's law constant ranging from 10-5 to 10-3. For both hydrophilic formaldehyde and hydrophobic benzene, the deviations do not exceed +/- 10 %. This study provides an intuitive and labor-saving method to evaluate VOC removal using internally-cooled dehumidifiers.
引用
收藏
页数:11
相关论文
共 50 条
  • [21] Entropy and exergy analysis of an internally-cooled membrane liquid desiccant dehumidifier
    Liang, Cai-Hang
    Li, Nan-Feng
    Huang, Si-Min
    ENERGY, 2020, 192
  • [22] Cooling and dehumidification performance analysis of internally-cooled liquid desiccant absorbers
    Khan, AY
    APPLIED THERMAL ENGINEERING, 1998, 18 (05) : 265 - 281
  • [23] Experimental analysis of a novel internally-cooled dehumidifier with self-cooled liquid desiccant
    Lun, Wei
    Li, Kuining
    Liu, Bin
    Zhang, Hongji
    Yang, Yuxiao
    Yang, Cheng
    BUILDING AND ENVIRONMENT, 2018, 141 : 117 - 126
  • [24] Heat and Mass Transfer Enhancement of a Multi-stage Internally-Cooled Membrane-Based Liquid Desiccant Dehumidification
    Fang, Song
    Wu, Qiao-Xian
    Rong, Yang-Yi-Ming
    Zhou, Xia
    Wang, Kai
    Qiu, Li-Min
    Zhi, Xiao-Qin
    Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics, 2021, 42 (09): : 2216 - 2226
  • [25] Performance analysis of an internally-cooled plate membrane liquid desiccant dehumidifier (IMLDD): An analytical solution approach
    Huang, Si-Min
    Yang, Minlin
    Hu, Bing
    Tao, Shi
    Qin, Frank G. F.
    Weng, Wanliang
    Wang, Wenhao
    Liu, Jian
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2018, 119 : 577 - 585
  • [26] Analytical solution of heat and mass transfer process in internally cooled liquid desiccant dehumidifiers using refrigerant as cooling medium (vol 190, pg 1, 2019)
    Liu, Jun
    Liu, Xiaohua
    Zhang, Tao
    ENERGY AND BUILDINGS, 2020, 210
  • [27] An analytical model for heat and mass transfer processes in internally cooled or heated liquid desiccant-air contact units
    Ren, Cheng Qin
    Tu, Min
    Wang, Hua Hui
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2007, 50 (17-18) : 3545 - 3555
  • [28] Mathematical modeling and parametric study of liquid desiccant system with internally-cooled dehumidifier
    Hendijani, Arash Doustani
    Gilani, Neda
    THERMAL SCIENCE AND ENGINEERING PROGRESS, 2018, 5 : 213 - 229
  • [29] Performance study of the internally-cooled ultrasonic atomization liquid desiccant dehumidification system
    Yang, Zili
    Tao, Ruiyang
    Ni, Hui
    Zhong, Ke
    Lian, Zhiwei
    ENERGY, 2019, 175 : 745 - 757
  • [30] On the importance of the heat and mass transfer driving force reversal and heat-cold offset in internally-cooled liquid-desiccant system
    Guan, Bowen
    Liu, Xiaohua
    Zhang, Tao
    Liu, Jun
    BUILDING AND ENVIRONMENT, 2020, 185