Analysis of the operation of cooling towers for the complete cooling of coke gases

被引:0
|
作者
Donetskij Gosudarstvennyj, Tekhnicheskij Univ, Donetsk, Ukraine [1 ]
机构
来源
Koks i Khimiya | 1996年 / 04期
关键词
Air pollution - Carbon dioxide - Coke plants - Cooling systems - Cooling water - Cyanides - Environmental protection - Hydrogen sulfide - Industrial wastes - Organic compounds - Purification - Volatile organic compounds;
D O I
暂无
中图分类号
学科分类号
摘要
The analysis of the desorption of volatile components from the circulating water of the commercial cooling-towers at the Avdeevskij and Donettsk coke plants is performed. The analysis revealed that 23.6-40.1% ammonia, 50% hydrogen cyanide, 6.7-51.2 volatile phenols, 27.3-68% H2S, and 18.2-41.7% CO2 pass to an air atmosphere. The use of a so-called ″closed″ cycle of water cooling improves the ecological conditions, but complicates the procedure of catching the benzene hydrocarbons and hydrogen sulfide from the coke gases.
引用
收藏
页码:39 / 40
相关论文
共 50 条