Experimental evaluation of attic radiant barriers

被引:0
|
作者
Al-Asmar, Husam R. [1 ]
Jones, Byron W. [1 ]
Matteson, Dennis K. [1 ]
机构
[1] Kansas State Univ, Manhattan, United States
来源
ASHRAE Transactions | 1996年 / 102卷 / 01期
关键词
Atmospheric temperature - Buildings - Cooling - Environmental chambers - Heat flux - Heat transfer - Mathematical models - Roofs - Thermal insulation - Ventilation;
D O I
暂无
中图分类号
学科分类号
摘要
This paper presents the results of ASHRAE Research Project 577-RP, 'Attic Radiant Barrier Systems,' an experimental study to evaluate the impact of radiant barrier systems on summer cooling loads in residential buildings. A simulated attic was built inside the entire area of a 24-ft by 12-ft (7.3-m by 3.7-m) environmental chamber. A total of 72 steady-state experiments were conducted. Roof temperature varied from 120°F to 160°F (41°C to 71°C), attic ventilation varied from 0 to 2.0 cfm/ft2 (0.01 m3/s&middotm2), and nominal R-11 and R-19 (2.0 and 3.3 m2&middot°C/W) insulations were used in the experiments. Three radiant barrier configurations were used: under the roof deck between the rafters, directly over the ceiling insulation, and with no radiant barrier. Additional experiments were conducted to examine the movement of ventilation air inside the attic. The results show reductions in attic heat gains ranging from 17% to 26% with no ventilation and from 24% to 42% when the attic was ventilated. The location of the radiant barrier had little effect on ceiling heat gain. In addition to reducing ceiling heat gains, the radiant barrier mounted under the roof reduced attic temperatures 10°F to 15°F (6°C to 8°C) under typical conditions. The radiant barrier mounted over the ceiling insulation had a lesser effect on attic air temperature. Soffit-to-ridge ventilation was more effective in reducing ceiling heat gains than gable-to-gable ventilation.
引用
收藏
页码:297 / 306
相关论文
共 50 条
  • [31] Study says radiant barriers reduce energy
    不详
    ASHRAE JOURNAL, 2001, 43 (10) : 6 - 6
  • [32] EXPERIMENTAL VALIDATION OF AN ATTIC CONDENSATION MODEL
    BURCH, DM
    ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1984, 26 (05): : 50 - 50
  • [33] Performance Evaluation and Experimental Study of the Induction Radiant Air-conditioning System
    Si, Qiang
    Zhang, Xiaosong
    9TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING (ISHVAC) JOINT WITH THE 3RD INTERNATIONAL CONFERENCE ON BUILDING ENERGY AND ENVIRONMENT (COBEE), 2015, 121 : 1795 - 1804
  • [35] Experimental Evaluation of Radiant Heating Ceiling Systems Based on Thermal Comfort Criteria
    Safizadeh, M. Reza
    Schweiker, Marcel
    Wagner, Andreas
    ENERGIES, 2018, 11 (11)
  • [36] Performance evaluation of radiant baseboards (skirtings) for room heating - An analytical and experimental approach
    Ploskic, Adnan
    Holmberg, Sture
    APPLIED THERMAL ENGINEERING, 2014, 62 (02) : 382 - 389
  • [37] Experimental Evaluation of the Thermal Performance of Raised Floor Integrated Radiant Heating Panels
    Kim, Dong-Woo
    Joe, Goo-Sang
    Park, Sang-Hoon
    Yeo, Myoung-Souk
    Kim, Kwang-Woo
    ENERGIES, 2017, 10 (10):
  • [38] Experimental evaluation of the cooling performance of radiant ceiling panels with thermal energy storage
    Gallardo, Andres
    Berardi, Umberto
    ENERGY AND BUILDINGS, 2022, 262
  • [39] Experimental evaluation of a heating radiant wall coupled to a ground source heat pump
    Romani, Joaquim
    Perez, Gabriel
    de Gracia, Alvaro
    RENEWABLE ENERGY, 2017, 105 : 520 - 529
  • [40] BARRIERS TO STUDENTS' CREATIVE EVALUATION OF UNEXPECTED EXPERIMENTAL FINDINGS
    Kadayifci, Hakki
    JOURNAL OF BALTIC SCIENCE EDUCATION, 2017, 16 (03): : 414 - 428