A new method to check the polarity of neutral reactor for 500 kV shunt-reactor

被引:0
|
作者
Zhang, Jing-Wei [1 ]
机构
[1] Shaoguan Power Supply Bureau, Guangdong Power Grid Corporation, Shaoguan 512026, China
关键词
Electric power system protection - Electric reactors;
D O I
暂无
中图分类号
学科分类号
摘要
The polarity of the zero-sequence current differential protection of 500 kV shunt-reactor is not easy to be checked by using the neutral reactor CT winding because there is no current during the normal operation. It may easily lead to misoperation when outside faults happen. This paper presents a method to check the polarity of neutral reactor CT winding. The basic idea is to simulate a single-phase ground by the reactor single-phase operation. There will be a current in the neutral reactor CT winding. The polarity of the zero-sequence protection can be checked by observing the protection's action. Using this method should avoid the impact on the other equipments. Some measures should be taken. The dangerous points in the testing are analyzed and the testing process as well as realative countermeasures is presented. At last, the effectiveness of this method is proved by the on-site testing.
引用
收藏
页码:241 / 243
相关论文
共 50 条
  • [31] Selection of dynamic current of neutral reactor on 1000 kV transmission system
    Gu, Ding-Xie
    Li, Zhen-Qiang
    Wu, Zhi-Rong
    Gaodianya Jishu/High Voltage Engineering, 2010, 36 (10): : 2362 - 2367
  • [32] A new IEEE application guide for shunt reactor switching
    Peelo, DF
    Ruoss, EM
    IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (02) : 881 - 887
  • [33] High-frequency reignition current and its influence on electrical durability of circuit breakers associated with shunt-reactor current switching
    Tanae, H
    Matsuzaka, E
    Nishida, I
    Matori, I
    Tsukushi, M
    Hirasawa, K
    IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (03) : 1105 - 1111
  • [34] Characteristics analysis of acoustic interference around 1000 kV uhv shunt reactor
    China Electric Power Research Institute, Wuhan
    430074, China
    不详
    310058, China
    Gaodianya Jishu, 12 (3926-3932):
  • [35] Application of universal neutral reactor in shunt compensated transmission lines: feasibility study
    Jafarian, Peyman
    Eskandari, Hamid
    Sanaye-Pasand, Majid
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (09) : 2181 - 2189
  • [36] Choice of neutral inductance and insulation level of shunt reactor neutral point in UHV AC pilot project
    Tian, Qing
    Gaodianya Jishu/High Voltage Engineering, 2009, 35 (03): : 475 - 479
  • [37] Calculation and Analysis of Internal Overvoltage of 500 kV High Coupled Split Reactor
    Mo, Wenxiong
    Wu, Kaijian
    Yuan, Zhao
    Chen, Lixue
    Liu, Junxiang
    Zhu, Lu
    Gaodianya Jishu/High Voltage Engineering, 2021, 47 (02): : 495 - 503
  • [38] Fault analysis and preventive measures for a 500 kV oil-immersed reactor
    Hu X.
    Xu P.
    Wang H.
    Chu Y.
    Chen H.
    Xu, Peng (xupeng1990_ncepu@163.com), 1600, Power System Protection and Control Press (49): : 173 - 178
  • [39] Effect of interphase magnetic coupling of shunt reactor on transmission-line open-phase overvoltages and neutral reactor optimisation
    Eskandari, Hamid
    Jafarian, Peyman
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (04) : 1004 - 1011
  • [40] Application of phase controlled circuit breakers in overvoltage suppression for 35 kV shunt reactor
    Zheng Y.
    Yang S.
    He W.
    Xu H.
    Yan D.
    Shao X.
    Zhao L.
    Luo T.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2019, 39 (02): : 211 - 215and223