Fault analysis and preventive measures for a 500 kV oil-immersed reactor

被引:0
|
作者
Hu X. [1 ]
Xu P. [2 ]
Wang H. [3 ]
Chu Y. [1 ]
Chen H. [2 ]
机构
[1] Xuchang Ketop Electrical Research Institute Co., Ltd., Xuchang
[2] State Grid Jiangsu Electric Power Co., Ltd. Maintence Branch Company, Nanjing
[3] XJ Group Corporation, Xuchang
来源
Xu, Peng (xupeng1990_ncepu@163.com) | 1600年 / Power System Protection and Control Press卷 / 49期
基金
中国国家自然科学基金;
关键词
Diagnostic test of oil chromatogram; Fault diagnosis; High voltage shunt reactor; Poor insulation between sheets;
D O I
10.19783/j.cnki.pspc.200246
中图分类号
学科分类号
摘要
As an important reactive power compensation device in a power system, the high voltage shunt reactor has the function of compensating for the capacitance effect of a transmission line, regulating reactive power and voltage. A reactor fault in operation will pose a serious threat to the safety and stability of the power grid, and so it is of great significance to analyze the cause of a fault for the maintenance of power grid security. A fault on a 500 kV oil-immersed high voltage shunt reactor is analyzed based on the component analysis of characteristic gas in the oil chromatogram, the calculation of gas content ratio, the trend analysis of characteristic gas and the characteristic gas calculation of the device before return to the factory. Diagnostic tests of DC resistance, insulation and dielectric loss, vibration, noise and temperature rise etc. are carried out for further investigation, and it is concluded that the cause of the accident is poor insulation between silicon steel sheets of reactor core, this being achieved by employing winding inspection, core inspection, connection part inspection, sample detection and analysis. Finally, corresponding preventive measures are presented, providing reference for process control, fault diagnosis and maintenance of the same type of high voltage shunt reactor. © 2021 Power System Protection and Control Press.
引用
收藏
页码:173 / 178
页数:5
相关论文
共 25 条
  • [1] GAN Yuan, BAI Rui, ZHANG Qi, Steady-state electromagnetic field and electrodynamic analysis of dry-type air-core reactor based on field-circuit coupling, Power System Protection and Control, 47, 21, pp. 144-149, (2019)
  • [2] ZIVANOVIC R., Analysis of recorded transients on 765 kV lines with shunt reactors, 2005 IEEE Russia Power Tech, pp. 1-4, (2005)
  • [3] DAI Feng, SUN Yongjun, TIAN Tao, Et al., Reliability analysis of SF6 circuit breaker crank arm based on NESSUS, Machine Building & Automation, 46, 1, pp. 215-219, (2017)
  • [4] XU Peng, GAN Qiang, SHAO Xincang, Et al., Fault analysis of 500 kV SF6 gas insulated current transformer, Transformer, 55, 6, pp. 70-73, (2018)
  • [5] MOHAMMAD A I, MORT T, JETER J, Et al., Turn-to-turn fault protection for dry-type shunt reactors, 2018 IEEE/PES Transmission and Distribution Conference and Exposition (T&D), pp. 1-5, (2018)
  • [6] ZHENG Tao, ZHAO Yanjie, JIN Ying, Et al., Design and analysis on the turn-to-turn fault protection scheme for the control winding of a magnetically controlled shunt reactor, IEEE Transactions on Power Delivery, 30, 2, pp. 967-975, (2015)
  • [7] CHEN Hao, DENG Guangjing, WANG Yurong, Et al., Research on the secondary side problem caused by breaker rear-wiring pattern in reactor interval, Power System Protection and Control, 42, 18, pp. 122-126, (2014)
  • [8] DAS S, SIDHU T S, ZADEH M R D, Et al., A novel hybrid differential algorithm for turn to turn fault detection in shunt reactors, IEEE Transactions on Power Delivery, 32, 6, pp. 2537-2545, (2017)
  • [9] MA Zhaoxin, CHEN Hao, CHAI Yanli, Et al., Analysis of voltage stability uncertainty using stochastic response surface method related to wind farm correlation, Protection and Control of Modern Power Systems, 2, 3, pp. 211-219, (2017)
  • [10] DING T, LI C, CHEN C, Et al., Risk assessment based long-term transmission system hardening under prior probabilistic information, IET Generation, Transmission & Distribution, 13, 1, pp. 108-115, (2019)