Fault analysis and preventive measures for a 500 kV oil-immersed reactor

被引:0
|
作者
Hu X. [1 ]
Xu P. [2 ]
Wang H. [3 ]
Chu Y. [1 ]
Chen H. [2 ]
机构
[1] Xuchang Ketop Electrical Research Institute Co., Ltd., Xuchang
[2] State Grid Jiangsu Electric Power Co., Ltd. Maintence Branch Company, Nanjing
[3] XJ Group Corporation, Xuchang
来源
Xu, Peng (xupeng1990_ncepu@163.com) | 1600年 / Power System Protection and Control Press卷 / 49期
基金
中国国家自然科学基金;
关键词
Diagnostic test of oil chromatogram; Fault diagnosis; High voltage shunt reactor; Poor insulation between sheets;
D O I
10.19783/j.cnki.pspc.200246
中图分类号
学科分类号
摘要
As an important reactive power compensation device in a power system, the high voltage shunt reactor has the function of compensating for the capacitance effect of a transmission line, regulating reactive power and voltage. A reactor fault in operation will pose a serious threat to the safety and stability of the power grid, and so it is of great significance to analyze the cause of a fault for the maintenance of power grid security. A fault on a 500 kV oil-immersed high voltage shunt reactor is analyzed based on the component analysis of characteristic gas in the oil chromatogram, the calculation of gas content ratio, the trend analysis of characteristic gas and the characteristic gas calculation of the device before return to the factory. Diagnostic tests of DC resistance, insulation and dielectric loss, vibration, noise and temperature rise etc. are carried out for further investigation, and it is concluded that the cause of the accident is poor insulation between silicon steel sheets of reactor core, this being achieved by employing winding inspection, core inspection, connection part inspection, sample detection and analysis. Finally, corresponding preventive measures are presented, providing reference for process control, fault diagnosis and maintenance of the same type of high voltage shunt reactor. © 2021 Power System Protection and Control Press.
引用
收藏
页码:173 / 178
页数:5
相关论文
共 25 条
  • [11] WANG Yurong, WAN Qiulan, LI Fangxing, Et al., Reactive power planning based on fuzzy clustering, gray code, and simulated annealing, IEEE Transactions on Power Systems, 26, 4, pp. 2246-2255, (2011)
  • [12] ZHOU Ming, CAO Wei, CHEN Wentao, Et al., Study on the influence of series reactor on short circuit current characteristics of power system, Power System Protection and Control, 45, 11, pp. 147-153, (2017)
  • [13] CAO J, DAVIDSON C, MOULSON S., Dynamic modelling of saturable reactor for HVDC applications, IET Science Measurement & Technology, 1, 3, pp. 138-144, (2007)
  • [14] CHEN Hao, ZHU Chao, LI Yifeng, Et al., Research on calculation and measurement of power frequency electric field for transmission line, Journal of Electrical Engineering, 11, 5, pp. 40-45, (2016)
  • [15] TENG Yufei, FENG Shilin, ZHANG Zhenyuan, Et al., Online identification of error overcurrent alerts of 500 kV high voltage shunt reactor based on data-driven, Power System Protection and Control, 47, 3, pp. 146-153, (2019)
  • [16] TIAN Xiaofei, SUN Wenxing, YANG Xian, Et al., Defect analysis and rectification measures of oil immersed shunt core reactor, Guangdong Electric Power, 32, 2, pp. 144-151, (2019)
  • [17] YAN Bing, QIAN Guochao, WANG Ke, Et al., Study on the partial discharge characteristics and gas production law of turn to turn insulation of oil immersed high voltage shunt reactor, High Voltage Apparatus, 54, 6, pp. 106-112, (2018)
  • [18] ZHANG Zongyou, HE Xiaofeng, ZHAO Yongxia, Calculation of eddy current loss of core reactor winding, Power Capacitor & Reactive Power Compensation, 36, 6, pp. 73-77, (2015)
  • [19] ZHANG Nongtao, YAN Bing, PENG Qingjun, Et al., Life cycle management of 500 kV oil immersed high voltage shunt reactor, Yunnan Electric Power, 46, 5, pp. 59-63, (2018)
  • [20] Guide to the analysis and the diagnosis of gases dissolved in transformer oil: DL/T722-2014