Integrated optimization of the building envelope and the HVAC system in office building retrofitting

被引:0
|
作者
Cui, Wenjing [1 ]
Liu, Guiwen [2 ]
Wang, Yanyan [1 ]
Li, Kaijian [2 ]
机构
[1] School of Management Engineering, Shandong Jianzhu University, Jinan,250101, China
[2] School of Management Science and Real Estate, Chongqing University, Chongqing,400044, China
基金
中国国家社会科学基金;
关键词
Air curtains - Air preheaters - Concretes - HVAC - Linear programming - Mortar - Multiobjective optimization - Thermal comfort - Thermal insulation - Walls (structural partitions);
D O I
10.1016/j.csite.2024.105185
中图分类号
学科分类号
摘要
Increasing the energy efficiency of existing buildings is the major strategy to reach carbon neutral targets, given that the building sector is a major emitter. In particular, one major part of building energy usage is the building heating, ventilation and air-cooling system, which are highly depending on the thermal performance of building envelope and increase the challenge of selecting optimal packages of energy efficiency measures. This paper thereby presents a method for optimizing the building envelope and heating, ventilation and air-cooling system. The simulation-based NSGA-III approach developed in this paper is based on coupling the dynamic simulation models created in EnergyPlus software with the non-dominated sorting genetic algorithm, as the engine that performs an optimization process. A large domain of energy efficiency packages combined with heating, ventilation and air-cooling systems and building envelope are investigated to minimize energy consumption, retrofit cost and thermal discomfort in indoor environments, which including ideal loads air system, four pipe fan coil system and variable refrigerant flow system, insulation materials and insulation thickness for external walls and roof, different types of external windows, and window-wall ratio. An office building in Chongqing was chosen as a case study to demonstrate the practical implementation of the proposed method. The results show that the four pipe fan coil system was superior in the diversity and performance of the Pareto front. Then, the optimal packages were generated by a synthetic method, which have 58.57 kWh/m2 of energy consumption, 30.76 CNY/m2 of retrofit cost and 40.67 % of the percentage of thermal discomfort hours. The results also indicate that the yearly energy savings rates are 17.30 %, 23.05 % and 21.10 % separately for ideal loads air system, four pipe fan coil system and variable refrigerant flow system after performing optimization. These results highlight the importance and necessity of performing an optimization procedure for existing buildings to select the optimal retrofit measures. © 2024 The Authors
引用
下载
收藏
相关论文
共 50 条
  • [11] HVAC system optimization - In-building section
    Lu, L
    Cai, WJ
    Soh, YC
    Li, SY
    PROCEEDINGS OF THE 4TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS 1 AND 2, 2003, : 622 - 631
  • [12] HVAC system optimization - in-building section
    Lu, L
    Cai, WJ
    Xie, LH
    Li, SJ
    Soh, YC
    ENERGY AND BUILDINGS, 2005, 37 (01) : 11 - 22
  • [13] Retrofitting an office building towards a net zero energy building
    Pyloudi, Eleni
    Papantoniou, Sotiris
    Kolokotsa, Dionysia
    ADVANCES IN BUILDING ENERGY RESEARCH, 2015, 9 (01) : 20 - 33
  • [14] Building Envelope Retrofitting Strategies for Energy-Efficient Office Buildings in Saudi Arabia
    Al-Tamimi, Nedhal
    BUILDINGS, 2022, 12 (11)
  • [15] An Investigation on the Impact of Retrofitting the Envelope of a Typical Small Office Building with PCM on the Building Energy Consumption in Different Zones of the US
    Hosseini, Amin
    Azar, Pouya Ammari
    Yang-Seon, Kim
    ASHRAE TRANSACTIONS 2021, VOL 127, PT 1, 2021, 127 : 161 - 169
  • [16] Design optimization of office building envelope configurations for energy conservation
    Lin, Yu-Hao
    Tsai, Kang-Ting
    Lin, Min-Der
    Yang, Ming-Der
    APPLIED ENERGY, 2016, 171 : 336 - 346
  • [17] Technoeconomic evaluation of insulated building integrated photovoltaic system as a building envelope
    Singh D.
    Rawat M.
    Buddhi D.
    Materials Today: Proceedings, 2023, 80 : 339 - 343
  • [18] TOOL FOR ENERGY EFFICIENT BUILDING ENVELOPE RETROFITTING
    Jha, Bandana
    Bhattacharjee, Bishwajit
    2018 BUILDING PERFORMANCE ANALYSIS CONFERENCE AND SIMBUILD, 2018, : 1 - 8
  • [19] Multi-objective optimization of building integrated photovoltaic windows in office building
    Qiao, Xinyu
    Zhao, Tianyi
    Zhang, Xingxing
    Li, Yu
    ENERGY AND BUILDINGS, 2024, 318
  • [20] THERMAL PERFORMANCE ESTIMATION OF THE OFFICE BUILDING WITH THE BUILDING INTEGRATED PHOTOVOLTAIC SYSTEM
    Egrican, Nilufer
    Akguc, Alpay
    PROCEEDINGS OF THE ASME 5TH INTERNATIONAL CONFERENCE ON ENERGY SUSTAINABILITY 2011, PTS A-C, 2012, : 91 - 101