Analysis of structural improvement and potential energy recovery in the rain zone of natural draft wet cooling tower

被引:1
|
作者
Wang, Zhanpeng [1 ]
Zhang, Wenjie [2 ]
Tong, Shuaiwen [1 ]
Wei, Huimin [1 ]
机构
[1] North China Elect Power Univ, Key Lab Power Stn Energy Transfer Convers & Syst, Minist Educ, Beijing 102206, Peoples R China
[2] China Nucl Power Engn Co Ltd, Beijing, Peoples R China
关键词
Natural draft wet cooling tower; Dry-wet hybrid rain zone; High-level water collecting natural draft wet; cooling tower; Potential energy recovery; Crosswind; THERMAL PERFORMANCE; VENTILATION PERFORMANCE; NUMERICAL-SIMULATION; FIELD-TEST; LAYOUT; FLOW;
D O I
10.1016/j.icheatmasstransfer.2024.108268
中图分类号
O414.1 [热力学];
学科分类号
摘要
To address the issues of mismatched resistance and heat transfer characteristics in the rain zone of natural draft wet cooling towers (NDWCT), as well as the insufficient utilization of potential energy, this paper proposes a potential energy recovery model. This model quantifies the recoverable potential energy in the rain zone based on the distribution characteristics of water droplets in the NDWCT. The recovered energy is then used to drive fans, improving both the resistance and heat transfer performance of the NDWCT. Using the NDWCT of a 1000 MW nuclear power unit as the research object, eight types of water collection plates with a coverage rate of 25 % were designed. These plates are used to collect circulating water to drive water turbines, which in turn power the fans. Calculations show that all designs can recover more than 450 kW of potential energy from falling water. After determining the recoverable potential energy, the thermal performance of NDWCT, HNDWCT (High-level water collecting natural draft wet cooling tower), NDWCT with dry-wet hybrid rain zone, and NDWCT with both dry-wet hybrid rain zone and potential energy recovery was compared under different environmental crosswind conditions. The results show that the performance of HNDWCT declines sharply under higher crosswind speeds. When the crosswind speed reaches 8 m/s, its heat exchange capacity decreases by 51.6 % compared to windless conditions, leaving it at only 63.1 % of the heat exchange capacity of NDWCT, with an outlet water temperature 3.66 degrees C higher than that of NDWCT. In contrast, the cooling tower modified with the dry-wet hybrid rain zones and potential energy recovery technology was less affected by crosswinds, with cooling capacity reductions of 5.4 % and 10.3 % at 4 m/s and 8 m/s crosswinds, respectively, whereas NDWCT exhibited reductions of 7.1 % and 11.1 %. Additionally, the former demonstrated superior performance under all crosswind conditions, the outlet water temperatures under windless, 4 m/s, and 8 m/s crosswind conditions decreased by 0.49 degrees C, 0.65 degrees C, and 0.53 degrees C, respectively, with heat exchange capacity improvements of 4.4 %, 6.3 %, and 5.3 %. Compared to traditional dry-wet hybrid rain zone towers, the cooling tower with the dry-wet hybrid rain zones and potential energy recovery technology is less affected by environmental crosswinds. The outlet water temperature decreased by 0.11 degrees C, 0.2 degrees C, and 0.17 degrees C under windless, 4 m/s, and 8 m/s wind conditions, respectively.
引用
收藏
页数:16
相关论文
共 50 条
  • [31] Comparative study on the cooling characteristics of high level water collecting natural draft wet cooling tower and the usual cooling tower
    Zhao, Yuanbin
    Sun, Fengzhong
    Long, Guoqing
    Huang, Xiaofeng
    Huang, Wenqiang
    Lyv, Dongqiang
    ENERGY CONVERSION AND MANAGEMENT, 2016, 116 : 150 - 164
  • [32] Analysis of Natural Draft Cooling Tower Aerodynamics Calculation Method
    Wang Liangzhong Northwest Electric Power Design Institute
    Electricity, 1996, (03) : 36 - 39
  • [33] Water Consumption Comparison Between a Natural Draft Wet Cooling Tower and a Natural Draft Hybrid Cooling TowerAn Annual Simulation for Luoyang Conditions
    Xia, Lin
    Li, Jishun
    Ma, Wei
    Gurgenci, Hal
    Guan, Zhiqiang
    Wang, Pei
    HEAT TRANSFER ENGINEERING, 2017, 38 (11-12) : 1034 - 1043
  • [34] Field test of the effect of crosswind on ventilation performance of a natural draft wet cooling tower
    Sun, F. (sfzh@sdu.edu.cn), 2012, Chinese Society for Electrical Engineering (32):
  • [35] An initial analysis on the energy-efficient performance of a natural draft wet cooling tower with CaCl2 solution for power plants
    Liu, Jiping
    Jiang, Yehui
    Chong, Daotong
    Yan, Junjie
    APPLIED THERMAL ENGINEERING, 2012, 48 : 249 - 255
  • [36] Evaluating vaporization heat, thermal performance, and efficiency of a natural draft wet cooling tower
    Song, Baohong
    Song, Yu
    PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART A-JOURNAL OF POWER AND ENERGY, 2022, 236 (06) : 1183 - 1191
  • [37] A 3D CFD model of a natural draft wet-cooling tower
    Silesian University of Technology, Institute of Thermal Technology, Konarskiego 22, 44-100 Gliwice, Poland
    Arch. Thermodyn., 2009, 4 (119-132):
  • [38] The effects of water droplet diameter distribution in the rain zone on the cooling capacity and water-splashing noise for natural draft wet cooling towers
    Jiang, Lei
    Han, Qiang
    Wang, Nini
    Gao, Ming
    He, Suoying
    Guan, Hongjun
    Tan, Xiaohui
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2021, 164
  • [39] Analysis and Evaluation of Cooling Characteristics of Natural Draft Dry Cooling Tower Based on the Cooling Approach
    Han H.
    Chen Q.
    Zhao Y.
    Wang L.
    Qin C.
    Li W.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2021, 41 (06): : 2212 - 2221
  • [40] Development and validation of a CFD model for numerical simulation of a large natural draft wet cooling tower
    Blain, Nicolas
    Belaud, Antoine
    Miolane, Matthieu
    APPLIED THERMAL ENGINEERING, 2016, 105 : 953 - 960